Installation Guide for COOPER models including: Neo Ray Cooper Lighting Solutions, Neo Ray, Cooper Lighting Solutions, Lighting Solutions, Solutions

IL52413024EN-Define-Patient-Grid-inst

NeoRay

1 giorno fa — This installation instruction is for the Define Patient Grid Ceiling. ... The purpose of this document is to provide sufficient detailed instructions for ...


File Info : application/pdf, 5 Pages, 1.30MB

PDF preview unavailable. Download the PDF instead.

NeoRay-Define-Patient-Grid-Installation-Instructions
Installation Instructions IL52411324EN

NeoRay

Installation Instructions ­ Define Patient Grid
IMPORTANT: Read carefully before installing product. Retain for future reference.
WARNING
Risk of Fire, Electrical Shock, Cuts or other Casualty Hazards- Installation and maintenance of this product must be performed by a qualified electrician. This product must be installed in accordance with the applicable installation code by a person familiar with the construction and operation of the product and hazards involved.
Risk of Fire and Electric Shock- Make certain power is OFF before starting installation or attempting any maintenance. Disconnect power at fuse or circuit breaker.
Risk of Fire- Minimum 90°C supply conductors.
Risk of Burn- Disconnect power and allow product to cool before handling or servicing.
Risk of Personal Injury- Due to sharp edges, handle with care.
Risk of Personal Injury- Do not install this product in locations such as gymnasiums, arenas, sports complexes, multi-purpose rooms and other locations where the fixture potentially will be subject to impacts from external sources. Doing so may result in cracking and/or breaking of the fixture which may cause pieces to fall from the application.
Risk of Personal Injury-Failure to comply with these instructions may result in death, serious bodily injury and property damage.

DISCLAIMER OF LIABILITY: Cooper Lighting Solutions assumes no liability for damages or losses of any kind that may arise from the improper, careless, or negligent installation, handling or use of this product.
IMPORTANT: Read carefully before installing fixture. Retain for future reference.
CAUTION: Fixture may become damaged and/or unstable if not installed properly.
NOTE: This product is not intended or approved as a medical device.
NOTE: Specifications and dimensions subject to change without notice.
NOTE: These instructions do not claim to cover all details or variations in the equipment, procedure or process described, nor to provide directions for every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for user purpose, please contact your nearest representative.
ATTENTION Receiving Department: Note actual fixture description of any shortage or noticeable damage on delivery receipt. File claim for common carrier (LTL) directly with carrier. Claims for concealed damage must be filed within 15 days of delivery. All damaged material, complete with original packing must be retained.

NeoRay

Define Patient | Grid

SAVE THESE INSTRUCTIONS
This installation instruction is for the Define Patient Grid Ceiling.
The purpose of this document is to provide sufficient detailed instructions for installation and basic troubleshooting.

INSTALLATION INSTRUCTIONS
Parts List
· Luminaire · Grid Bracket/Joiner (pre-installed in fixture) · Access Plate (pre-installed in housing) · Support Wire (by others) · Shielded Cable (by others) · Lens Removal Tool
Cross Section and Spacing Details

· Push-in Quick Connects or wire nuts · Alignment Pins (pre-installed in fixture) (Continuous runs only) · #8-32 2-1/2" Bolts and Nuts (Continuous runs only) · 9/64" Allen Wrench (by others) · 11/32" Flexible Nut Driver (by others) · #2 Phillips Screwdriver (by others)

Define Cross Section Dimensions

All Grid

W (Regressed)

X

Y

W

Define 5

6.000

5.000

4.680

1.000"
Y X Z
Regressed S12xRDR

Mounting Information - Extruded Trim Flange Details - Refer to submittal drawings for detailed flange information

Z 6.000

ETG 15/16" T-Grid

FTG 9/16" T-Grid

STG Slotted T-Grid

FTT 9/16" Tegular
T-Grid

ETT 15/16" Tegular
T-Grid

ITG 9/16" Interlude
T-Grid

Trimless Extruded Side

Warranties and Limitation of Liability
Please refer to www.cooperlighting.com/global/warranty for our terms and conditions.
Garanties et limitation de responsabilité
Veuillez consulter le site www.cooperlighting.com/global/warranty pour obtenir les conditions générales.
Garantías y Limitación de Responsabilidad
Visite www.cooperlighting.com/global/warranty para conocer nuestros términos y condiciones.

IL52413024EN page 2
month 2024

www.cooperlighting.com

Define Patient | Grid
Wiring Table
1st Circuit - Ambient
Power Supply (Input)

Black/Red (BK/RD) - Emergency Hot White/Red (WT/RD) - Emergency Neutral Black (BK) - Hot White (WT) - Neutral Green (GN) - Ground Violet (VT) - Dimming (+) Pink (PK) - Dimming (-)

Vivid Tune

2nd Circuit - Downlight Group 1 (Exam)

Power Supply (Input)

Black/Orange (BK/OR) - 2nd Circuit Hot White/Orange (WT/OR) - 2nd Circuit Neutral

Green (GN) - Ground

Orange (OR) - 2nd Circuit Dimming (+) Yellow (YL) - 2nd Circuit Dimming (-)

3rd Circuit - Downlight Group 2 (Reading)

Power Supply (Input)

Black/Blue (BK/BL) - 3rd Circuit Hot White/Yellow (WT/YL) - 3rd Circuit Neutral Green (GN) - Ground Yellow/Black (YL/BK) - 3rd Circuit Dimming (+) Brown (BR) - 3rd Circuit Dimming (-)

NeoRay
Violet/White (VT/WT) - 1st Circuit CCT (+) Pink/Black (PK/BK) - 1st Circuit CCT (-)

www.cooperlighting.com

IL52413024EN page 3
month 2024

NeoRay 1

Define Patient | Grid
2

Prepare grid width spacing according to chart above and local building code. Install fixture housing into grid. Ensure Grid brackets secure over grid and fixture is resting on grid tee. Unscrew access plate and slide to remove as shown.

Connect shielded cable to access plate. Connect electrical wiring as required using provided push-in connector. Ensure wires are fully secure in connectors.

3

4

Reattach access plate by sliding plate back into housing as shown and secure access plate by re-installing screw.

Secure fixture at both ends using support wire according to local building codes (not supplied).

Lens Removal

Insert Lens Removal Tool as shown, biased toward one side of the lens. Lifting from center of lens may cause lens to crack.

Tilt Lens Removal Tool as shown and gently pry lens up. Complete lens removal by hand.

IL52413024EN page 4
month 2024

www.cooperlighting.com

Define Patient | Grid Downlight Aiming
5

NeoRay 6

Remove the baffles using the provided lens removal tool or by gently using a flat head screw driver.

Rotate the downlight by gently turning the module to desired angle represented on the tray.

7

8

Adjust the tilt of the downlight gently with the heatsink to the desired angle represented on the bracket. Each notch is 5 degrees.

Replace the baffles.

Warranties and Limitation of Liability
Please refer to www.cooperlighting.com/global/warranty for our terms and conditions.
Garanties et limitation de responsabilité
Veuillez consulter le site www.cooperlighting.com/global/warranty pour obtenir les conditions générales.
Garantías y Limitación de Responsabilidad
Visite www.cooperlighting.com/global/warranty para conocer nuestros términos y condiciones.

www.cooperlighting.com

IL52413024EN page 5
month 2024



References