DEWALT D-CLIP Wire Component
Specifications
- Material: Carbon steel with Zinc Plating
- Approval: ICC-ES PMG-1786
- Code Listed: ICC-ES PMG-1786
Product Usage Instructions
Installation Specifications
- Description: D-Clip for 1/4 Anchor/Fastener
- Clearance Hole Size: 5/16
- Compatible with wire rope sizes DW1, DW2, and DW3
Installation Instructions
- Pass the Loop End Wire Attachment through the opening of the D-Clip.
- Select and install an appropriately sized anchor through the D-Clip into the base material following safety instructions.
Performance Data
Allowable Load Capacities for TOUGHWIRETM D-Clip Assemblies in Normal-Weight Concrete:
Anchor Description | Nominal Anchor Diameter (in.) | Minimum Embedment Depth (in.) | TOUGHWIRETM Size | lbs. (kN) | Mounting Orientation |
---|---|---|---|---|---|
D-Clip with 5/16 Clearance Hole (Cat. No. DTWDCLIP025) | 1/4 | 1 (25) | DW1 | 40 (0.2) | screw-bolt+TM Hex Washer Head |
GENERAL INFORMATION
D-CLIP
Wire Component
PRODUCT DESCRIPTION
The D-Clip Wire Component is a one piece clip that is used to fasten TOUGHWIRE™ to the mounting surface. Can be mounted on flat or sloped surfaces. TOUGHWIRE™ Loop End Wire Assembly products (sold separately) are looped through the D-Clip, then anchored to the structure with a variety of DEWALT® Anchors and Fasteners (sold separately).
GENERAL APPLICATIONS AND USES
- HVAC duct
- Electrical and mechanical systems
- Luminaires and lighting systems
- Plumbing & piping supports
- Signage and displays
- Office partitions and panels
FEATURES AND BENEFITS
- + Multiple Sizes – Available in 5/16 in. hole size and 1/2 in. hole size to pair with DEWALT® Anchors and Fasteners (sold separately).
- + Versatile Hanging – Can be mounted on flat or sloped surfaces.
- + ToughWire™ Compatible – Can be used with all three ToughWire™ wire diameters (DW1, DW2, and DW3, sold separately).
GUIDE SPECIFICATIONS
3 05 29 – Hangers and Supports for HVAC Piping and Equipment and 22 05 29 – Hangers and Supports for Plumbing Piping and Equipment. Hangers shall be the TOUGHWIRE™ system as supplied by DEWALT, Towson, MD. Hangers shall be installed by published instructions and the Authority Having Jurisdiction.
DEVICE MATERIAL
- Zinc Plated Carbon Steel
SIZE RANGE
- 5/16″ Hole
- 1/2″ Hole
SUITABLE MATERIAL PAIRING
- TOUGHWIRE™ Loop End Wire Assembly
CODE LISTED
- ICC-ES PMG-1786
MATERIAL SPECIFICATIONS
Hanger/Device Component | Component Material |
D-Clip | Carbon steel |
Zinc Plating | AsTM b633 (Fe/Zn5) Min. plating requirements for mild service condition |
INSTALLATION SPECIFICATIONS
Description | Clearance Hole Size | Suggested DEWALT® Anchor(s) |
D-Clip for 1/4″ Anchor/Fastener | 5/16″ | 1/4″ screw-bolt+ |
D-Clip for 3/8″ Anchor/Fastener | 1/2″ | 3/8″ screw-bolt+ |
All three wire rope sizes, DW1, DW2, and DW3, can be considered for use with both D-Clip parts. |
INSTALLATION INSTRUCTIONS
Step 1
Pass the Loop End Wire Attachment through the opening of the D-Clip.
- Note: A loop created with a TOUGHLOCK™ device may also be used.
- Note: Must follow safety instructions for tools.
Step 2
Select and install an appropriately sized anchor through the D-Clip into the base material to the required minimum embedment.
- Note: The two sides of the D-Clip should be compressed together when the anchor is fully installed.
- Note: Refer to the specific Anchor Installation Instructions
PERFORMANCE DATA
Allowable Load Capacities for TOUGHWIRE™ D-Clip Assemblies in Normal-Weight Concrete1,2,3,4,5,6,7,8
Anchor Description |
Nominal Anchor Diameter (in.) |
Minimum Embedment Depth in (mm) |
TOUGHWIRE™ Size | Minimum Concrete Compressive Strength = 3,000 psi | |
lbs. (kN) | |||||
Mounting Orientation | |||||
![]() | ![]() | ||||
D-Clip with 5/16″ Clearance Hole (Cat. No. DTWDCLIP025) | |||||
screw-bolt+™ Hex Washer Head |
1/4″ |
1 (25) | DW1 | 40 (0.2) | 40 (0.2) |
DW2 | 125 (0.6) | 125 (0.6) | |||
DW3 | 300 (1.3) | 300 (1.3) | |||
spike® Mushroom Head |
1/4″ |
1 (25) | DW1 | 40 (0.2) | 40 (0.2) |
DW2 | 125 (0.6) | 125 (0.6) | |||
DW3 | 195 (0.9) | 300 (1.3) | |||
1-1/4 (31) | DW3 | 275 (1.2) | 300 (1.3) | ||
Power-stud®+ sD1 |
1/4″ |
1-1/8 (28) | DW1 | 40 (0.2) | 40 (0.2) |
DW2 | 125 (0.6) | 125 (0.6) | |||
DW3 | 300 (1.3) | 300 (1.3) | |||
UltraCon® Hex Washer Head / TrimFit Hex Head |
5/16″ |
1 (25) | DW1 | 40 (0.2) | 40 (0.2) |
DW2 | 125 (0.6) | 125 (0.6) | |||
DW3 | 185 (0.8) | 300 (1.3) | |||
1-3/4 (45) | DW3 | 300 (1.3) | 300 (1.3) | ||
D-Clip with 1/2″ Clearance Hole (Cat. No. DTWDCLIP044) | |||||
screw-bolt+™ Hex Washer Head |
3/8″ |
1-1/2 (38) | DW1 | 40 (0.2) | 40 (0.2) |
DW2 | 125 (0.6) | 125 (0.6) | |||
DW3 | 300 (1.3) | 300 (1.3) | |||
spike® Mushroom Head |
3/8″ |
1-3/4 (45) | DW1 | 40 (0.2) | 40 (0.2) |
DW2 | 125 (0.6) | 125 (0.6) | |||
DW3 | 300 (1.3) | 300 (1.3) | |||
Power-stud®+ sD1 |
3/8″ |
1-5/8 (41) | DW1 | 40 (0.2) | 40 (0.2) |
DW2 | 125 (0.6) | 125 (0.6) | |||
DW3 | 300 (1.3) | 300 (1.3) | |||
1. Tabulated load values are for anchors installed in uncracked concrete. Concrete compressive strength must be at taminimum at the time of installation. 2. In unshaded cells, the capacity of the wire rope controls the failure in the assembly. 3. In shaded cells, the capacity of the anchor in concrete controls the failure in the assembly. 4. Allowable capacities are based on a safety factor of 4.0. 5. The minimum base material thickness should be 3-1/2 inches. 6. Tabulated data is based on a minimum spacing distance of 2-3/4 inches for 1/4″ and 5/16″ diameter anchors and a minimum spacing distance of 4 inches for 3/8″ diameter anchors. 7. Tabulated data is based on a minimum edge distance of 3-1/2 inches. 8. Nominal anchor length must exceed the minimum embedment depth + 1/4 inch. |
CONDITIONS OF USE
ORDERING INFORMATION
D-Clip | ||||
Cat. No. | Description | Clearance Hole Diameter (in.) | Pack Qty. | Carton Qty. |
DTWDCLIP025 | D-Clip for 1/4″ Anchor/Fastener | 5/16″ | 50 | 300 |
DTWDCLIP044 | D-Clip for 3/8″ Anchor/Fastener | 1/2″ | 50 | 300 |
TOUGHWIRE™ Loop End
Cat. No. | TOUGHWIRE™ Size | TOUGHWIRE™ Cable Length (ft) | Pack Qty. | Carton Qty. |
DTW0106LE | DW1 | 6 | 75 | 300 |
DTW0112LE | DW1 | 12 | 50 | 200 |
DTW0120LE | DW1 | 20 | 25 | 100 |
DTW0206LE | DW2 | 6 | 25 | 100 |
DTW0212LE | DW2 | 12 | 25 | 100 |
DTW0220LE | DW2 | 20 | 25 | 100 |
DTW0235LE | DW2 | 35 | 25 | 100 |
DTW0306LE | DW3 | 6 | 25 | 100 |
DTW0312LE | DW3 | 12 | 25 | 100 |
DTW0320LE | DW3 | 20 | 10 | 40 |
DTW0335LE | DW3 | 35 | 15 | 30 |
TOUGHLOCK™ Wire Locking Device
Cat. No. | TOUGHWIRE™ Size | Pack Qty. | Carton Qty. |
DTWTOUGHLOCK01 | DW1 | 100 | 1000 |
DTWTOUGHLOCK02 | DW2 | 50 | 500 |
DTWTOUGHLOCK03 | DW3 | 25 | 150 |
STRUTLOCK™ Wire Locking Devices
Cat. No. | TOUGHWIRE™ Size | Pack Qty. | Carton Qty. |
DTWsTrUTLOCK02 | DW2 | 15 | 90 |
DTWsTrUTLOCK03 | DW3 | 10 | 60 |
SQUARELOCK™ Wire Locking Device
Cat. No. | TOUGHWIRE™ Size | Pack Qty. | Carton Qty. |
SQUARELOCK™ Device Without EPDM Gasket | |||
DTWsQLOCK02 | DW2 | 50 | 300 |
DTWsQLOCK03 | DW3 | 20 | 120 |
SQUARELOCK™ Device With EPDM Gasket | |||
DTWsQLOCKP02 | DW2 | 50 | 300 |
DTWsQLOCKP03 | DW3 | 20 | 120 |
TOUGHWIRE™ Cable Cutter
C | Description | Pack Qty. | Carton Qty. |
DTWHANDCUTTEr | Cutters for DW1, DW2 and DW3 TOUGHWIrE™ Cable | 1 | 10 |
TECHNICAL GUIDE – CABLE HANGERS ©2025 DEWALT – REV. A
FAQS
- What wire rope sizes are compatible with the D-Clip?
All three wire rope sizes, DW1, DW2, and W3, can be considered for use with both D-Clip parts. - What is the minimum concrete compressive strength required for installation?
The minimum concrete compressive strength required is 3,000 psi.