DESCO-logo

DESCO TB-3099 Ground Hub Continuous Monitor

DESCO-TB-3099-Ground-Hub-Continuous-Monitor-product

Specifications

  • Model Numbers: 19203 (Type B – North America, Japan), 19204 (Type G – Southeast Asia, UK)
  • Country of Origin: United States of America
  • Number of Verified Ground Points: 13 in PASS condition
  • Components: Ground Hub Continuous Monitor, 6 Socket Head Screws (#10-32 x 1/4), 6 Split Lock Washers (#10), 1 Hex L-Key (5/32)

Product Usage Instructions

Installation

  1. Plug the Ground Hub Continuous Monitor into a proper electrical outlet.
  2. The Ground LED will illuminate green if the outlet’s wiring is correct and the path-to-equipment ground via the equipment grounding conductor is intact.
  3. The Ground LED will illuminate red and the audible alarm will sound if the outlet’s wiring is incorrect or the path to equipment ground via the equipment grounding conductor is not intact.

Operation
Use the included socket head screws and split lock washers to  connect ring terminals or banana jacks to the Ground Hub. Ring terminals may also be connected to the ground post.

Features and Components

Desco 19203 Ground Hub Continuous Monitor
Ground LED: Green when wired correctly, Red when not
Desco 19204 Ground Hub Continuous Monitor
Using the Ground Hub Continuous Monitor
Illuminates green when AC outlet is properly wired and path to equipment ground is intact; Red light and alarm forissues
Calibration  
Note: Calibration should only be performed by individuals familiar with voltage hazards. Ensure proper referencing of neutral and ground for 220 VAC configurations to avoid a FAIL result.

Ground Hub Continuous Monitor Installation, Operation, and Maintenance

Figure 1. Desco 19203 Ground Hub Continuous Monitor

DESCO-TB-3099-Ground-Hub-Continuous-Monitor-fig-00

Description

  • The Desco Ground Hub Continuous Monitor confirms the integrity of the resistance path from the common ground point to electrical ground. It is designed in accordance with ESD TR 12-01 to “monitoring equipment ground connections.” When the Ground
  • Hub Continuous Monitor is plugged into an AC outlet, the green LED illuminates when both the outlet’s wiring is correct and the path to equipment ground via the equipment grounding conductor is intact. The monitor provides 13 verified ground points when in  PASS condition. The red LED illuminates when either the outlet’s wiring is incorrect or the path-to-equipment ground is defective.
  •  The outlet ground line is tested by measuring voltage between it and the neutral line. It is normal to have a few volts of AC induced on the neutral line. If the Ground Hub Continuous Monitor measures only a few volts, the ground line to neutral impedance is low and the ground line would make a suitable ESD ground point. If the monitor measures more than just a few volts between ground and neutral, this indicates either that they are not referenced to each other or that the outlet and associated wiring should be checked for loose connections. In this case, the Ground Hub Continuous Monitor will sound a warning alarm and display a red FAIL indication and should not be used for an ESD grounding point until corrected.

Use the Ground Hub Continuous Monitor to fulfill the S6.1 Section 6.3.1 requirement. “The hot, neutral, and equipment grounding conductor shall be verified to be in the proper wiring orientation in accordance with the National Electric Code (ANS/NFPA-70).” (Grounding ANSI/ESD S6.1 section 6.3.1 Equipment Grounding Conductor)

The Ground Hub Continuous Monitor is available in two models:

DESCO-TB-3099-Ground-Hub-Continuous-Monitor-fig- (5)

Packaging

  • 1 Ground Hub Continuous Monitor
  • 6 Socket Head Screw, 10-32 x 1/4″
  • 6 Split Lock Washer, #10
  • 1 Hex L-Key, 5/32″

DESCO-TB-3099-Ground-Hub-Continuous-Monitor-fig- (1)

Figure 2. Ground Hub Continuous Monitor packaging contents

Features and Components

DESCO-TB-3099-Ground-Hub-Continuous-Monitor-fig- (2)

Figure 2. Desco 19203 Ground Hub Continuous Monitor features and components

DESCO-TB-3099-Ground-Hub-Continuous-Monitor-fig- (3)

Figure 3. Desco 19204 Ground Hub Continuous Monitor features and components

  • A. Ground LED: Illuminates green when the AC outlet is properly wired and its path to equipment ground via the equipment ground conductor is intact. Illuminates red and audible alarm sounds when the AC outlet is not properly wired and its path to equipment ground via the equipment ground conductor is broken.
  • B. Ground Hub: Provides 12 verified ground points via six banana jacks and six screws for #8 ring terminals.
  • C. Ground Post: Provides a verified ground point. Bond to the 09842 Multi-Ground Hub to create an additional 12 ground points.

Installation

  1. Plug the Ground Hub Continuous Monitor into a proper electrical outlet.
  2. The Ground LED will illuminate green if the outlet’s wiring is correct and the path-to-equipment ground via the equipment grounding conductor is intact. The Ground LED will illuminate red and the audible alarm will sound if the outlet’s wiring is incorrect or the path to equipment ground via the equipment grounding conductor is not intact.
Operation
Use the included socket head screws and split lock washers to connect ring terminals (not included) or the banana jacks (not included) to connect banana plugs to the Ground Hub. Ring terminals may also be connected to the ground post.
DESCO-TB-3099-Ground-Hub-Continuous-Monitor-fig- (4)
Figure 4. Using the Ground Hub Continuous Monitor
Calibration
Note
: The following procedure should only be  performed by someone familiar with voltage hazards. This procedure will work for 220 VAC configurations as long as the neutral and ground are referenced. 220 VAC produced with out-of-phase 110 VAC-to-Ground-to-110 VAC will produce a FAIL result.
  1. Isolate the ground plug from the tester by inserting it into a 3 to 2 plug adapter.
  2.  Connect a 5 kilohm resistor between the supply ground and tester ground. The Ground LED should illuminate green until the resistor is removed. This test confirms the pass limit for the neutral-to-ground resistance.
  3. Connect a 12.5 kilohm resistor between the supply ground and tester ground. The Ground LED should illuminate red and sound the audible alarm until the resistor is removed. This test confirms the fail limit for the neutral-to-ground resistance.
Specifications
  • Input Voltage and Frequency 100-240 VAC, 50/60 Hz
  • Operating Temperature 50 to 95°F (10 to 35°C)
  • Environmental Requirements Indoor use only at altitudes less than 6500 ft. (2 km) Maximum relative humidity of 80% up to 85°F (30°C) decreasing linearly to 50% @ 85°F (30°C)
  • Equipment Ground  Conductor Test Limit 10 kilohms (±25%)
  • Dimensions 19203: 3.0″ x 2.0″ x 1.4″ (76 mm x 51 mm x 36 mm) 19204: 3.1″ x 2.1″ x 2.0″ (79 mm x 53 mm x 50 mm)
  • Weight 0.4 lbs (181 g)
  • Country of Origin United States of America

Limited Warranty, Warranty Exclusions, Limit of Liability and RMA Request Instructions See the Desco Warranty – Desco.com/Limited-Warranty.aspx

FAQs

Q: What should I do if the red LED illuminates on the Ground Hub Continuous Monitor?A: If the red LED illuminates, it indicates incorrect wiring or a defective path to equipment ground. Check your electrical connections and wiring for issues.

Q: Can I use ring terminals or banana jacks with the Ground Hub?
A: Yes, you can use ring terminals or banana jacks with the Ground Hub to establish connections for monitoring equipment ground

Q: How many verified ground points does the Ground Hub provide?
A: The Ground Hub provides 13 verified ground points when in PASS condition.

Documents / Resources

DESCO TB-3099 Ground Hub Continuous Monitor [pdf] Instruction Manual
19203, 19204, TB-3099 Ground Hub Continuous Monitor, TB-3099, Ground Hub Continuous Monitor, Hub Continuous Monitor, Continuous Monitor, Monitor