Delta-logo

DELTA DVP04TC-H2 Temperature Measurement Module

DELTA-DVP04TC-H2-Temperature-Measurement-Module-product-image

Product Information

The DVP04TC-H2 is an open-type temperature measurement module. It is designed to be installed in a control cabinet that is free of airborne dust, humidity, electric shock, and vibration. The module should be protected with a safeguard to prevent unauthorized access or accidents that may damage the module. It is important to ensure that AC power is not connected to any of the I/O terminals to avoid serious damage. The module should be properly grounded to prevent electromagnetic interference. Additionally, the correct setting of the thermocouple temperature sensor is crucial to avoid errors.

The product profile and dimensions are as follows:

  • DIN rail (35mm)
  • Connection port for extension module
  • Model name
  • POWER, ERROR, A/D indicator
  • DIN rail clip
  • Terminals
  • Mounting hole
  • I/O terminals
  • Mounting port for extension module

The I/O terminal layout is as follows:

24 V   0V     D+     SL D     D-     L+     L-
RS-485 CH1
SL D
L+
L-
CH2
SL D     L+     L-
CH3
-1-
SL D
L+
L-
CH4
The external wiring instructions are as follows:
  1. For thermocouple wiring, use shielded cable and connect it to the appropriate terminals based on the thermocouple type.
  2. Ensure proper grounding by connecting the system ground terminal to the system earth point and grounding the system contact or connecting it to the cover of the power distribution cabinet.
  3. Separate the analog input wiring from other power cables or wirings that may cause interference.

The electrical specifications of the temperature measurement module are:

  • Power supply voltage: 24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)
  • Analog output channel: 4 channels/module

Product Usage Instructions

  1. Ensure that the control cabinet where the DVP04TC-H2 module is installed is free of airborne dust, humidity, electric shock, and vibration.
  2. Install a safeguard on the control cabinet to prevent unauthorized access and accidents that may damage the module.
  3. Do not connect AC power to any of the I/O terminals to avoid serious damage.
  4. Double-check all wiring before powering up the DVP04TC-H2 module.
  5. After disconnecting the module, avoid touching any terminals for at least a minute.
  6. Properly ground the ground terminal on the DVP04TC-H2 module to prevent electromagnetic interference.
  7. Keep the wire as short as possible when wiring a platinum resistance thermometer (RTD) to the controller.
  8. Route power wires as far as possible from load wires to prevent interference and induced noise.
  9. Ensure that the setting of the thermocouple temperature sensor in CR#1 is correct to avoid serious errors.

DVP04TC-H2 is able to receive 4 points 0~150mV voltage input of thermocouple temperature sensors (J-type, K-type, R-type, S-type, T-type, E-type, N-type) and convert them into 24-bit digital signals. Besides, through FROM/TO instructions in DVP-EH2 MPU program, the data in DVP04TC-H2 can be read or written. There are 49 16-bit control registers (CR) in it. DVP04TC-H2 displays temperatures in Celsius (resolution: 0.1°C) and Fahrenheit (resolution: 0.18°F).

  • This Instruction Sheet only provides descriptions for electrical specifications, general specifications, installation & wiring. Other detail information about programming and instruction’s, please see “DVP-PLC Application Manual: Programming”. For more information about the optional peripherals, please see individual product instruction sheet or “DVP-PLC Application Manual Special Modules”.
  • DVP04TC-H2 is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration. To prevent
    non-maintenance staff from operating DVP04TC-H2, or to prevent an accident from damaging DVP04TC-H2, the control cabinet in which DVP04TC-H2 is installed should be equipped with a safeguard. For example, the control cabinet in which DVP04TC-H2 is installed can be unlocked with a special tool or key.
  • DO NOT connect AC power to any of I/O terminals, otherwise serious damage EN  DO NOT connect AC power to any of I/O terminals, otherwise serious damage  may occur. Please check all wiring again before DVP04TC-H2 is powered up. After DVP04TC-H2 is disconnected, Do NOT touch any terminals in a minute.
    Make sure that the ground terminal on DVP04TC-H2 is correctly grounded in order to prevent electromagnetic interference.
  • Please keep the wire as short as possible when wiring a platinum resistance
    thermometer (RTD) to the controller and please route power wires as far as possible from load wires to prevent interference and induced noise.
  • Please make sure the setting of thermocouple temperature sensor in CR#1 is correct, or it will cause serious errors.

Product Profile & Dimension

DELTA-DVP04TC-H2-Temperature-Measurement-Module-1

Unit: mm

  1. DIN rail (35mm)
  2. Connection port for extension module
  3. Model name
  4. POWER, ERROR, A/D indicator
  5. DIN rail clip
  6. Terminals
  7. Mounting hole
  8. I/O terminals
  9. Mounting port for extension module

 I/O Terminal Layout

DELTA-DVP04TC-H2-Temperature-Measurement-Module-2

External Wiring

DELTA-DVP04TC-H2-Temperature-Measurement-Module-3

  1. The wiring used for analog input should adopts the connection cable or shielding cable of thermocouple temperature sensor J-type / K-type / R-type / S-type / T-type / E-type / N-type and should be separated from other power cable or wirings that may cause interference. The screw torque of the terminal should be 1.95 kg-cm (1.7 in-lbs).
  2. Terminal SLD is the ground location for noise suppression.
  3. Please connect the terminal on both the power module and DVP04TC-H2 to the system earth  point and ground the system contact or connect it to the cover of power distribution cabinet.
    Note: DO NOT wire empty terminal. Use 60/75°C copper conductor only.

Electrical Specifications

Temperature measurement moduleExplanation
Power supply voltage24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)
Analog output channel4 channels/module
Applicable sensor typesJ-type, K-type, R-type, S-type, T-type, E-type, N-type Floating thermocouple sensor, 0~150mV voltage input.
Range of input temp.See the table in section Temperature / Digital Curve
Range of digital conversionSee the table in section Temperature / Digital Curve
Resolution0.1°C/0.18°F*1
Overall accuracy±0.6% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F
Response time200ms × the number of channels
IsolationIsolation between digital circuits and analog circuits. Isolation between channels. 500VDC between digital circuits and Ground 500VDC between analog circuits and Ground 500VDC between analog circuits and digital circuits 500VDC between 24VDC and Ground
Digital data format15 significant bits out of 16 bits are available; in 2’s complement
Average functionYes; available for setting up in CR#2 ~ CR#5; range: K1 ~ K100
Self-diagnosisUpper and lower bound detection/channel
Communication mode (RS-485)Supported, including ASCII/RTU mode. Default communication format: 9600, 7, E, 1, ASCII; refer to CR#32 for details on the communication format.

Note1: RS-485 cannot be used when connected to CPU series PLCs.

Note2: Use extension module wizard in ISPSoft to search or modify the control register (CR) in the modules.

When connected to DVP-PLC MPU inThe modules are numbered from 0 to 7 automatically by their distance from MPU. No. 0 is the closest to MPU and No. 7 is the furthest.
seriesMaximum 8 modules are allowed to connect to MPU and will not occupy any digital I/O points.

The unit of temperature would be displayed as 0.1°C/0.1°F. If the temperature unit is set to be Fahrenheit, the second decimal place would not be shown.

Other Specifications

Power supply
Max. rated power consumption24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%), 2.5W supplied by external power.
Environment
Operation/storage
  1. Operation: 0°C~ 55°C (Temperature), 5 ~ 95% (Humidity), pollution degree 2
  2. Storage: -25°C~ 70°C (Temperature), 5 ~ 95%(Humidity)
Vibration/shock immunityStandard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)

 Control Register

CR#1: The working mode of the 4 channels in the sensors selected by the temperature measurement module. There are 8 modes (J-type, K-type, R-type, S-type, T-type, E-type, N-type, 0~150mV) for each channel which can be set up separately. For example, if the user needs to set up CH1: mode 0 (b2 ~ b0 = 100); CH2: mode 1 (b5 ~ b3 = 001); CH3: mode 0 (b8 ~ b6 = 000) and CH4: mode 1 (b11 ~ b9 = 001), CR#1 has to be set as H0208 and the higher bits (b12 ~ b15) is CH1~CH4 Disable/Enable. The default value = H’0000.

CR#Attrib.Register nameExplanation
#0ORModel nameSet up by the system.
DVP04TC-H2 model code = H’6403.
You can read the model name from the program and see if the extension module exists.
 

 

 

 

 

 

 

#1

 

 

 

 

 

 

 

O

 

 

 

 

 

 

 

R/W

 

 

 

 

 

 

 

Thermocouple type

CH1 Disable/Enable:bit12 CH2 Disable/Enable:bit13 CH3 Disable/Enable:bit14 CH4 Disable/Enable:bit15 1=Disable,0 =Enable

Take the setting of CH1 for example:

  1. When (b2, b1, b0) is set as (0,0,0), choose J-type
  2. When (b2, b1, b0) is set as (0,0,1), choose K-type
  3. When (b2, b1, b0) is set as (0,1,0), choose R-type
  4. When (b2, b1, b0) is set as (0,1,1), choose S-type
  5. When (b2, b1, b0) is set as (1,0,0), choose T-type
  6. When (b2, b1, b0) is set as (1,0,1), choose E-type
  7. When (b2, b1, b0) is set as (1,1,0), choose N-type
  8. When (b2, b1, b0) is set as (1,1,1), choose 0 ~ 150mV
CR#1: The working mode of the 4 channels in the sensors selected by the temperature measurement module. There are 8 modes (J-type, K-type, R-type, S-type, T-type, E-type,

N-type, 0~150mV) for each channel which can be set up separately. For example, if the user needs to set up CH1: mode 0 (b2 ~ b0 = 100); CH2: mode 1 (b5 ~ b3 = 001); CH3: mode 0 (b8

~ b6 = 000) and CH4: mode 1 (b11 ~ b9 = 001), CR#1 has to be set as H0208 and the higher bits (b12 ~ b15) is CH1~CH4 Disable/Enable. The default value = H’0000.

#2OR/WCH1 average time 

Range of settings in CH1 ~ CH4: K1 ~ K100. Default

=K10.

#3OR/WCH2 average time
#4OR/WCH3 average time
#5OR/WCH4 average time
#6XRAverage °C temp. measured at CH1 

 

Average Celsius temperature measured at CH1 ~ CH4.
Unit: 0.1°C

#7XRAverage °C temp. measured at CH2
#8XRAverage °C temp. measured at CH3
#9XRAverage °C temp. measured at CH4
CR#6 ~ CR#9: The average Celsius temperature measured at CH1 ~ CH4 obtained from the average time settings in CR#2 ~ CR#5.
#10XRAverage °F temp. measured at CH1Average Fahrenheit temperature measured at CH1 ~ CH2.
Unit: 0.1°F
#11XRAverage °F temp. measured at CH2
#12XRAverage °F temp. measured at CH3Average Fahrenheit temperature measured at CH3 ~ CH4.
Unit: 0.1°F
#13XRAverage °F temp. measured at CH4
CR#10 ~ CR#13: The average Fahrenheit temperature measured at CH1 ~ CH4 obtained from the average time settings in CR#2 ~ CR#5.
#14XRPresent °C temp. measured at CH1 

 

Present Celsius temperature measured at CH1 ~ CH4.
Unit: 0.1°C

#15XRPresent °C temp. measured at CH2
#16XRPresent °C temp. measured at CH3
#17XRPresent °C temp. measured at CH4
#19XRPresent °F temp. measured at CH1 

 

Present Fahrenheit temperature measured at CH1 ~ CH4.
Unit: 0.1°F

#20XRPresent °F temp. measured at CH2
#21XRPresent °F temp. measured at CH3
#22XRPresent °F temp. measured at CH4
#24OR/WOFFSET value of CH1Adjustable OFFSET settings at CH1 ~ CH4. Range: -1,000 ~ +1,000
Default = K0 Unit: 0.1°C
#25OR/WOFFSET value of CH2
#26OR/WOFFSET value of CH3
#27OR/WOFFSET value of CH4
#30XRError statusRegister for storing all error status. See the table of error status for more information.
#31OR/WCommunication address settingFor setting RS-485 communication address. Range: 01 ~ 254, Default = K1.
#32OR/WCommunication format setting6 communication speeds: 4,800 bps /9,600 bps /19,200 bps / 38,400 bps /57,600 bps /115,200 bps. Data formats include:
ASCII: 7, E, 1/ 7,O,1 / 8,E,1 / 8,O,1 / 8,N,1 / 7,E,2 / 7,O,2 / 7,N,2 / 8,E,2 / 8,O,2 / 8,N,2

RTU: 8, E, 1 / 8,O,1 / 8,N,1 / 8,E,2 / 8,O,2 / 8,N,2 Default: ASCII,9600,7,E,1(CR#32=H‘0002)

Please refer to✽CR#32 at the bottom of the page for more details.

#33OR/WReturning to default settingTake the setting of CH1 for example: b0 is reserved. b1 is reserved.
When b2 is set as 1, all the settings will return to default settings.
ERR LED definition: default of b12 ~ b15 = 1111
  1. When b12 = 1, CH1 wiring to empty external contact, ERR LED will flash.
  2. When b13 = 1, CH2 wiring to empty external contact, ERR LED will flash.
  3. When b14 = 1, CH3 wiring to empty external contact, ERR LED will flash.
  4. When b15 = 1 CH2 wiring to empty external contact, ERR LED will flash.
#34ORFirmware versionDisplaying the current firmware version in hex; e.g.
version 1.0A is indicated as H’010A
#35 ~ #48For system use
Symbols: ○: Latched. ╳: Non-latched.
R: Able to read data by FROM instruction or RS-485 communication. W: Able to write data by TO instruction or RS-485 communication.
  • Reset Module (Firmware V4.08 or above): Having connected the external power 24V, write the reset code H’4352 in CR#0, then disconnect and reboot to complete the setup.
  • CR#32 Communication Format Setting:
    • Firmware V4.06 (and lower): Data format (b11~b8) is not available, ASCII format is 7, E, 1 (code H’00xx), RTU format is 8, E, 1 (code H’C0xx/H’80xx).
    • Firmware V4.07 (and higher): Refer to the following table for setup. For new communication format, please take note that modules in the original code H’C0xx/H’80xx is changed to 8E1 for RTU.
b15 ~ b12b11 ~ b8b7 ~ b0
ASCII/RTU & High/Low Bit Exchange of CRCData FormatCommunication Speed
Description
H’0ASCIIH’07,E,1*1H’67,E,2*1H’014800 bps
 

H’8

RTU,

No High/Low Bit Exchange of CRC

H’18,E,1H’78,E,2H’029600 bps
H’2H’87,N,2*1H’0419200 bps
 

H’C

RTU,

High/Low Bit Exchange of CRC

H’38,N,1H’98,N,2H’0838400 bps
H’47,O,1*1H’A7,O,2*1H’1057600 bps
H’58.O,1H’B8,O,2H’20115200 bps

ex: To setup 8N1 for RTU (High/Low Bit Exchange of CRC), communication speed is 57600 bps, write H’C310 in CR #32.
Note *1. Supports ASCII mode ONLY.

  • CR#0 ~ CR#34: The corresponding parameter address H’4096 ~ H’40B8 are for users to read/write data by RS-485 communication. When using RS-485, the user has to separate the module with MPU first.
  • Function: H’03 (read register data); H’06 (write 1 word datum into register); H’10 (write many word data into register).
  • Latched CR should be written by RS-485 communication to stay latched. CR will not be latched if written by MPU through TO/DTO instruction; ; however, when using TO/DTO instruction to modify the PID control registers, all latched CR will stay latched.

CR#30: Error status (see the table below)

Error statusValueb15 ~ b12b11b10b9b8b7b6b5b4b3b2b1b0
Abnormal powerK1000000000001
supply(H’1)
Wiring to emptyK2000000000010
external contact(H’2)
Memory self-testK16000000010000
Fail(H’10)
CH1 wiring to

empty external contact

K256 (H’100)Reserved 

0

 

0

 

0

 

1

 

0

 

0

 

0

 

0

 

0

 

0

 

0

 

0

CH2 wiring to empty external

contact

K512 (H’200) 

0

 

0

 

1

 

0

 

0

 

0

 

0

 

0

 

0

 

0

 

0

 

0

CH3 wiring to

empty external contact

K1024 (H’400) 

0

 

1

 

0

 

0

 

0

 

0

 

0

 

0

 

0

 

0

 

0

 

0

CH4 wiring to empty external

contact

K2048 (H’800) 

1

 

0

 

0

 

0

 

0

 

0

 

0

 

0

 

0

 

0

 

0

 

0

Note: Each error status is determined by the corresponding bit (b0 ~ b11) and there may be more than 2 errors occurring at the same time. 0 = normal; 1 = error.

PID Control Registers

CR#LatchedRegister contentExplanation
CH1CH2CH3CH4
#51#71#91#111OR/WTemperature SVDefault = K0.
#52#72#92#112OR/WSampling time (s)Range: K1 ~ K30 (s). Default = K2.
#53#73#93#113OR/WKPDefault = K121.
#54#74#94#114OR/WKIIntegral constant, Default = K2,098.
#55#75#95#115OR/WKDDerivative constant, Default = K-29.
#56#76#96#116OR/WUpper limit of I valueRange: K-32,760 ~ K32,760. Default = K0.
#57#77#97#117OR/WLower limit of I valueRange: K-32,760 ~ K32,760.
Default = K0.
#58#78#98#118XRI valueCurrent accumulated offset value. Default = K0.
#59#79#99#119OR/WHeating/cooling control0: Heater, 1: Cooler. Default = K0.
#60#80#100#120OR/WUpper limit of outputRange: K-32,760 ~ K32,760.
Default = K4,000.
#61#81#101#121OR/WLower limit of outputRange: K-32,760 ~ K32,760.
Default = K0.
#62#82#102#122XROutput percentage (%)Range: K0 ~ K1,000 (Unit: 0.1%).
Default = K0.
#63#83#103#123XROutput width (ms)Width of control output, Unit: ms. Default = K0.
#64#84#104#124XROutput cycle (ms)Cycle of control output, Unit: ms. Default = K0.
#65#85#105#125XROutput volumeDefault = K0.
#66#86#106#126XR/WPID_Run/Stop0: Stop, 1: Run. Default = K0.
#67#87#107#127XR/WAuto Tune0: Disabled, 1: Auto-tuning. Default = K0.
  • The CR#51 ~ CR#127 listed above do not support RS-485 read/write.
  • When using TO/DTO instruction to modify PID control registers, latched CR and PID control registers will stay latched.

Temperature / Digital Curve

Temperature Measurement Mode (°C/°F):

DELTA-DVP04TC-H2-Temperature-Measurement-Module-4

Documents / Resources

DELTA DVP04TC-H2 Temperature Measurement Module [pdf] Instruction Manual
DVP-0070630-03, DVP04TC-H2, DVP04TC-H2 Temperature Measurement Module, Temperature Measurement Module, Measurement Module

References

Leave a comment

Your email address will not be published. Required fields are marked *