1. Einleitung
This manual provides essential information for the safe and efficient installation, operation, and maintenance of your EARU Electric 3-Phase Auto Transfer Switch (ATS) - 440V 63A. Please read this manual thoroughly before installation and operation to ensure proper functionality and to prevent damage or injury.
The ATS is designed to provide uninterrupted power by automatically transferring loads between phases in a three-phase supply system. It features intelligent monitoring and protection against phase failure, over/under voltage, and overcurrent conditions, ensuring the stability and safety of connected equipment.
2. Sicherheitshinweise
WARNUNG: Stromschlaggefahr. Installation und Wartung dürfen nur von qualifiziertem Fachpersonal durchgeführt werden.
- Vor der Installation oder Wartung des ATS muss immer die Stromzufuhr unterbrochen werden.
- Stellen Sie sicher, dass alle Verkabelungen den lokalen und nationalen Elektrovorschriften entsprechen.
- Überprüfen Sie die korrekte VoltagPrüfen Sie die Nennwerte und die Stromstärke, bevor Sie das Gerät anschließen.
- Das Gerät darf nicht bedient werden, wenn es beschädigt erscheint.
- Halten Sie Kinder von elektrischen Geräten fern.
3. Produktüberschreitungview
The EARU Electric 3-Phase ATS is an intelligent device that continuously monitors your three-phase power supply. It automatically switches single-phase loads to a healthy phase in case of a phase failure or imbalance, ensuring continuous operation of critical equipment.
3.1. Packungsinhalt
- 1 x EARU Electric 3-Phase Auto Transfer Switch (ATS)
3.2. Frontplatte und Anzeigen

Bildbeschreibung: The front panel of the ATS features a digital display showing voltage for L1, L2, L3 phases and current for L1. Below the display are indicators for Power, Over-voltage (>V), Under-voltage (<V), and Over-current (>I). Control buttons include 'SET' (Menu key), 'Digit+/Up', 'Digit-/Down', and 'Manual ON/OFF' (Power button).
The digital display provides real-time voltage readings for each phase (L1, L2, L3) and the current for L1. Status indicators alert you to the operational state and any detected faults:
- Leistung: Output indication.
- >V: Überlautstärketage-Anzeige.
- <V: Untervolumentage-Anzeige.
- >ICH: Over-current indication.
Control buttons allow for parameter settings and manual operation:
- EINSTELLEN: Menu key for accessing settings.
- Digit+/Up: Increases value or navigates up in menus.
- Digit-/Down: Decreases value or navigates down in menus.
- Manuell EIN/AUS: Power button for manual control.
4. Einrichtung und Installation
The ATS is designed for standard DIN rail mounting. Ensure sufficient space for ventilation and wiring connections.
4.1. Schaltplan

Bildbeschreibung: A detailed wiring diagram illustrates the connection points for the ATS. The top terminals are labeled 'IN' with connections for N, L1, L2, L3. The bottom terminals are labeled 'OUT' with connections for N and L1. The diagram shows how to connect the three-phase input to the ATS and how a single-phase load (L1 and N) is connected to the output, with internal connections for phase monitoring and switching.
Follow the wiring diagram carefully. Incorrect wiring can lead to device malfunction or electrical hazards.
- Connect the incoming three-phase power supply (N, L1, L2, L3) to the 'IN' terminals.
- Connect the single-phase load (N, L1) to the 'OUT' terminals. The ATS will manage the phase transfer for the L1 output.
- Ensure all connections are secure and tightened to prevent loose contacts and overheating.
4.2. Erste Inbetriebnahme
After completing the wiring, restore power to the system. The ATS will power on and begin monitoring the phases. The digital display will show the current voltage readings for each phase. If all phases are stable and within acceptable limits, the ATS will provide power to the output.
5. Bedienungsanleitung
The ATS operates automatically, but you can adjust its protection parameters to suit your specific requirements.
5.1. Die Anzeige und die Indikatoren verstehen
The digital display continuously shows the real-time voltage of each phase (L1, L2, L3) and the current on L1. The indicator lights provide quick visual feedback on the device's status and any detected anomalies.

Bildbeschreibung: Eine Nahaufnahme view of the ATS digital display. It shows '220V' for L1, L2, and L3, and '63.0A' for L1 current. Below these readings are small indicator icons for Power, >V (Over-voltage), <V (Under-voltage), and >I (Over-current).
5.2. Adjusting Protection Parameters
Use the 'SET' button to enter the parameter setting mode. Use the 'Digit+/Up' and 'Digit-/Down' buttons to navigate through settings and adjust values. Press 'SET' again to confirm and save changes.
| Parameter | Einstellbereich | Standardeinstellung |
|---|---|---|
| Over Current Protection Setting Range | 1-63A/100A | 30 A |
| Continuous Over Current Protection Times | 0-20 Mal | AUS |
| Über Voltage Protection Setting Range | 230 bis 300 V | 270 V |
| Über Voltage Protection Recover Setting Range | 225 bis 295 V | 265 V |
| Unter Voltage Protection Setting Range | 140 bis 210 V | 170 V |
| Unter Voltage Protection Recover Setting Range | 145 bis 215 V | 175 V |
| Bandtage & Current Protection Recover Delay | 1-500 Sekunden | 30er Jahre |
5.3. Automatic Phase Transfer
The ATS automatically monitors the three input phases (L1, L2, L3). If a phase failure or significant voltage imbalance (over/under voltage) is detected on the currently supplying phase, the device will automatically transfer the single-phase output load to a healthy, stable phase within the same supply. This process is designed to be seamless and rapid, minimizing power interruption to connected equipment.
5.4. Automatic Recovery
Once the primary phase recovers and stabilizes, the ATS will intelligently switch the load back to the primary source, ensuring optimal power distribution and preventing equipment damage from unstable power. The recovery delay can be configured as per your operational needs.
6. Wartung
The EARU Electric ATS is designed for minimal maintenance. However, periodic checks are recommended to ensure optimal performance and longevity.
- Reinigung: Halten Sie das Gerät sauber und frei von Staub und Schmutz. Verwenden Sie zum Reinigen ein trockenes, weiches Tuch. Verwenden Sie keine flüssigen Reinigungsmittel.
- Verbindungsprüfungen: Überprüfen Sie regelmäßig alle Drahtverbindungen, um sicherzustellen, dass sie fest sitzen und frei von Korrosion sind.
- Umgebungsbedingungen: Stellen Sie sicher, dass die Betriebsumgebung innerhalb der vorgegebenen Temperatur- und Feuchtigkeitsbereiche bleibt.
7. Fehlerbehebung
Sollten Sie Probleme mit Ihrem Bewerbermanagementsystem (ATS) haben, beachten Sie bitte die folgenden häufig auftretenden Probleme und Lösungen:
| Problem | Mögliche Ursache | Lösung |
|---|---|---|
| Keine Leistungsabgabe | No input power; all phases unstable; device in fault state. | Check incoming power supply. Verify all phases are stable. Check fault indicators. |
| ">V" or "<V" indicator lit | Überlautstärketage oder Unterlautstärketage detected on a phase. | Eingangslautstärke prüfentage stability. The ATS will automatically transfer if another phase is healthy. |
| ">I" indicator lit | Over-current detected on the output. | Reduce load on the output. Check for short circuits in the connected equipment. |
| Device not transferring phases | No healthy alternative phase available; transfer delay setting too long. | Ensure at least one healthy phase is present. Check and adjust the transfer delay settings. |
| Digitalanzeige funktioniert nicht | No power to the device; internal fault. | Check power supply. If power is present and display is off, contact support. |
For issues not covered here, please contact EARU customer support.
8. Spezifikationen

Bildbeschreibung: This image displays the physical dimensions of the ATS (90mm width, 96mm height, 66mm depth) and a table of detailed technical specifications, including current rating, voltage, frequency, and various protection setting ranges.
| Besonderheit | Detail |
|---|---|
| Marke | EARU |
| Modellnummer | EARU-1012 |
| Betriebsmodus | EIN-AUS |
| Aktuelle Bewertung | 63 Amps |
| Betriebslautstärketage | 440 Volts (AC 3*220V (N-L1/L2/L3)) |
| Nennfrequenz | 50/60 Hz |
| Kontakttyp | Normalerweise offen |
| Steckertyp | Standard DIN rail 63A |
| Schaltungsart | 4-Wege |
| Kontaktmaterial | Kupfer |
| Over Current Protection Setting Range | 1-63A/100A (Default 30A) |
| Continuous Over Current Protection Times | 0-20 Times (Default OFF) |
| Über Voltage Protection Setting Range | 230-300V (Default 270V) |
| Über Voltage Protection Recover Setting Range | 225-295V (Default 265V) |
| Unter Voltage Protection Setting Range | 140-210V (Default 170V) |
| Unter Voltage Protection Recover Setting Range | 145-215V (Default 175V) |
| Bandtage & Current Protection Recover Delay | 1-500s (Default 30s) |
| Artikelgewicht | 450 g |
| Verpackungsabmessungen | 15 x 15 x 15 cm |
| Ursprungsland | Indien |
9. Garantie und Support
9.1. Garantieinformationen
The EARU Electric 3-Phase Auto Transfer Switch (ATS) comes with a 1 Jahr Herstellergarantie Diese Garantie gilt ab Kaufdatum und deckt Material- und Verarbeitungsfehler bei normalem Gebrauch ab. Sie deckt keine Schäden ab, die durch unsachgemäße Installation, Missbrauch, Unfälle oder unbefugte Änderungen verursacht wurden.
9.2. Kundendienst
For technical assistance, warranty claims, or any questions regarding your EARU Electric ATS, please contact your retailer or the manufacturer directly. Ensure you have your product model number (EARU-1012) and proof of purchase available when contacting support.