1. Einleitung
This manual provides essential information for the safe and efficient installation, operation, and maintenance of the MEAN WELL HDR-150-48 Ultra Slim Step Shape LED DIN Rail Power Supply. Please read this manual thoroughly before using the product and retain it for future reference.
The HDR-150-48 is a high-performance, ultra-slim power supply designed for LED lighting and other industrial control applications requiring a stable 48V DC output. Its compact design allows for easy integration into DIN rail systems.
2. Sicherheitshinweise
WARNUNG: Stromschlaggefahr. Installation und Wartung dürfen nur von qualifiziertem Fachpersonal durchgeführt werden.
- Vor jeglichen Installations-, Verkabelungs- oder Wartungsarbeiten muss sichergestellt werden, dass das Netzteil von der Hauptstromquelle getrennt ist.
- Do not operate the unit in environments with excessive moisture, dust, or extreme temperatures outside its specified operating range.
- Überprüfen Sie die korrekte Eingangslautstärke.tage and polarity before connecting the power supply.
- Sorgen Sie für eine ordnungsgemäße Erdung, um Stromschläge zu vermeiden.
- Öffnen Sie nicht das casing des Netzteils; im Inneren befinden sich keine vom Benutzer wartbaren Teile.
- Observe all local and national electrical codes during installation.
3. Produktüberschreitungview
The MEAN WELL HDR-150-48 is an ultra-slim, step-shape power supply designed for efficient power conversion in various applications. It features a robust design suitable for DIN rail mounting.
3.1 Hauptmerkmale
- Ultra slim design for space-saving installations.
- DIN rail mountable (TS-35/7.5 or TS-35/15).
- Universeller AC-Eingang / Volle Reichweite.
- Schutz: Kurzschluss / Überlast / Überspannungtage / Übertemperatur.
- Kühlung durch freie Luftkonvektion.
- LED indicator for power on.
3.2 Produktkomponenten
Refer to the images below for a visual representation of the HDR-150-48 power supply and its connection terminals.

Abbildung 1: Front view of the MEAN WELL HDR-150-48 power supply, showing the input/output terminals and status indicator.

Abbildung 2: Seite view of the MEAN WELL HDR-150-48 power supply, highlighting its ultra-slim profile for DIN rail mounting.

Abbildung 3: Detaillierte view of the terminal block on the HDR-150-48, showing input (AC L, N, FG) and output (V+, V-) connections.
4. Spezifikationen
The following table outlines the key technical specifications for the HDR-150-48 model.
| Parameter | Wert |
|---|---|
| Modellnummer | HDR-150-48 |
| Ausgangsvolumentage | 48 V Gleichstrom |
| Ausgangsstrom | 3 Amps |
| Ausgangsleistung | 154 W |
| Eingangslautstärketage Reichweite | 85 ~ 264 VAC |
| Effizienz | Bis zu 90% |
| Abmessungen (L x B x H) | 9.61 x 2.8 x 1.48 Zoll (244 x 71 x 37.5 mm) |
| Artikelgewicht | 10.9 Unzen (0.31 Kilogramm) |
| Betriebstemperatur | -30 ~ + 70 ° C. |
| Montage | DIN Rail TS-35/7.5 or TS-35/15 |
| Schutz | Kurzschluss, Überlast, Überspannungtage, Übertemperatur |
Note: Specifications are subject to change without notice. Refer to the official MEAN WELL datasheet for the most up-to-date and complete information.
5. Installation
Proper installation is crucial for the safe and reliable operation of the power supply.
5.1 Montage
- Ensure the mounting surface is stable and capable of supporting the weight of the power supply.
- Mount the HDR-150-48 onto a standard TS-35/7.5 or TS-35/15 DIN rail.
- Allow adequate clearance around the unit for proper ventilation (minimum 10-15mm on all sides). Do not block ventilation holes.
- Mount the unit vertically to optimize heat dissipation.
5.2 Verkabelung
CAUTION: Disconnect all power before wiring. Incorrect wiring can damage the unit and pose a safety hazard.
- Identify the input terminals (AC L, AC N, FG) and output terminals (V+, V-). Refer to Figure 3 for terminal locations.
- Connect the AC input wires (Live and Neutral) to the respective AC L and AC N terminals.
- Connect the Earth Ground wire to the FG (Frame Ground) terminal. This connection is essential for safety.
- Connect the load to the output terminals: positive (+) to V+ and negative (-) to V-. Ensure correct polarity.
- Use appropriate wire gauges for the expected current draw to prevent overheating.
- Tighten all terminal screws securely to prevent loose connections.

Abbildung 4: Example of wiring connections for the HDR-150-48, showing input AC and output DC connections. Always refer to the specific terminal markings on your unit.
6. Bedienung
Once installed and wired correctly, the HDR-150-48 is ready for operation.
- Vor dem Einschalten der Stromversorgung überprüfen Sie bitte alle Kabelverbindungen auf Korrektheit und sicheren Sitz.
- Schließen Sie das Gerät an die Wechselstrom-Eingangsspannung an.
- The LED indicator on the front panel (refer to Figure 1) should illuminate, indicating that the power supply is operating.
- Das Ausgangsvolumentage is factory set to 48V. Some models may have a voltage adjustment potentiometer; if present, use a non-conductive tool to make minor adjustments within the specified range.
- Ensure the total load connected to the output does not exceed the rated output power of 154W or the rated current of 3A.
7. Wartung
The HDR-150-48 power supply is designed for reliable, long-term operation with minimal maintenance.
- Reinigung: Periodically inspect the unit for dust accumulation, especially around ventilation openings. Disconnect power and use a soft, dry brush or compressed air to gently clean the exterior. Do not use liquid cleaners.
- Inspektion: Regularly check wiring connections for tightness and signs of wear or damage. Ensure the unit is securely mounted on the DIN rail.
- Umfeld: Maintain the operating environment within the specified temperature and humidity ranges to ensure optimal performance and lifespan.
- Keine vom Benutzer zu wartenden Teile: Versuchen Sie nicht, das Gerät zu öffnen oder zu reparieren. Überlassen Sie alle Wartungsarbeiten qualifiziertem Fachpersonal.
8. Fehlerbehebung
If the power supply is not functioning as expected, consider the following common issues and solutions:
| Problem | Mögliche Ursache | Lösung |
|---|---|---|
| No output, LED off | No input power; Incorrect wiring; Internal fault | Check AC input power source and connections. Verify wiring. If problem persists, unit may be faulty. |
| Ausgangsvolumentage too low or fluctuating | Overload; Short circuit; Input voltage zu niedrig | Reduce load. Check for short circuits in the output wiring. Verify input voltage liegt im Bereich. |
| Unit is hot, shuts down intermittently | Overload; Insufficient ventilation; Over-temperature protection activated | Reduce load. Ensure adequate airflow around the unit. Check ambient temperature. |
| LED is on, but no output | Output wiring issue; Load fault; Internal fault | Check output wiring for breaks or loose connections. Test the load independently. |
If troubleshooting steps do not resolve the issue, contact qualified service personnel or the manufacturer for assistance. Do not attempt to repair the unit yourself.
9. Garantie und Support
This MEAN WELL product is covered by a standard manufacturer's warranty against defects in materials and workmanship. The specific terms and duration of the warranty may vary by region and distributor. Please retain your proof of purchase for warranty claims.
For technical support, service, or warranty inquiries, please contact your local distributor or visit the official MEAN WELL webWebsite für Kontaktinformationen.
MEAN WELL Offizieller WebWebsite: www.meanwell.com