Einführung
This manual provides essential instructions for the safe and effective installation, operation, and maintenance of your APC RBC43 UPS Battery Replacement Cartridge. The APC RBC43 is designed for full compatibility with your APC UPS, ensuring optimal performance and reliability. Each APC Replacement Battery Cartridge (RBC) is rigorously tested and certified to restore your APC UPS to its original specifications. This VRLA battery comes with a 2-year manufacturer warranty.

Image: The APC RBC43 UPS Battery Replacement Cartridge, shown with its metallic enclosure.
Wichtige Sicherheitsinformationen
Please read and understand all safety instructions before handling or installing the battery cartridge. Failure to follow these instructions may result in electric shock, fire, or serious injury.
- Akku-Typ: This is a Sealed, Non-Spillable Lead Acid Battery.
- Recycling: Batteries must be recycled. Refer to the user's manual for battery recycling information. Do not dispose of in regular waste.
- Laden: Do not charge in a gas-tight container.
- Terminals: Batterieklemmen nicht kurzschließen.
- Verbrennung: Verbrennen Sie die Batterie nicht.
- Electrolyte Contact: If contaminated with electrolyte (acid), flush with water at once.
- Originalteile: For best performance and warranty support, use only genuine APC replacement batteries with your APC UPS. Use of non-APC RBC™ battery cartridges may result in lower UPS performance, damage to the UPS, create a hazardous condition, or void UL, CSA, VDE, and other safety certifications on the UPS.
Lieferumfang
Your APC RBC43 package should contain the following items:
- UPS Battery Cartridge
- All Required Connectors
- Battery Recycling Guide
- Metallic Battery Tray or Enclosure
- Mehrwegverpackungen
- Installationshandbuch
Installationsanleitung
Follow these steps to safely replace the battery cartridge in your APC UPS. The RBC43 is compatible with many APC models including SMT2200RM2U, SMT200RM2UC, SMT3000RM2U, SMT2200RM2UNC, SMT2200US, SMT3000RM2UC, SMT3000RM2UNC, SMT3000US, SUA2200RM2U, SUA2200RM2US, SUA3000RM2U, SUA3000RMT2U, SUA3000RMUS, SUM3000RMXL2U, SUM1500RMXL2U, SUM3000RMXL2U and select others.
Video Guide: RBC43 Battery Installation
Video: A detailed guide demonstrating the easy battery switch process for the APC RBC43 UPS battery. This video covers unboxing, identifying the old battery, removing it, and installing the new RBC43 cartridge.
Schritt-für-Schritt-Installation
Refer to the following instructions for a successful installation.

Image: The APC RBC43 battery module, ready for installation into a compatible UPS unit.
- Prepare the UPS: Ensure the UPS is powered off and disconnected from the main power source. If hot-swapping, ensure the UPS supports this feature and follow specific hot-swap procedures.
- Zugang zum Batteriefach: Open the front panel or access door of your UPS to expose the battery compartment.
- Alte Batterie abklemmen: Carefully disconnect the battery cables from the old battery cartridge. Note the orientation of the connectors (usually color-coded).
- Alte Batterie entfernen: Slide the old battery cartridge out of the UPS unit. Be aware that the battery is heavy (approximately 42 pounds or 18-32 kg).
- Prepare New Battery: Unpack the new APC RBC43 battery cartridge.
- Neue Batterie einlegen: Carefully slide the new RBC43 cartridge into the UPS compartment, ensuring it is fully seated.
- Neue Batterie anschließen: Reconnect the battery cables to the new cartridge, matching the color coding or previous orientation.
- Batterie sichern: Close and secure the battery compartment door or front panel.
- Power On UPS: Reconnect the UPS to the main power source and power it on.
- Reset Battery Constant (if applicable): Some UPS models require resetting the battery constant after replacement to ensure accurate runtime reporting. Refer to your specific UPS model's manual for this procedure.
Bedienungsanleitung
Once installed, your APC RBC43 battery will integrate with your UPS to provide reliable backup power. The UPS will automatically manage charging and discharge cycles.
- Grundgebühr: Allow the new battery to charge for at least 24 hours to reach full capacity before relying on it for extended backup.
- Laufzeit: The UPS will display the estimated runtime based on the connected load and battery charge level. Genuine APC batteries ensure accurate runtime reporting.
- Selbsttest: Periodically perform a UPS self-test to verify battery health and functionality. Refer to your UPS manual for instructions on initiating a self-test.
Why Choose Genuine APC Batteries
Video: This video highlights the benefits of using genuine APC replacement batteries, emphasizing reliability, compatibility, and proper recycling options compared to generic alternatives.
Wartung
The APC RBC43 is a maintenance-free battery. However, proper care and recycling are crucial for its lifespan and environmental responsibility.
- Umgebungsbedingungen: Operate the UPS within recommended temperature and humidity ranges to maximize battery life.
- Recycling Old Batteries: When you replace your RBC, it is essential to recycle the old battery responsibly. APC offers an "RBC Recycling Program" on their website, which includes free return to a recycling center. Use the packaging from your new battery to return the old one.
Fehlerbehebung
If you encounter issues after battery replacement, consider the following common scenarios:
- "Battery Near End of Life" Warning Persists:
- Ensure the new battery is correctly installed and all connections are secure.
- Verify that the battery constant has been reset in the UPS (if required for your model).
- Allow the battery to fully charge for 24 hours. If the warning persists, contact APC support.
- UPS liefert nicht die erwartete Laufzeit:
- Confirm the battery has completed its initial charge cycle.
- Check the total load connected to the UPS; excessive load will reduce runtime.
- Perform a manual calibration if your UPS model supports it, to re-learn the battery's capacity.
- Akku lädt nicht:
- Ensure the UPS is connected to a live power outlet.
- Check all battery connections within the UPS.
- If the issue persists, the UPS charging circuit may require service.
Technische Daten
| Besonderheit | Detail |
|---|---|
| Modellnummer | RBC43 |
| Technische Daten | 1.1 x 9.7 x 6.5 Zoll |
| Artikelgewicht | 42 pounds (18-32 kg) |
| Akku-Typ | Sealed Lead-Acid (VRLA) |
| Batterien erforderlich | 1 Product Specific battery required (cartridge contains multiple cells) |
| Hersteller | APC |
| Kompatibilität | SMT2200RM2U, SMT2200RM2UC, SMT2200RM2UNC, SMT3000RM2U, SMT3000RM2UC, SUA2200RM2U, SUA2200RM2US, SUA3000RM2U, SUA3000RMT2U, SUA3000RMUS, SUM3000RMXL2U, SUM1500RMXL2U, SUM3000RMXL2U and select others. |
Garantie und Support
Genuine APC Batteries are backed by a 2 Jahr Herstellergarantie. For warranty claims, technical support, or further assistance, please visit the official APC webWebsite oder wenden Sie sich an den Kundendienst.
APC WebWebsite: www.apc.com