Danfoss-LOGO

Danfoss RET2001M-V2 Programmable Room Thermostats

Danfoss-000RET2001M-V2-Programmable-Room-Thermostats-PRODUCT

Specifications

  • Operating: Product is designed for continuous use
  • Operating Voltage
  • Output: Volt free
  • Switch rating: 3 A (1) at 250 Vac
  • Switch type: 1x SPDT Type 1B
  • Terminals: 1 to 2.5 mm2 wires
  • IP rating: IP30 (installed)
  • Load compensation control: Yes
  • On/off control: Yes
  • ErP class: Class IV, efficiency gain 2%
  • Construction: EN60730-2-9
  • Control pollution situation Degree: 2
  • Rated impulse voltage: 4 kV
  • Ball pressure test
  • Dimensions: H86 x W86 x D30
  • Software classification
  • Running and setting accuracy (for thermostats with build in timer)
  • RET2001M-V2: Setting resolution 1 minute. Accuracy +/- 1 minute per month.
  • TP5001M-V2: Setting resolution 1 minute. Accuracy +/- 1 minute per month.

Installation Steps

  1.  Installation must be done by an authorized electrician.
  2. The room thermostat should be installed at approx. 1.5 m above floor and where the effects of sunlight, draught or other heat sources (eg. TV’s) are avoided, see fig. 1 on page 44.
    Danfoss-000RET2001M-V2-Programmable-Room-Thermostats-01
  3. First loosen lower retaining screw and carefully remove back plate, see fig. 2 on page 44.
    Danfoss-000RET2001M-V2-Programmable-Room-Thermostats-2
  4. Mount back plate direct to wall or on wall box and wire according to application, see fig. 3 & 6 (pages 44 and 45).
    Danfoss-000RET2001M-V2-Programmable-Room-Thermostats-3
  5. Remove battery backup tab, see fig. 4 on page 45.
    Danfoss-000RET2001M-V2-Programmable-Room-Thermostats-4 Remove battery backup tab
  6. Locate hooks at top of front part into top of back plate and lower into position and tighten retaining screw.

Danfoss-000RET2001M-V2-Programmable-Room-Thermostats-5

Dimensions and Wiring

See fig. 5 for dimensions and fig. 6 for wiring diagram on page 45.Danfoss-000RET2001M-V2-Programmable-Room-Thermostats-6

Error codes

DisplayDescription
E1Sensor Failure
EEEEPROM Failure
LoMeasured temperature below 0 °C
HiMeasure temperature above 50 °C
E6Real Time Clock Failure(TP5001M Only)

Technical Specifications

SpecificationsRET2001M-V2 TP5001M-V2
OperatingProduct is designed for continuous use
Operating Voltage230 Vac ± 10 % 50/60 Hz
OutputVolt free
Setting temperature range5 °C to 35 °C
Operating temperature range0 °C to 40 °C
Switch rating3 A (1) at 250 Vac
Switch type1x SPDT Type 1B
Terminals1 to 2.5 mm2 wires
IP ratingIP30 (installed)
Load compensation controlYes
On/off controlYes
ErP classClass IV, efficiency gain 2 %
ConstructionEN60730-2-9
Control pollution situationDegree 2
Rated impulse voltage4 kV
Ball pressure test75 °C
DimensionsH86 x W86 x D30
SpecificationsRET2001M-V2 TP5001M-V2
Software classificationA
Running and setting accuracy (for thermostats with build in timer)Setting resolution 1 minute. Accuracy +/- 1 minute per month.

Note 

  1. Both live(L) terminals are internally linked and available for ease of cable termination only.
  2. If replacing a 230-volt room stat, a link between the live(L) and a common(COM) terminal is required.

Danfoss Ltd.
22 Wycombe End, HP9 1NB, GB

Danfoss A/S

  • Climate Solutionsheating.danfoss.com
  • +45 7488 2222
  • E-mail: heating@danfoss.com
  • Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation.
  • Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product. All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

VISUO14F | AN30483462054701-010103

© Danfoss | FEC | 01.2023

Documents / Resources

Danfoss RET2001M-V2 Programmable Room Thermostats [pdf] Installation Guide
RET2001M-V2 Programmable Room Thermostats, RET2001M-V2, Programmable Room Thermostats, Room Thermostats, Thermostats

References

Leave a comment

Your email address will not be published. Required fields are marked *