Danfoss MCX15B Electronic Controller
Specifications
- Input: Analog NTC, 0/1 V, 0/5 V (software configurable), Universal NTC, Pt1000, 0/1 V, 0/5 V, 0/10 V, ON/OFF, 0/20 mA, 4/20 mA
- Digital Inputs: 24 V optoisolated, 230 V AC optoisolated
- Analog Outputs: 0/10 V DC optoisolated PWM, PPM (software configurable)
- Power Supply: 24 V AC / 20-60 V DC, 110 V / 230 V AC
- Other: Programming key connection, remote keyboard terminal connection, Buzzer, CANbus, RTC Clock, Modbus RS485 Serial
Product Usage Instructions
Installation and Setup
- Ensure the power supply matches the product requirements.
- Connect the necessary analog and digital inputs based on your configuration needs.
- Configure the analog input types using the provided software.
- Set up the analog outputs according to your application requirements.
Programming and Configuration
Use the software provided to configure input types, set up digital inputs and outputs, and adjust output parameters as needed for your specific application.
Operation
- Power on the device and ensure all connections are secure.
- Monitor the input signals and adjust settings if necessary.
- Observe the output responses and make any adjustments required for optimal performance.
Maintenance
Regularly check connections, clean the device if needed, and ensure proper ventilation for optimal performance and longevity.
Controllo elettronico MCX15B
GENERAL FEATURES
- MCX15B is fitted with or without graphic LCD display. It is an electronic controller that stands on the top of the MCX range, thanks to the large number of its inputs and outputs. It holds all the typical functionalities of MCX controllers: programmability, connection to the CANbus local network and up to two Modbus RS485 serial communication interfaces.
- Furthermore it is available in two models, powered at 110-230 V AC or 24 V AC
GENERAL FEATURES AND WARNINGS
PLASTIC HOUSING FEATURES
- DIN rail mounting complying with EN 60715
- Self extinguishing V0 according to IEC 60695-11-10 and glowing/hot wire test at 960 °C according to IEC 60695-2-12
- Ball test: 125 °C according to IEC 60730-1. Leakage current: ≥ 250 V according to IEC 60112
OTHER FEATURES
- Operating conditions CE: -20T60 / UL: 0T55, 90% RH non-condensing – Storage conditions: -30T80, 90% RH non-condensing
- To be integrated in Class I and/or II appliances
- Index of protection: IP40 only on the front cover
- Period of electric stress across insulating parts: long
- Suitable for use in environments with degree of pollution 2
- Category of resistance to heat and fire: D
- Immunity against voltage surges: category II
- Software class and structure: class A
CE MARK
This product is designed to comply with the following EU standards:
- Low voltage directive LVD 2014/35/EU:
- EN60730-1: 2011 (Automatic electrical control for household and similar use. General requirements)
- EN60730-2-9: 2010 (Particular Requirements for Temperature Sensing Controls)
- EN 61000-6-3: 2007 +A1: 2011 (Emission standard for residential, commercial and light-industrial environments)
- EN 61000-6-2: 2005 (Immunity for industrial environments)
- EN50581: 2012
UL APPROVAL
- UL file: E31024
GENERAL WARNINGS
- Every use that is not described in this manual is considered incorrect and is not authorised by the manufacturer
- Verify that the installation and operating conditions of the device respect the ones specified in the manual, specially concerning the supply voltage and environmental conditions
- This device contains live electrical components therefore all the service and maintenance operations must be performed by qualified personnel
- The device can’t be used as a safety device
- Liability for injury or damage caused by the incorrect use of the device lies solely with the user
INSTALLATION WARNINGS
- Mounting position recommended: vertical
- The installation must be executed according the local standards and legislation of the country
- Always operate on the electrical connections with the device disconnected from the main power supply
- Before carrying out any maintenance operations on the device, disconnect all the electrical connections
- For safety reasons the appliance must be fitted inside an electrical panel with no live parts accessible
- Don’t expose the device to continuous water sprays or to relative humidity greater than 90%.
- Avoid exposure to corrosive or pollutant gases, natural elements, environments where explosives or mixes of flammable gases are present, dust, strong vibrations or chock, large and rapid fluctuations in ambient temperature that in combination with high humidity can condensate, strong magnetic and/or radio interference (e.g. transmitting antennae)
- When connecting loads beware of the maximum current for each relay and connector
- Use cable ends suitable for the corresponding connectors. After tightening the screws of connectors, slightly tug the cables to check their tightness
- Use appropriate data communication cables. Refer to the Fieldbus Installation Guide for the kind of cable to be used and setup recommendations
- Reduce the path of the probe and digital inputs cables as much as possible, and avoid spiral paths enclosing power devices. Separate from inductive loads and power cables to avoid possible electromagnetic noises
- Avoid touching or nearly touching the electronic components fitted on the board to avoid electrostatic discharges
DISPOSAL INSTRUCTION
- Equipment containing electrical components may not be disposed together with domestic waste. It must be separately collected with electrical and electronic waste according to local and valid legislation.
TECHNICAL SPECIFICATIONS
POWER SUPPLY
- 85 – 265 V AC, 50/60 Hz. Maximum power consumption: 26 VA. Insulation between power supply and the extra-low voltage: reinforced
- 20 – 60 V DC and 24 V AC ± 15% 50/60 Hz SELV. Maximum power consumption: 12 W, 20 VA. Insulation between power supply and the extra-low voltage: functional
I/O | TYPE | NUMBER | SPECIFICATIONS |
Digital outputs | Relay | 15 | Concerning the insulation distance there are three groups of relays:
– group 1: relays 1 to 8 – group 2: relays 9 to 13 – group 3: relays14 to 15 Insulation between relays of the same group: functional Insulation between relays of different groups: reinforced Insulation between relays and the extra-low voltage parts: reinforced Total current load limit: 92 A C1-NO1 to C9-NO9 Normally open contact relays 8 A: – characteristics of each relay: 6 A 250 V AC for resistive loads – 100.000 cycles 4 A 250 V AC for inductive loads – 100.000 cycles with cos(phi) = 0.6 UL: 240 V AC – 4 A resistive – 3.6 FLA – 21.6 LRA – 346 VA pilot duty 30.000 cycles C10-NO10-NC10 to C13-NO13-NC13 Changeover contacts relay 8 A: – characteristics of each relay: 6 A 250 V AC for resistive loads – 100.000 cycles 4 A 250 V AC for inductive loads – 100.000 cycles with cos(phi) = 0.6 UL: 240 V AC – 4 A resistive – 3.6 FLA – 21.6 LRA – 346 VA pilot duty 30.000 cycles C14-NO14-NC14, C15-NO15-NC15 High inrush current (80 A – 20 ms) changeover contacts relay 16 A: – characteristics of each relay: 7 A 250 V AC for resistive loads – 100.000 cycles 3.5 A 230 V AC for inductive loads – 230.000 cycles with cos(phi) = 0.4 UL: 240 V AC – 6 A resistive – 4.9 FLA – 29.4 LRA – 470 VA pilot duty 30.000 cycles
Using of device in case of Tamb = 70 °C has to be according to following requirements: – maximum load admitted for 8 A relay: 4 A 250 V AC – maximum load admitted for 16 A relay: 5 A 250 V AC |
- Via San Giuseppe 38/G
- 31015 Conegliano (TV) Italy
- Tel: +39 0438 336611
- Fax: +39 0438 336699
- www.danfoss.com
- Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
- All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
- AN15468641839001-000701 / 520H9940 – MCX15B instruction sheet – P.N. 3106000420 – 15-310600042-E © Danfoss A/S (RAC-DCS-IMCGP/vt), 2020.02
CONNECTION DIAGRAM
TOP BOARD
BOTTOM BOARD
CONNECTIONS
TOP BOARD
- Analog output 5-6 connector
- 3 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- Digital input 1 connector
- 3 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- Digital output 14 connector
- 3 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- Digital output 15 connector
- 3 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- Digital input 2 connector
- 3 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- Digital input 3 connector
- 3 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- Digital input 4 connector
- 3 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- Digital input 5-8 connector
- 5 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- Digital input 9-12 connector
- 5 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- Digital input 13-16 connector
- 5 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- Digital input 17-18 connector
- 4 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
BOTTOM BOARD
- Analog output 5-6 connector
- 3 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- Digital output 1-5 connector
- 10 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- Digital output 6-8 connector
- 6 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- Analog input 1-6 connector
- 11 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- Analog input 7-10 connector
- 6 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- Power supply connector
- 2 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- Digital output 9-12 connector
- 11 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- Digital output 13 connector
- 3 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- Analog output 1-4 connector
- 6 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- RS485-2 connector
- 3 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- RS485-1 connector
- 3 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- CAN connector
- 4 way screw plug-in connector type pitch 5 mm: section cable 0.2-2.5 mm²
- CAN-RJ connector
- 6/6 way telephone RJ12 plug type
DIMENSIONS
USER INTERFACE
DISPLAY LCD
- display mode: STN blue transmissive
- backlight: white LED backlight adjustable via software
- display format: 128×64 dots
- active visible area : 58×29 mm
- number of keys: 6
- Settings of the LCD display like contrast and brightness, might need to be adjusted due to external ambient factors. Press and release simultaneously the Enter and X key after power ON to access the BIOS menu and select the DISPLAY menu. Use UP and
- Use the down arrow keys to adjust the contrast or the brightness of the display at the desired level.
PRODUCT PART NUMBERS
CODE 080G0036
DESCRIPTION
- MCX15B, 24V, LCD, RS485, RTC, Single Pack
FAQS
Q: What is the maximum total load capacity for the digital outputs?
A: The maximum total load capacity for the digital outputs is 92 A.
Q: How do I configure the analog outputs for specific voltage ranges?
A: Use the provided software to configure the analog outputs between 0-10 V DC and adjust the settings based on your requirements.
Q: Can I use both 24 V AC and 230 V AC inputs simultaneously?
A: Yes, you can use both 24 V AC and 230 V AC inputs simultaneously for different purposes as needed.
Documents / Resources
![]() |
Danfoss MCX15B Electronic Controller [pdf] Instructions MCX15B, MCX15B Electronic Controller, Electronic Controller, Controller |