Danfoss MCF 107 VLT C-option Adapter

Danfoss MCF 107 VLT C-option Adapter

Introduction

Product Overview

The VLT® C-option Adapter MCF 107 extends the number of B options that can be installed in a VLT® AutomationDrive FC 302.
The following drives support the MCF 107 option:

  • VLT® AutomationDrive FC 302, enclosure sizes A5, B1, and B2.

The MCF 107 option is supported from firmware version 8.43.
Normally, a drive can be fitted with 1 A option and 1 B option in the A- and B-slots on the control card. With the MCF 107, it is possible to have 2 different B options installed. One in the standard B-slot and 1 in the MCF 107. However, when 2 B options are installed, it is not possible to have any fieldbus options (A options) installed.
In MCF 107, the following options are supported in the standard B-slot combined with VLT® PTC Thermistor Card MCB 112:

  • VLT® Encoder Option MCB 102.
  • VLT® Resolver Option MCB 103.
  • VLT® Safe PLC I/O MCB 108.

The following options are supported in the MCF 107:

  • VLT® PTC Thermistor Card MCB 112.

Order Numbers

Table 1: Order Numbers

Option Uncoated Coated
VLT® C-option Adapter MCF 107 134B7093
VLT® Encoder Option MCB 102 130B1115 130B1203
VLT® Resolver Option MCB 103 130B1127 130B1227
VLT® Safe PLC I/O MCB 108 130B1120 130B1220
VLT® PTC Thermistor Card MCB 112 130B1137

Items Supplied

The following items are supplied:

  • VLT® C-option Adapter MCF 107
  • Ribbon cable
  • 2 x Torx 10 screws
  • Installation Guide

Tools Required

The following tools are required for installing the VLT® C-option Adapter MCF 107:

  • Torx 10 screwdriver
  • Flat-head screwdriver

Safety

Safety Instructions

Symbol WARNING Symbol

DISCHARGE TIME

The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be present even when the warning indicator lights are off.
Failure to wait the specified time after power has been removed before performing service or repair work could result in death or serious injury.

  • Stop the motor.
  • Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and DC-link connections to other drives.
  • Wait for the capacitors to discharge fully. The minimum waiting time is specified in the table Discharge time and is also visible on the nameplate on top of the drive.
  • Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.

Table 2: Discharge Time

Voltage [V]  Minimum waiting time (minutes)
4 7 15 20
200–240 0.25–3.7 kW (0.34–5.0 hp) 5.5–37 kW (7.5–50 hp)
380–500 0.25–7.5 kW (0.34–10 hp) 11–75 kW (15–100 hp) 90–200 kW (150–350 hp)
400 90–315 kW (125–450 hp)
500 110–355 kW (150–450 hp)
525 55–315 kW (75–400 hp)
525–600 0.75–7.5 kW (1.0–10 hp) 11–75 kW (15–100 hp)
525–690 1.5–7.5 kW (2.0–10 hp) 11–75 kW (15–100 hp) 37–315 kW (50–450 hp)
690 55–315 kW (75–400 hp)

Installation

Overview

Illustration 1: Location of the MCF 107 Option

  1. Front cover
  2. VLT® C-option Adapter MCF 107
    Installation

Installing the MCF 107

  1. Location of A options
  2. Location of B options
  3. B option
  4. LCP frame
    Installation

Procedure

  1. Disconnect power to the drive.
  2. Disconnect power to the live part connections on the relay terminals.
  3. Remove the LCP or the blind cover.
  4. Remove the terminal cover.
  5. Remove the control cables.
  6. Remove the front cover.
  7. Remove the LCP cradle.
    Installation
  8. Remove all control cables from the metal bracket (spring-loaded).
  9. Install the VLT® C-option Adapter MCF 107.
    Installation
  10. Tighten the 2 T10 screws (marked with circles in the following illustration). Tightening torque is 1.5 Nm (13.27 in-lb).
    Installation
  11. Connect 1 end of the ribbon cable in the A-option slot and the other end in the upper slot in the MCF 107.
    Installation
  12. Install the VLT® PTC Thermistor Card MCB 112 option in the option holder and plug on the MCF 107.
    1. Encoder or resolver option
    2. Ribbon cable
    3. VLT® PTC Thermistor Card MCB 112
      Installation

Customer Support

Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
vlt-drives.danfoss.com

Danfoss can accept no responsibility for possible errors in catalogs, brochures and other printed material. Danfoss reserves the right to alter its products without notice.
This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Danfoss A/S © 2021.02 AN320938053147en-000201 / 130R0911