Danfoss KPI 38 Pressure Switch

Danfoss KPI 38 Pressure Switch

DIMENSION

Dimension

INSTRUCTION FOR USE

Info for UK customers only: Danfoss Ltd., 22 Wycombe End, HP9 1NB, GB

Instruction For Use
Instruction For Use
Instruction For Use
Instruction For Use

KPI 34, KPI 35, KPI 36, KPI 38

t1min. -40 °C
t1max. 65 °C
t2min. -40 °C
t2max. 100 °C

Instruction For Use

TypeRangeDiff.
KPI 34-0.2 − 3 bar0.5 − 1.25 bar
KPI 35-0.2 − 8 bar0.4 − 2 bar
KPI 364 − 12 bar0.5 − 1.6 bar
KPI 388 − 28 bar1.8 − 6 bar

Instruction For Use

KPI 34: 18 bar
KPI 35: 18 bar
KPI 36: 18 bar
KPI 38: 30 bar

Please note: No maintenance is required for the switches after final installation.

Instruction For Use

Please note: scale in KP units is indicative only.
For accurate setting or when using according to FM aproval use additional pressure gauge to set the unit.

Instruction For Use

Standard contact
Alternating current
AC-1 : 10 A, 440 V
AC-3 : 6 A, 440 V
AC-15: 4 A, 440 V
Blocked rotor: 112 A

Direct current:
DC-13, 12 W, 220 V

SymbolListed refrigeration controller 61B5
VoltageFLLRResist. loadPilot duty
ACDCAA
2406368A3A
12084810
24012W

Use copper wire only Tightening torque 20 lb. in.

Instruction For Use

Symbol CAUTION:
Disconnect power supply before wiring connections are made or service to avoid possible electrical shock or damage to equipment. Do never touch live parts wite your fingers ro with ant tool.

Instruction For Use
Instruction For Use

Symbols  060R9308Logo

Documents / Resources

Danfoss KPI 38 Pressure Switch [pdf] Installation Guide
KPI 34, KPI 35, KPI 36, KPI 38, KPI 38 Pressure Switch, Pressure Switch, Switch