Danfoss FJVR Thermostatic Return Temperature Limiter Installation Guide
Setting
FJVR thermostats maintain radiator return temperature constant according to the setting (g.1), and so limit heat consumption.
Limiting
Always check the basic calibration before limiting the setting range.
Limiting the minimum setting
Set the thermostat as shown in (g. 1).
Remove the scale ring with a screwdriver (g. 2). Take the two stop rings out of the selector knob gear rim (g. 3). Place the scale ring as shown in g. 1 and set the knob to the required minimum value, „2“ for example.
Take the scale ring o again and insert one of the stop rings so that its stop lug contacts the righthand side of the lug on the centre piece (g. 3). Place the scale ring in position with »2« opposite the arrow.
Limiting the maximum setting
Set the thermostat to the required maximum setting, »6« for example. Place the second stop ring so that its stop lug contacts the lefthand side of the grey lug on the centre piece. Place the scale ring in position with the gure »6« opposite the arrow.
Basic calibration
If the selector knob is removed from the element (only possible after the scale and stop rings have been removed) basic calibration can be carried out: place the selector knob and turn it anticlockwise.
If the selector knob does not engage the spring tightener, rotate the knob 180 degrees. When the knob does engage, turn it anticlockwise until the mark on the gear rim isopposite the arrow. Insert the stop rings on top of each other with the stop lugs to the right of the lug on the centre piece (g. 4). Replace the scale ring.
Danfoss A/S
Climate Solutions • danfoss.com • +45 7488 2222
Any information, including, but not limited to information on selection of product, its application or use, priduct design, weight, dimensions, capacity or any other technical data in product manuals. catalogues descriptions, advertisements, etc. and weather made availabe in writing, orally, electronically, online or via download, shall be considered informative, and i sonly binding if any to the extent, explicit reference is made in a quotation or order conformation. Danfoss cannpt accept any repsponsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its procucts without notice.
This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, t or function of the product.
All trademarks in this material are the property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.
Read More About This Manual & Download PDF:
Documents / Resources
![]() | Danfoss FJVR Thermostatic Return Temperature Limiter [pdf] Installation Guide FJVR, FEB, FJVR Thermostatic Return Temperature Limiter, FJVR, Thermostatic Return Temperature Limiter, Return Temperature Limiter, Temperature Limiter, Limiter |