Danfoss F Series Ground Bar Kit Installation Guide

F Series Ground Bar Kit

Specifications:

  • Compatible with iC7 Series Frequency Converters in FB09a,
    FK09a, FB10a, and FK10b frames
  • Available kit numbers: 176F4170, 176F4171, 176F4186,
    176F4187
  • Single ground bar kits for FK09a/FB09a and FK10a/FB10a; split
    ground bar kits for FK09c/FB09c and FK10c/FB10c

Product Usage Instructions:

2 Installation

2.1 Safety Information

WARNING: ELECTRIC SHOCK HAZARD

  • Only use qualified electricians for installation.
  • Disconnect the drive from all power sources before installation
    or service.
  • Treat the drive as live whenever the mains voltage is
    connected.
  • Follow the guidelines in these instructions and local
    electrical safety regulations.

WARNING: DISCHARGE TIME (20 MINUTES)

  • Stop the motor.
  • Disconnect AC mains and remote DC-link power supplies.
  • Wait for capacitors to discharge fully (minimum of 20
    minutes).
  • Use a voltage measuring device to ensure capacitors are fully
    discharged before service or repair work.

WARNING: INTERNAL FAILURE HAZARD

  • Ensure all safety covers are in place and securely fastened
    before applying power.

NOTICE: ELECTROSTATIC DISCHARGE

  • Follow standard ESD procedures.
  • Ensure discharge before touching internal components.

FAQ:

Q: Can the ground bar kit be installed by
non-professionals?

A: No, only qualified electricians should handle the
installation due to safety hazards.

Q: What should I do if I encounter an internal failure in the
drive?

A: Ensure all safety covers are in place and seek professional
assistance to address internal failures.

“`

Installation Guide
Ground Bar Kit for FK09/FB09 and FK10/FB10
iC7 Series Frequency Converters

1 Overview

1.1 Description
The ground bar kit fits iC7 Series Frequency Converters in FB09a, FK09a, FB10a, and FK10b frames. The frame is listed on the frequency converter product label. The ground bar kit can be installed in drives both with or without a touch protection option.
1.2 Kit Numbers
Use these instructions with the following kits. Table 1: Numbers for Ground Bar Kits

Number 176F4170 176F4171 176F4186 176F4187

Description Ground bar kit, FK09a/FB09a Ground bar kit, FK10a/FB10a Ground bar kit, FK09c/FB09c Ground bar kit, FK10c/FB10c

1.3 Items Supplied
The kits contain a ground bar with brackets and fasteners for attaching the ground bar. Kits for FK09a/FB09a and FK10a/FB10a contain a single ground bar. Kits for FK09c/FB09c and FK10c/FB10c have a 2-part split ground bar.
Table 2: Items Supplied in Single Ground Bar Kits (176F4170 and 176F4171)

Item Ground bar Left bracket Right bracket Screws Table 3: Items Supplied in Split Ground Bar Kits (176F4186 and 176F4187)

Quantity 1 1 1 5

Item Ground bar Left bracket Right bracket Screws

Quantity 2 1 1 6

Danfoss A/S © 08.2025

AN422434236428en-000401 / 136R0288 | 1

Installation Guide | Ground Bar Kit for FK09/FB09 and FK10/FB10

Installation

2 Installation
2.1 Safety Information
WARNING
ELECTRIC SHOCK HAZARD AC drives contain dangerous voltages when connected to mains voltage. Installing or servicing the drive with power connected can cause death, serious injury, or equipment failure.
Only use qualified electricians for the installation. Disconnect the drive from all power sources before installation or service. Treat the drive as live whenever the mains voltage is connected. Follow the guidelines in these instructions and local electrical safety regulations.

WARNING
DISCHARGE TIME (20 MINUTES)
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be present even when the warning LED indicator lights are off. Failure to wait 20 minutes after power has been removed before performing service or repair work can result in death or serious injury.
Stop the motor.
Disconnect AC mains and remote DC-link power supplies, including battery backups, UPS, and DC-link connections to other drives.
Disconnect or lock the PM motor.
Wait for the capacitors to discharge fully. The minimum waiting time is 20 minutes.
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.

WARNING
INTERNAL FAILURE HAZARD An internal failure in the drive can result in serious injury when the drive is not properly closed.
Ensure that all safety covers are in place and securely fastened before applying power.

NOTICE
ELECTROSTATIC DISCHARGE Electrostatic discharge can damage components.
Follow standard ESD procedures. Ensure discharge before touching internal components, for example by touching a grounded, conductive surface or by
wearing a grounded armband.

2 | Danfoss A/S © 08.2025

AN422434236428en-000401 / 136R0288

Installation Guide | Ground Bar Kit for FK09/FB09 and FK10/FB10

Installation

2.2 Replacing the Side Brackets
Before installing the ground bar, use the following steps to replace the existing brackets with the brackets from the kit.
1. Remove the existing side brackets by removing 2 screws (T25) from the cabinet exterior, 1 from the left bracket and 1 from the right bracket. See Figure 1.
2. Attach the new left bracket by fastening 1 screw (T25) through the side panel of the cabinet and into the bracket. Repeat for the right bracket.
If the kit has screws of different lengths, use the shorter screws to attach the brackets.
The left and right brackets differ from each other. For FK09a/FB09a/FK10a/FB10a frames, see Figure 2 for the positioning of each bracket. For FK09c/FB09c/FK10c/FB10c frames, see Figure 3.

e30bk197.10

Figure 1: Removal of Existing Side Brackets Danfoss A/S © 08.2025

AN422434236428en-000401 / 136R0288 | 3

Installation Guide | Ground Bar Kit for FK09/FB09 and FK10/FB10
R L

Installation

e30bk198.10

e30bm664.10

Figure 2: Installation of Left and Right Brackets (FK09a/FB09a and FK10a/FB10a Frames)
R L
Figure 3: Installation of Left and Right Brackets (FK09c/FB09c and FK10c/FB10c Frames)

4 | Danfoss A/S © 08.2025

AN422434236428en-000401 / 136R0288

Installation Guide | Ground Bar Kit for FK09/FB09 and FK10/FB10

Installation

2.3 Installing the Single Ground Bar
For kits with a single ground bar, use the following steps to install the ground bar. See Figure 4. For kits with a 2-piece split ground bar, refer to 2.4 Installing the Split Ground Bar.
1. Attach the ground bar to the 2 brackets by fastening 2 screws (T25), 1 in each end of the ground bar. 2. Fasten 1 screw (T25) in the center of the ground bar, attaching it to the lower EMC shield.

e30bk199.10

T25

T25

T25

Figure 4: Installation of Single Ground Bar in FK09a/FB09a and FK10a/FB10a Frames

Danfoss A/S © 08.2025

AN422434236428en-000401 / 136R0288 | 5

e30bk369.10

Installation Guide | Ground Bar Kit for FK09/FB09 and FK10/FB10
2.4 Installing the Split Ground Bar
For kits with a 2-part split ground bar, use the following steps to attach the left and right sections of the ground bar. 1. Attach the left ground bar between the left bracket and the EMC shield using 2 screws (T25), 1 in each end of the ground bar. See Figure 5. 2. Attach the right ground bar between the EMC shield and the right side bracket using 2 screws (T25), 1 in each end of the ground bar.

T25

T25

T25

T25

F igure 5: Installation of Split Ground Bar in FK09c/FB09c and FK10c/FB10c Frames

Danfoss A/S Ulsnaes 1 DK-6300 Graasten drives.danfoss.com
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalog descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogs, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product. All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

Danfoss A/S © 08.2025

M00374
*136R0288*

AN422434236428en-000401 / 136R0288