Danfoss logoDEVIreg Hotwater DIN Rail
Programmable Controller
User GuideDanfoss DEVIreg Hotwater DIN Rail Programmable Controller

Installation and User Guide
DEVIreg™ Hotwater
DIN-rail programmable controller for Hotwater maintenance

Introduction

DEVIreg™ Hotwater is a 4 channel electronic programmable controller. 3 additional chancels are not used in this constellation. The device is DIN-rail mountable and is used for control of Devi Hot watt cables. Every channel (4) can be  individually set up, this will allow for 4 different temperatures and disinfection schedules.
Universal analog channels’ inputs can be selected via software between 7 types of temperature sensors including NTC 15 kOhm at 25 °C. The controller has a LCD display, Modbus RS-485 serial interface and 110/230 V AC power supply.  Voltage to sensors is SELV.
DEVIreg™ Hotwater has 8 control relays – 2 sets of max. 10 A and 6 sets of max. 6 A; For this specific application 2, 10A and 2, 6A relays are used. Relay control functions can be set to Hot-water maintenance and legionella control of a  hot-water system by use of applicable heating cables. Additionally, relay contacts are not connected to a voltage source inside the controller, and can be used for control systems with any voltage up to 250 V AC.
Hardware of DEVIreg™ Hotwater is based on the Danfoss controller type MCX08M2, art. no. 080G0307, but is customized with special software.
The product complies with the EN/IEC Standard “Automatic electrical controls for household and similar use”:
• EN/IEC 60730-1 (general)
• EN/IEC 60730-2-9 (thermostat)
More information on this product can also be found at: devi.com
Connection scheme DEVIreg™ Hotwater

Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - Hotwater

Safety Instructions

Make sure the mains supply to the controller is turned off before installation.
Please also note the following:

  • The installation of the controller must be done by an authorized and qualified installer according to local regulations.
  • The controller must be connected to a power supply via an all-pole disconnection switch.
  • Always connect the controller to continuous power supply.
  • Do not expose the controller to moisture, water, dust and excessive heat.

Note: Product is designed for Over Voltage Category II. When used, installation must be equipped with transient protection.

Mounting Instructions

Please observe the following placement guidelines:
Install the thermostat in an electric cabinet with DIN rail attachment or a separate DIN attachment according to local regulation on IP classes.
Do not place the thermostat in a way that will expose the controller to direct sunlight.
Follow the steps below to mount the thermostat:

  1. Click the thermostat on the DIN rail attachment.
  2. Connect the thermostat according to the connection diagram, see page 4.
  3. The screen of the heating cable must be connected to the earth conductor of the power supply cable by using a separate connector.
  4. Turn on the power supply.

Note: Always install the sensors at assumed hottest and coldest locations on the respective pipe, and in direct contact with the pipe (2 sensors pr. heating circuit)

User Manual

4.1 General use
The DEVIreg™ Hotwater is operated via 6 physical buttons to the right of the LCD-display.
Buttons
The functions of the 4 operated buttons are:

Up, DownDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - iconShows additional information
Left, RightDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon1Next menu entry / next line / next setting parameter
EscapeDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon2Escape return to previous level of menu / show Alarm screen
EnterDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3Confirm / select / go to the Main menu

Display
The DEVIreg™ Hotwater can simultaneously control up to 4 different systems. These 4 systems are referred as H1, H2, H3 and H4 (short for Heater).
The DEVIreg™ Hotwater provides the user with an opportunity to view the current status of the all systems. This status is always shown on the main screen.
Main Screen view (default)

The Main Screen is the main window appearing when the controller is powered. This screen displays an overview of data from the different heaters. (H1-H4) by pressing the Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon4and Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon5more detailed information can be obtained from the respective heaters sub screen. Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - Main ScreenThis view provides the user with an overview of all systems, however with limited information.

Heater sub-screen view
These screens give to user quick and more detailed information about settings and status of each heater.Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - Heater

Just press buttonDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon4 on the Main Screen of con troller and H1 data will appear, pressDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon4 again – and you’ll see H2 data, and so on. To progress reversely through this menu please use Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon5.
To exit from sub-screens view and return to the Main Screen – press Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon2 1 time.
Setup wizard
On the first power on of the device, the device will ask to run the wizard to do this pressDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - Setup wizardPressDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3 once more to proceed into the setup.Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - Setup wizard1The device will ask for the amount heaters use Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon to select and Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3 to accept. Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - Setup wizard2

The device will now ask for the details of each heater in the following pattern
– Pipe material
– Sensor type
– Temperature setpoint
– Enable disinfectionDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - Setup wizard3

All mentioned can be selected with Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - iconand accepted byDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3.Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - Setup wizard4If multiple heaters are entered, this exact procedure will repeat till all information is filled for all heaters.Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - Setup wizard5

The final step in the wizard is the RTC (Real Time Clock) pressDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3
Navigate withDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon orDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon1 select withDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3 Manipulate withDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon accept with Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3or return with Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon2Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - Setup wizard6Once time and date are set confirm withDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon2
First start-up
Ensure everything is correctly connected and securely fixed.
Please check this now.Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - First start

Once verified press and holdDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon6 (approx. 3-5 sec.) to turn on the device.
The device will now commence normal operation.
Sub-menu Alarm
The structure in this Sub-menu is navigated like the main menu.Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - menu AlarmActive alarms: display of the currently active alarms and is to navigate like Alarm view. Having an active alarm will activate alarm relay. Alarms will be retained till reset has been performed.
Reset Alarms: Reset all alarms by pressing Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3
Log history: display previous alarms in a list with date and timestamp. This is navigated like Alarm view.
Clear log history: clears the log history permanently by pressingDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3.
Sub-menu Service
The structure in this Sub-menu is navigated like the main menu.Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - ServiceSystem: contains a system submenu for professional users containing (Yxx) parameters.
Additionally this menu should under normal circumstances not be used.
This menu will change according to the user level password entered in Login.
Relay counters:
Displays the number of relay ON/OFF switching’s performed by each relay.
Software info:
Displays the installed software version.
Device info:
Displays serial number, product code and BIOS version
RTC setup:
Setup of the real time clock, this is to navigate like explained in setup wizard step RTC.
Login:
Enables a password to be input and is to be navigated withDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon andDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon1 select withDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3
Configuration:
Contains buzzer activation time, delay for alarm activation and alarm state when device is OFF.
Serial settings:
Contains Modbus/CAN serial address, Modbus serial baudrate and Modbus serial settings
Language:
The structure in this Sub-menu is navigated like the main menu.
Contains the different language variants.
Function Setup Wizard
This function will reset the device into the Setup Wizard.Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - Setup WizardYes with Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3or NO withDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon2

Sub-menu (H1-H4)
The structure in this Sub-menu is navigated like the main menu.
Sensor type:
Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon to select correct type andDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3 to confirm.
Be aware that 2 sensors must be used for each heater circuit (H1-H4) and that these must be the same type.
-PT1000
-NTC16K (NTC16.8K)
-NTC100 (NTC100K)
-NTC2K
-NTC5K
-NTC10K
-NTC15K (Std. DEVI sensor)
Has no default value as this must be set in setup wizard. Please refer to the sensors maximum and minimum temperatures to ensure safe operation of the system.
Setpoint:
Settable with Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - iconto select and Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3to confirm.
Settable temperature setpoint (desired maintained temperature) between 20.0-80.0°C (20-60.0°C on plastic pipe).
Has no default value as this must be set in setup wizard.
Hysteresis:
Settable withDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon to select andDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3 to confirm.
Settable between 1.0-10.0K
Defaults to 2.0K
High temperature:
Settable withDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon to select andDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3 to confirm.
Settable between 20.0-90.0K
Defaults to Setpoint+Hysteresis+5K
Not settable below setpoint
Alarm delay:

Settable withDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon to select and Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3 to confirm.
Temperature alarm delay
Settable between 10-240s
Defaults to 10s
Sensor weighting:

Settable with Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon to select and Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3 to confirm.
Weighting the impact of the 2 sensors on the heater regulation.
0% means that the regulation is made on basis of sensor A only 100% meaning sensor B only, thus 50% is the mean between sensor A and B.
Settable between 0-100%
Defaults to 50%
Disinfection temp:

Settable withDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon to select andDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3 to confirm.
Settable between 55-80.0°C
Defaults to 55°C
Pipe material:

Settable withDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon to select and Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3 to confirm.
This parameter will have impact on the maximum settable temperatures.
Can be set to metal or plastic.
Has no default value as this must be set in setup wizard
Disinfection alarm temperature:

SettableDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon withDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3 to select and to confirm.
This parameter will have impact on the alarm temperature for disinfection temperatures.
Defaults to 65°C
Maximum rising time:

SettableDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon withDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3 to select and to confirm.
This parameter will have impact on when the alarm will be triggered due to, too low temperature (setpoint not reached).
Defaults to 120 minutes.
Sub-menu Disinfection schedule
The structure in this Sub-menu is navigated like the main menu.
(H1-H4) Schedule:Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - schedule

Press Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3to go to next parameter andDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon2 to cancel.
Settable withDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon to select and Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3 to confirm.
Defaults to Sunday at 02:00.
(H1-H4) Manual start:
Starts the Disinfection procedure manually by pressingDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3
Temperature time table:

Temperature of disinfection [C°]Disinfection time
552h 00 minutes
561h 20 minutes
571h 00 minutes
580h 50 minutes
590h 45minutes
600h 40 minutes
610h 35 minutes
620h 30minutes
630h 28 minutes
640h 27 minutes
650h 26minutes
660h 25 minutes
670h 25 minutes
680h 22 minutes
690h 21 minutes
700h 20 minutes
710h 18minutes
720h 14 minutes
730h 12 minutes
740h 10 minutes
750h 10 minutes

Alarms view

By pressingDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon2 button from Main Screen – screen(-s) with Alarm appears.
If more than 1 Alarm is happened – use navigation by going Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon. PressingDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon2 button again leads from Alarm to Main Screen. Having an active alarm will activate alarm relay. Alarms will be retained till reset has been performed.
Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - Alarms view
Main menu

By pressingDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3 from the Main Screen– screen Main Menu appears.
Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - Main menu

The menu system is navigated from Main Screen by the following sequence:
The main menu is navigated byDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon6 andDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon7.
Pressing theDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3 the selected sub-menu will be shown. Pressing Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon2 button you will be taken back to the previous menu step.
4.2 Language setting
DEVIreg™ Hotwater controller has different programmed languages located in Sub-menu Service under languages.
4.3 Date and Time settings
DEVIreg™ Hotwater controller has RTC (Real Time Clock) for fixing time of data logging information, for example Alarms.
NB: Battery back-up time is min. 48 hours.
4.4 BMS(Building Management System) settings
DEVIreg™ Hotwater controller has Modbus RS-485 opto-insulated serial interface.
Modbus RS-485 settings can be done by the following menu sequence:
Main Screen – EnterDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3 to Main Menu – Enter Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3 to Service – EnterDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - icon3 to Serial settings
More detailed information is contained in the Appendix A.

Connection diagram

Connection scheme DEVIreg™ HotwaterDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - Connection diagram

Technical Specifications

6.1 Technical data

TypeValue
Nominal voltage110/230 V~ AC, 50–60 Hz
Power consumption, max.20 V A
Relay load:
Resistive (inductive, cos(phi sign) = 0,6) Total current load limit
C1-NO1, C2-NO2
C3-NO3-NC3, C4-NO4-NC4 C8-NO8-NC8
32 A
10 (3,5) A (100 000 cycles), cos(phi) = 0.5
6 (4) A (100 000 cycles), cos(phi) = 0.6
6 (4) A (100 000 cycles), cos(phi) = 0.6
Sensor inputsAnalog inputs AI1-AI8
Compatible sensorsNTC15k (15 kOhm @ 25 °C) (standard) (max 90 °C)
NTC10k (10 kOhm @ 25 °C)
NTC5k (5 kOhm @ 25 °C)
NTC2k (2 kOhm @ 25 °C)
NTC100 (100 kOhm @ 25 °C)
NTC16k (16,7 kOhm @ 100 °C)
PT1000 (1000 Ohm @ 0 °C)
Digital inputsDI1-DI8, voltage free contacts, on/off inputs
Connection specificationGrouped screws plug-in connectors
Cable specification for connectors terminals0,2-2,5 mm²
Battery back-up time, min.48 hours
Ball pressure test125 °C
Pollution degree2 (domestic use)
Controller type1 C
Operating temperatures and conditionsCE: -20T60 / UL: 0T55, 90% RH non-condensing
Storage temperature and conditions-30Т85, 90% RH non-condensing
IP classIP40 only on the front cover
Protection classClass II –
Immunity against voltage surgesOver Voltage Category II
Dimensions (H/W/D), DIN dimension :110(122) х 138 х 70 mm, 8 DIN modules
Mounting methodDIN rail, complying with EN 60715
Weight, net511 g
Menu languages:EN
Base controllerDanfoss MCX08M2, item no. 080G0307
Software classA

6.2 DimensionsDanfoss DEVIreg Hotwater DIN Rail Programmable Controller - Dimensions

Disposal Instruction

Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - Disposal

Appendix A. BMS and RS-485 interface

The controller has a built-in Modbus data transmission system and can be connected to the BMS central unit.
A1. Communication settings
Default communication settings:

  • Serial address: 1.
  • Serial baud rate (Transmission speed): 19200.
  • Serial setting: 8N1.

A2. RS-485 specifications
MCX hardware network specifications (wiring, topology, etc.) can be found in Danfoss document:
User manual. Meet any HVAC requirement with the reliability of MCX network.
This document provides general indications for the setup of RS-485 networks.
A3. Modbus parameters and variables
Modbus parameters and variables for DEVIreg™ Hotwater controller.

LABELDESCRIPTIONMINMAX.VALUE/ TYPEUNITRWADU
PARAMETERS & STATUS VARIABLES
SYSMain Menu > System variables
S1MaxH1_0dec010080RW3001
S2MaxH1_1dec0.0100.080.0RW3002
S3MaxH2_0dec010080RW3003
S4MaxH2_1dec0.0100.080.0RW3004
S5MaxH3_0dec010080RW3005
S6MaxH3_1dec0.0100.080.0RW3006
S7MaxH4_0dec010080RW3007
S8MaxH4_1dec0.0100.080.0RW3008
S9AlarmH10.090.090.0RW3009
S10AlarmH20.090.090.0RW3010
S11AlarmH30.090.090.0RW3011
S12AlarmH40.090.090.0RW3012
S13InitConfigured010RW3013
S14Dis_warn010RW3014
StUService > System
y01Main switch010 – OFFEnum 1RW3015
y02Heaters used040RW3016
y03Maximum plastic temp0.080.060.0°CRW3017
y04Reset counters040 – NOEnum 7RW3018
y07Restore default parameters010 – NOEnum 2RW3019
ALAService > Configuration
BUZBuzzer activation time0151minRW3023
AdLAlarm relay activation delay09990sRW3024
AOFAlarm relay active if unit in OFF011 – YESEnum 2RW3025
SErService > Serial settings
SErSerial address (Modbus and CAN)11001RW3026
bAUSerial baudrate (Modbus)075 – 192Enum 3RW3027
COMSerial settings (Modbus)020 – 8N1Enum 4RW3028
HE1Main Menu > H1 Settings
H00Sensor type066 – PT1000Enum 5RW3029
H01Setpoint20.0S240.0°CRW3030
H02Hysteresis1.010.02.0KRW3031
H03High temperatureH01S955.0°CRW3032
H04Alarm delay1024010sRW3033
H05Sensor weighting (0 = 100% sensor A)010050%RW3034
H06Disinfection temp55S155°CRW3035
H07Pipe material010 – MetalEnum 6RW3036
H08Disinfection alarm tempH0690.065.0°CRW3037
H09Max rising time1240120minRW3038
HE2Main Menu > H2 Settings
H10Sensor type066 – PT1000Enum 5RW3039
H11Setpoint20.0S440.0°CRW3040
H12Hysteresis1.010.02.0KRW3041
H13High temperatureH11S1055.0°CRW3042
H14Alarm delay1024010sRW3043
H15Sensor weighting (0 = 100% sensor A)010050%RW3044
H16Disinfection temp55S355°CRW3045
H17Pipe material010 – MetalEnum 6RW3046
H18Disinfection alarm tempH1690.065.0°CRW3047
H19Max rising time1240120minRW3048
HE3Main Menu > H3 Settings
H20Sensor type066 – PT1000Enum 5RW3049
H21Setpoint20.0S640.0°CRW3050
H22Hysteresis1.010.02.0KRW3051
H23High temperatureH21S1155.0°CRW3052
H24Alarm delay1024010sRW3053
H25Sensor weighting (0 = 100% sensor A)010050%RW3054
H26Disinfection temp55S555°CRW3055
H27Pipe material010 – MetalEnum 6RW3056
H28Disinfection alarm tempH2690.065.0°CRW3057
H29Max rising time1240120minRW3058
HE4Main Menu > H4 Settings
H30Sensor type066 – PT1000Enum 5RW3059
H31Setpoint20.0S840.0°CRW3060
H32Hysteresis1.010.02.0KRW3061
H33High temperatureH31S1255.0°CRW3062
H34Alarm delay1024010sRW3063
H35Sensor weighting (0 = 100% sensor A)010050%RW3064
H36Disinfection temp55S755°CRW3065
H37Pipe material010 – MetalEnum 6RW3066
H38Disinfection alarm tempH3690.065.0°CRW3067
H39Max rising time1240120minRW3068
LOGStatus var > MCX Design Hotspots
V01SystemOnOff010 – OFFEnum 1Read8101
C01Reset Alarms02RW1859
V11H1_highTemp010 – NOEnum 2Read8102
V09H1_controlTemp-50.0120.00.0°CRead8103
V11H1_reference0.0100.00.0°CRead8104
V12H1 pullDown010 – NOEnum 2Read8105
V13H1 manualDis010RW9901
V14H2 manualDis010RW9902
V15H3 manualDis010RW9903
V16H4 manualDis010RW9904
V16H1 sensorA error010 – NOEnum 2Read8106
V17H1 sensorB error010 – NOEnum 2Read8107
V16H1_sensorA-50.0120.00.0°CRead8108
V17H1_sensorB-50.0120.00.0°CRead8109
V15H1_heater010 – OFFEnum 1Read8110
V16H1_state060Read8111
V17H1_DisinfectionTimer0500000sRead8112
V18H2 sensorA-50.0120.00.0°CRead8113
V19H2 sensorB-50.0120.00.0°CRead8114
V20H2 sensorA error010 – NOEnum 2Read8115
V21H2 sensorB error010 – NOEnum 2Read8116
V22H2 controlTemp-50.0120.00.0°CRead8117
V23H2 reference-50.0120.00.0°CRead8118
V24H2 heater010 – NOEnum 2Read8119
V25H2 pullDown010 – NOEnum 2Read8120
V26H2 highTemp010 – NOEnum 2Read8121
V27H2 DisinfectionTimer0500000sRead8122
V28H2 state060Read8123
V29H3_sensorA-50.0120.00.0°CRead8124
V30H3_sensorB-50.0120.00.0°CRead8125
V31H3_controlTemp-50.0120.00.0°CRead8126
V32H3_reference-50.0120.00.0°CRead8127
V33H3 heater010 – NOEnum 2Read8128
V34H3 state060Read8129
V35H3 sensorA error010 – NOEnum 2Read8130
V36H3 sensorB error010 – NOEnum 2Read8131
V37H3 DisinfectionTimer0500000sRead8132
V38H3 highTemp010 – NOEnum 2Read8133
V39H3 pullDown010 – NOEnum 2Read8134
V40H4 sensorA-50.0120.00.0°CRead8135
V41H4 sensorB-50.0120.00.0°CRead8136
V42H4 sensorA error010 – NOEnum 2Read8137
V43H4 sensorB error010 – NOEnum 2Read8138
V44H4 controlTemp-50.0120.00.0°CRead8139
V45H4 reference-50.0120.00.0°CRead8140
V46H4 heater010 – NOEnum 2Read8141
V47H4 state060Read8142
V48H4 DisinfectionTimer0500000sRead8143
V49H4 highTemp010 – NOEnum 2Read8144
V50H4 pullDown010 – NOEnum 2Read8145
V51H1 Duty01000%Read8146
V52H2 Duty01000%Read8147
V53H3 Duty01000%Read8148
V54H4 Duty01000%Read8149
V56H1 counter021474836470Read8150
V57H2 counter021474836470Read8152
V58H3 counter021474836470Read8154
V59H4 counter021474836470Read8156
ALARMS
LABELDESCRIPTIONMINMAXRESETIN OFF
E01Sensor1 A error01AUTOACTIVERead1901 .08
E02Sensor1 B error01AUTOACTIVERead1901 .09
E03Sensor2 A error01AUTOACTIVERead1901 .10
E04Sensor2 B error01AUTOACTIVERead1901 .11
E05Sensor3 A error01AUTOACTIVERead1901 .12
E06Sensor3 B error01AUTOACTIVERead1901 .13
E07Sensor4 A error01AUTOACTIVERead1901 .14
E08Sensor4 B error01AUTOACTIVERead1901 .15
A01Heater1 high temp01AUTOINACTIVERead1901 .00
A02Heater2 high temp01AUTOINACTIVERead1901 .01
A03Heater3 high temp01AUTOINACTIVERead1901 .02
A04Heater4 high temp01AUTOINACTIVERead1901 .03
A05Heater1 disinfection fail01MANUALINACTIVERead1901 .04
A06Heater2 disinfection fail01MANUALINACTIVERead1901 .05
A07Heater3 disinfection fail01MANUALINACTIVERead1901 .06
A08Heater4 disinfection fail01MANUALINACTIVERead1901 .07
A09Heater1 rising fail01MANUALINACTIVERead1902 .08
A10Heater2 rising fail01MANUALINACTIVERead1902 .09
A11Heater3 rising fail01MANUALINACTIVERead1902 .10
A12Heater4 rising fail01MANUALINACTIVERead1902 .11
A13Heater1 high disinfection01MANUALINACTIVERead1902 .12
A14Heater2 high disinfection01MANUALINACTIVERead1902 .13
A15Heater3 high disinfection01MANUALINACTIVERead1902 .14
A16Heater4 high disinfection01MANUALINACTIVERead1902 .15
I/O CONFIGURATION
AIANALOG INPUTS
1Sensor 1A-30.0170.0PT1000Read18502
2Sensor 1B-30.0170.0PT1000Read18503
3Sensor 2A-30.0170.0PT1000Read18504
4Sensor 2B-30.0170.0PT1000Read18505
5Sensor 3A-30.0170.0PT1000Read18506
6Sensor 3B-30.0170.0PT1000Read18507
7Sensor 4A-30.0170.0PT1000Read18508
8Sensor 4B-30.0170.0PT1000Read18509
DIDIGITAL INPUTS
AOANALOG OUTPUTS
DODIGITAL OUTPUTS
1Heater 101N.O.Read18003
2Heater 201N.O.Read18004
3Heater 301N.O.Read18005
4Heater 401N.O.Read18006
8Alarm01N.O.Read18002

Warranty

A 2-year product warranty is valid for:
• thermostats: DEVIreg™ Hotwater.
Should you, against all expectations, experience a problem with your DEVI product, you will find that Danfoss offers DEVI warranty valid from the date of purchase on the following conditions: During the warranty period Danfoss  shall offer a new comparable product or repair the product if the product is found to be faulty by reason of defective design, materials or workmanship. The repairer replacement. The decision to either repair or replace will be solely at  the discretion of Danfoss. Danfoss shall not be liable for any consequential or incidental damages including, but not limited to, damages to property or extra utility expenses. No extension of the warranty period following repairs undertaken  is granted.
The warranty shall be valid only if the WARRANTY CERTIFICATE is completed correctly and in accordance with the instructions, the fault is submitted to the installer or the seller without undue delay and proof of purchase is provided. Please note that the WARRANTY CERTIFICATE must be filled in, stamped and signed by the authorized installer performing the installation (Installation date must be indicated). After the installation is performed, store and keep the  WARRANTY CERTIFICATE and purchase documents (invoice, receipt or similar) during the whole warranty period.
DEVI warranty shall not cover any damage caused by incorrect conditions of use, incorrect installation or if installation has been carried out by non-authorized electricians. All work will be invoiced in full if Danfoss is required to inspect or repair faults that have arisen as a result of any of the above. The DEVIwarranty shall not extend to products which have not been paid in full. Danfoss will, at all times, provide a rapid and effective response to all complaints and inquiries from our customers.
The warranty explicitly excludes all claims exceeding the above conditions.
For full warranty text visit www.devi.com.devi.danfoss.com/en/warranty/
WARRANTY CERTIFICATE
The DEVIwarranty is granted to:

Address—————————————–
Stamp——————————————
Purchase date ——————————-
Serial number of the product—————
Product —————————————-
Art. No.—————————————-
*Connected output [W]———————-
Installation Date & Signature————–
Connection Date & Signature————-
*Not mandatory

Danfoss DEVIreg Hotwater DIN Rail Programmable Controller - br codeDanfoss A/S
Nordborg Vej 81
6430 Nordborg, Syddanmark
Denmark

Danfoss A/S
DEVI • devi.com • +45 7488 2222 • EH@danfoss.com
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product. All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

Danfoss logo8097137 & AN377831097153en-010103
Produced by Danfoss © 03/2024