Danfoss-LOGO

Danfoss 80G8429 Case Controller Type EKC 224

Danfoss-80G8429-Case-Controller-Type-EKC-224-PRODUCT

Specifications

  • Model: Case controller Type EKC 224
  • Power Supply: 115 V AC / 230 V AC, 50/60 Hz
  • Rated Power: Less than 0.7 W
  • Inputs: Sensor inputs, Digital inputs, Programming key
  • Allowed Sensor Types: SELV limited energy

Product Usage Instructions

Installation

  • Refer to the installation guide for detailed steps on mounting and dismounting the controller. Ensure proper wiring based on the provided wiring diagrams.

Data Communication

  • The EKC 22x controller can be integrated into a Modbus network via the RS-485 adapter (EKA 206) using an interface cable (080N0327). Follow the installation guide for EKA 206 for detailed installation instructions.

Wiring

  • Follow the provided wiring diagrams to connect the controller to the power supply and sensors. Use appropriate cables and connectors for secure connections.

Interface

  • For data communication, use the RS-485 adapter (EKA 206) and interface cable (080N0327) as specified. Ensure proper configuration for seamless integration into the Modbus network.

Controller Features

  • Purpose of Control: Operating temperature sensing control for air-conditioning and refrigeration applications
  • Construction: Incorporated control with galvanic isolated low voltage regulated power supply
  • Accuracy: High precision control with less than 0.7 W power consumption

FAQ

  • Q: How do I mount the controller?
    • A: The controller can be mounted using rear mounting with clips as indicated in the dimensions section of the manual.
  • Q: What types of inputs are supported by the controller?
    • A: The controller supports sensor inputs, digital inputs, and programming key inputs, connected to SELV-limited energy sources.

Identification

Danfoss-80G8429-Case-Controller-Type-EKC-224-FIG-1

Application

Danfoss-80G8429-Case-Controller-Type-EKC-224-FIG-2

Dimensions

Danfoss-80G8429-Case-Controller-Type-EKC-224-FIG-3

Mounting

Danfoss-80G8429-Case-Controller-Type-EKC-224-FIG-4

Wiring diagrams

Danfoss-80G8429-Case-Controller-Type-EKC-224-FIG-5

  • Note: Power connectors: wire size = 0.5 – 1.5 mm2, max. tightening torque = 0.4 Nm
  • Low voltage signal connectors: wire size = 0.15 – 1.5 mm2, max. tightening torque = 0.2 Nm 2L and 3L must be connected to the same phase.

Data communication

InstallationDanfoss-80G8429-Case-Controller-Type-EKC-224-FIG-6

  • The EKC 22x controller can be integrated into a Modbus network via the RS-485 adapter (EKA 206) using an interface cable (080N0327).
  • For installation details please refer to the installation guide for EKA 206 – RS485 adapter.

WiringDanfoss-80G8429-Case-Controller-Type-EKC-224-FIG-7

Technical data

FeaturesDescription
Purpose of controlOperating temperature sensing control suitable for incorporation into commercial air-conditioning and refrigeration applications
Construction of controlIncorporated control
Power supply084B4055 – 115 V AC / 084B4056 – 230 V AC

50/60 Hz, galvanic isolated low voltage regulated power supply

Rated powerLess than 0.7 W
InputsSensor inputs, Digital inputs, Programming key Connected to SELV limited energy <15 W
Allowed sensor typesNTC 5000 Ohm at 25 °C, (Beta value=3980 at 25/100 °C – EKS 211) NTC 10000 Ohm at 25 °C, (Beta value=3435 at 25/85 °C – EKS 221) PTC 990 Ohm at 25 °C, (EKS 111)

Pt1000, (AKS 11, AKS 12, AKS 21)

AccuracyMeasuring range: -40 – 105 °C (-40 – 221 °F)
Controller accuracy:

±1 K below -35 °C, ±0.5 K between -35 – 25 °C,

±1 K above 25 °C

Type of action1B (relay)
OutputDO1 – Relay 1:

16 A, 16 (16) A, EN 60730-1

10 FLA / 60 LRA at 230 V, UL60730-1

16 FLA / 72 LRA at 115 V, UL60730-1

DO2 – Relay 2:

8 A, 2 FLA / 12 LRA, UL60730-1

8 A, 2 (2 A), EN60730-1

DO3 – Relay 3:

3 A, 2 FLA / 12 LRA, UL60730-1

3 A, 2 (2 A), EN60730-1

DO4 – Relay 4: 2 A
DisplayLED display, 3 digits, decimal point and multi-function icons, °C + °F scale
Operating conditions-10 – 55 °C (14 – 131 °F), 90% Rh
Storage conditions-40 – 70 °C (-40 – +158 °F), 90% Rh
ProtectionFront: IP65 (Gasket integrated) Rear: IP00
EnvironmentalPollution degree II, non-condensing
Overvoltage categoryII – 230 V supply version – (ENEC, UL recognized) III – 115 V supply version – (UL recognized)
Resistance to heat and fireCategory D (UL94-V0)

Temperature for ball pressure test statement According to Annex G (EN 60730-1)

EMC categoryCategory I
ApprovalsUL recognition (US & Canada) (UL 60730-1) CE (LVD & EMC Directive)

EAC (GHOST) UKCA

UA CMIM ROHS2.0

Hazloc approval for flammable refrigerants (R290/R600a).

R290/R600a end-use applications employing under the IEC60079-15 requirements.

Display operation

The buttons on the front of the display can be operated with short and long (3s) presses.Danfoss-80G8429-Case-Controller-Type-EKC-224-FIG-8

AStatus indication: LEDs light up at ECO/Night mode, cooling, defrost, ing, and fan running.
BAlarm indication: The alarm icon flashes in case of an alarm.
CShort press = Navigate back

Long press = Initiate pulldown cycle. The display will show “Pud” to confirm the start.

DShort press = Navigate up

Long press = Switch controller ON/OFF (setting r12 Main switch in ON/OFF position)

EShort press = Navigate down

Long press = Start the defrosting cycle. The display will show the code “-d-“ to confirm the start.

FShort press = Change set point

Long press = Go to the parameter menu

View alarms:

  • Temperature and alarm codes alternate ˛ashes until the alarm is resolved. The alarm bell ˛ashes during alarm condition.Danfoss-80G8429-Case-Controller-Type-EKC-224-FIG-9

Lock keyboard:

  • After 5 minutes of no activity, the keypad is locked (if P76=yes).
  • When the keypad is locked any button press shows “LoC” in the display.
  • Press the UP and DOWN buttons simultaneously for 3 seconds to unlock the keyboard. “until” is displayed for 3 s

Factory resetting

The controller can be set back to factory settings by using the following procedure.

  1. Power OFF controller
  2. Keep up “∧” and down “∨” arrow buttons pressed while reconnecting the supply voltage
  3. When the code “Fac” is shown in the display, select “yes

Note: The OEM factory setting will either be the Danfoss factory settings or a user deÿned factory setting if one has been made. The user can save his setting as OEM factory setting via parameter o67.

Display codes

Display codeDescription
-d-The defrost cycle is in progress
PudA temperature pulldown cycle has been initiated
ErrThe temperature cannot be displayed due to a sensor error
Shown at the top of the display: The parameter value has reached the max. Limit
Shown at the bottom of the display: The parameter value has reached min. Limit
LocThe display keyboard is locked
URLThe display keyboard has been unlocked
PSThe access code is required to enter the parameter menu
Axx/ExxAlarm or error code flashing with normal temp. readout
OFFControl is stopped as the r12 Main switch is set OFF
OnControl is started as r12 Main switch is set ON (code shown in 3 seconds)
FacThe controller is reset to the factory setting

Navigation

  • The parameter menu is accessed by pressing the “SET” key for 3 seconds. If an access protection code “o05” has been deÿned the display will ask for the access code by showing the code “PS”.
  • Once the access code has been provided by the user, the parameter list will be accessed.Danfoss-80G8429-Case-Controller-Type-EKC-224-FIG-10

Get a good start

With the following procedure, you can start regulation very quickly.

  1. Press the “SET” button for 3 seconds and access the parameter menu (display will show “in”)
  2. Press the down button “∨” to go to the “cFg” menu (display will show “cFg”)
  3. Press the right/“>” key to open the conÿguration menu (display will show r12)
  4. Open the “r12 Main switch” parameter and stop control by setting it OFF (Press SET)
  5. Open the “o61 application mode” and select the needed application mode (Press SET)
  6. Open the “o06 Sensor type” and select the temperature sensor type used (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) – (Press “SET”).
  7. Open the “o02 DI1 Conÿguration” and select the function associated with digital input 1 (Please refer to parameter list) – (Press “SET”).
  8. Open the “o37 DI2 Conÿguration” and select the function associated with digital input 2 (Please refer to parameter list) –(Press “SET”).
  9. Open the “o62 Quick setting” parameter and select the presetting that ÿts with the application in use (please refer to the preset table below) – (Press “SET”).
  10. Open the “o03 Network address” and set the Modbus address if required.
  11. Navigate back to parameter “r12 Main switch” and set it in the “ON” position to start control.
  12. Go through the entire parameter list and change the factory settings where needed.

Selection of quick settings

Quick setting1234567
 Cabinet MT Natural def. Stop on timeCabinet MT El. def.

Stop on time

Cabinet MT El. def.

Stop on temp

Cabinet LT El. def.

Stop on temp

Room MT El. def.

Stop on time

Room MT El. def.

Stop on temp

Room LT El. def.

Stop on temp

r00 Cut-out4 °C2 °C2 °C-24 °C6 °C3 °C-22 °C
r02 Max Cut-out6 °C4 °C4 °C-22 °C8 °C5 °C-20 °C
r03 Min Cut-out2 °C0 °C0 °C-26 °C4 °C1 °C-24 °C
A13 HighLim Air10 °C8 °C8 °C-15 °C10 °C8 °C-15 °C
A14 LowLim Air-5 °C-5 °C-5 °C-30 °C0 °C0 °C-30 °C
d01 Def. MethodNaturalElectricalElectricalElectricalElectricalElectricalElectrical
d03 Def.Interval6 hour6 hour6 hour12 hour8 hour8 hour12 hour
d10 DefStopSens.TimeTimeS5 SensorS5 SensorTimeS5 SensorS5 Sensor
o02 DI1 Config.    Door FCT.Door FCT.Door FCT.

Programming key

Programming controller with Mass Programming Key (EKA 201)

  1. Power up the controller. Make sure the controllers are connected to the mains.
  2. Connect the EKA 201 to the controller using the respective controller interface cable.
  3. The EKA 201 will automatically start the programming process.Danfoss-80G8429-Case-Controller-Type-EKC-224-FIG-11

Parameter list

CodeShort text manual 

Min.

 

Max.

 

Def.

 

Unit

 

R/W

EKC 224 Appl.
1234
CFgConfiguration
r12Main switch (-1=service / 0=OFF / 1=ON)-110 R/W****
o611)Selection of application mode

(1) AP1: Cmp/Def/Fan/Light

(2) AP2: Cmp/Def/Fan/Alarm

(3) AP3: Cmp/Al/Fan/Light

(4) AP4: Heat/Alarm/Light

141 R/W****
o061)Sensor type selection

(0) n5 = NTC 5k, (1) n10 = NTC 10k, (2) Pt = Pt1000, (3) Ptc = PTC 1000

032 R/W****
o021)DI1 configuration

(0) oFF=not used, (1) Sdc=status, (2) doo=door function, (3)

doA=door alarm, (4) SCH=main switch,

(5) nig=day/night mode, (6) rFd=reference displacement,

(7) EAL=external alarm, (8) dEF=defrost,

(9) Pud=pull down, (10) Sc=condenser sensor

0100 R/W****
o371)DI2 configuration

(0) oFF=not used, (1) Sdc=status, (2) doo=door function, (3)

doA=door alarm, (4) SCH=main switch,

(5) nig=day/night mode, (6) rFd=reference displacement,

(7) EAL=external alarm, (8) dEF=defrost,

(9) Pud=pull down

090 R/W****
o621)Quick presetting of primary parameters 0 = Not used

1 = MT, Natural defrost, stop on time 2 = MT, El defrost, stop on time

3 = MT, El defrost, stop on temp. 4 = LT, El defrost, stop on temp.

5 = Room, MT, El defrost, stop on time 6 = Room, MT, El defrost, stop on temp.

7 = Room, LT, El defrost, stop on temp.

070 R/W*** 
o031)Network address02470 R/W****
r–Thermostat
r00Temperature setpointr03r022.0°CR/W****
r01Di erential0.120.02.0KR/W****
r02Max. limitation of setpoint settingr03105.050.0°CR/W****
r03Min. limitation of setpoint setting-40.0r02-35.0°CR/W****
r04Adjustment of the display’s temperature readout-10.010.00.0KR/W****
r05Temperature unit (°C / °F)0 / C1 / F0 / C R/W****
r09Correction of the signal from the Sair sensor-20.020.00.0°CR/W****
r12Main switch (-1=service / 0=OFF / 1=ON)-110 R/W****
r13Displacement of reference during night operation-50.050.00.0KR/W****
r40Thermostat reference displacement-50.020.00.0KR/W****
r96Pull-down duration09600minR/W*** 
r97Pull-down limit temperature-40.0105.00.0°CR/W*** 
A–Alarm settings
A03Delay for temperature alarm (short)024030minR/W****
A12Delay for temperature alarm at pulldown (long)024060minR/W****
A13High alarm limit-40.0105.08.0°CR/W****
A14Low alarm limit-40.0105.0-30.0°CR/W****
A27Alarm delay DI1024030minR/W****
A28Alarm delay DI2024030minR/W****
A37Alarm limit for condenser temperature alarm0.0200.080.0°CR/W*** 
CodeShort text manual 

Min.

 

Max.

 

Def.

 

Unit

 

R/W

EKC 224 Appl.
1234
A54Limit for condenser block alarm and comp. Stop0.0200.085.0°CR/W*** 
A72Voltage protection enable0/No1/ Yes0/No R/W*** 
A73Minimum cut-in voltage02700VoltR/W*** 
A74Minimum cut-out voltage02700VoltR/W*** 
A75Maximum cut-in voltage0270270VoltR/W*** 
d–Defrost
d01Defrost method

(0) non = None, (1) nat = Natural, (2) El = Electrical,

(3) gas = Hot gas

032 R/W*** 
d02Defrost stop temperature0.050.06.0°CR/W*** 
d03The interval between defrost starts02408hourR/W*** 
d04Max. defrost duration048030minR/W*** 
d05Time o set for start of first defrost at start-up02400minR/W*** 
d06Drip o time0600minR/W*** 
d07Delay for fan start after defrost0600minR/W*** 
d08Fan start temperature-40.050.0-5.0°CR/W*** 
d09Fan operation during defrosting0/O1/ On1/On R/W*** 
d101)Defrost sensor (0=time, 1=Sair, 2=S5)020 R/W*** 
d18Max. comp. runtime between two defrosts0960hourR/W*** 
d19Defrost on demand – S5 temperature’s permitted variation during frost build-up.

On the central plant choose 20 K (=o )

0.020.020.0KR/W*** 
d30Defrost delay after pull-down (0 = OFF)09600minR/W*** 
F-Fan
F01Fan at the top of the compressor

(0) FFC = Follow comp., (1) Fao = ON, (2) FPL = Fan pulsing

021 R/W*** 
F04Fan stop temperature (S5)-40.050.050.0°CR/W*** 
F07Fan pulsing ON cycle01802minR/W*** 
F08Fan pulsing OFF cycle01802minR/W*** 
c–Compressor
c01Min. ON-time0301minR/W*** 
c02Min. OFF-time0302minR/W*** 
c04Compressor OFF delay at door open09000secR/W*** 
c70Zero crossing selection0/No1/ Yes1/ Yes R/W*** 
o–Miscellaneous
o01Delay of outputs at start-up060010secR/W****
o021)DI1configuration

(0) oFF=not used, (1) Sdc=status, (2) doo=door function, (3)

doA=door alarm, (4) SCH=main switch,

(5) nig=day/night mode, (6) rFd=reference displacement, (7)

EAL=external alarm, (8) dEF=defrost,

(9) Pud=pull down, (10) Sc=condenser sensor

0100 R/W****
o031)Network address02470 R/W****
o05Access code09990 R/W****
o061)Sensor type selection

(0) n5 = NTC 5k, (1) n10 = NTC 10k, (2) Pt = Pt1000, (3) Ptc = PTC 1000

032 R/W****
o15Display resolution

(0) 0.1, (1) 0.5, (2) 1.0

020 R/W****
o16Max. standby time after coordinated defrost036020minR/W*** 
CodeShort text manual 

Min.

 

Max.

 

Def.

 

Unit

 

R/W

EKC 224 Appl.
1234
o371)DI2 configuration

(0) oFF=not used, (1) Sdc=status, (2) doo=door function, (3)

doA=door alarm, (4) SCH=main switch,

(5) nig=day/night mode, (6) rFd=reference displacement, (7)

EAL=external alarm, (8) dEF=defrost,

(9) Pud=pull down

090 R/W****
o38Configuration of light function

(0) on=always on, (1) dAn=day/night,

(2) doo=based on door action, (3) nEt = Network

031 R/W* **
o39Light control via a network (only if o38=3 (nEt))0/O1/ On1/ On R/W* **
o611)Selection of application mode

(1) AP1: Cmp/Def/Fan/Light

(2) AP2: Cmp/Def/Fan/Alarm

(3) AP3: Cmp/Al/Fan/Light

(4) AP4: Heat/Alarm/Light

141 R/W****
o621)Quick presetting of primary parameters 0 = Not used

1 = MT, Natural defrost, stop on time 2 = MT, El defrost, stop on time

3 = MT, El defrost, stop on temp. 4 = LT, El defrost, stop on temp

5 = Room, MT, El defrost, stop on time 6 = Room, MT, El defrost, stop on temp.

7 = Room, LT, El defrost, stop on temp.

070 R/W*** 
o67Replace the controller factory settings with the present settings0/No1/ Yes0/No R/W****
o91Display at defrost

(0) Air=Sair temperature / (1) FrE=freeze temperature / (2)

-d-=”-d-” is displayed

022 R/W*** 
P–Polarity         
P75Invert alarm relay

(1) = Invert relay action

010 R/W ***
P76Keyboard lock enable0/No1/ Yes0/No R/W****
u–Service
u00Control state

S0: Normal, S1: Wait after defrosting, S2: Min ON timer,

S3: Min OFF timer, S4: Drip o , S10: r12 Main switch set OFF,

S11: Thermostat cut-out, S14: Defrosting, S15: Fan delay,

S17: Door open, S20: Emergency cooling, S25: Manual control,

S30: Pulldown cycle, S32: Power up delay, S33: Heating

0330 R****
u01Sair Air temperature-100.0200.00.0°CR****
u09S5 Evaporator temperature-100.0200.00.0°CR****
u10Status of DI1 input0/O1/ On0/O R****
u13Night condition0/O1/ On0/O R****
u37Status of DI2 input0/O1/ On0/O R****
u28Actual thermostat reference-100.0200.00.0 R****
u58Compressor / Liquid line solenoid valve0/O1/ On0/O R*** 
u59Fan relay0/O1/ On0/O R*** 
u60Defrost relay0/O1/ On0/O R**  
u62Alarm relay0/O1/ On0/O R ***
u63Light relay0/O1/ On0/O R* **
u80Firmware version readout    R****
u82Controller code no.    R****
u84Heat relay0/O1/ On0/O R   *
U09Sc Condenser temperature-100.0200.00.0 R*** 

Alarm codes

In an alarm situation, the display will alternate between the readout of the actual air temperature and the readout of the alarm codes of active alarms.

CodeAlarmsDescriptionNetwork alarm
E29Sair sensor errorThe air temperature sensor is defective or the electrical connection is lost— Sair Error
E27Def sensor errorS5 Evaporator sensor is defective or the electrical connection is lost— S5 Error
E30Sc sensor errorSc Condenser sensor is a defect or electrical connection is lost— Sc Error
A01High temp alarmThe air temperature in the cabinet is too high— High t.alarm
A02Low temp alarmThe air temperature in the cabinet is too low— Low t. Alarm
A99High Volt alarmThe supply voltage is too high (compressor protection)— High Voltage
AA1Low Volt alarmThe supply voltage is too low (compressor protection)— Low Voltage
A61Condenser alarmCondenser temp. too high – check airflow— Cond Alarm
A80Cond. block alarmCondenser temp. too high – Manual reset of alarm required)— Cond Blocked
A04Door alarmThe door has been open for too long— Door alarm
A15DI AlarmExternal alarm from DI input— DI Alarm
A45Standby AlarmControl has been stopped by “r12 Main switch”— Standby mode
  • The condenser block alarm can be reset by setting the r12 Main switch OFF and ON again or by powering down the controller.

Danfoss A/S

  • Climate Solutions
  • danfoss.com
  • +457488 2222
  • Any information, including, but not limited to information on the selection of the product, its application or use, product design, weight, dimensions, capacity, or any other technical data in product manuals catalogs descriptions, advertisements, etc., and whether made available in writing, orally, electronically, online or via download, shall be considered informative and is only binding if and to the Danfos reserves the rige iso atterits products without enotice.
  • This also apies to products ordered but not die/vered sive ed that such alterations canes, be made without changes to the form, fit, or function of the product.
  • All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.
  • AN432635050585en-000201
  • © Danfoss Climate Solutions 2023.05

Documents / Resources

Danfoss 80G8429 Case Controller Type EKC 224 [pdf] Installation Guide
80G8429, 80G8446, 80G8390, 80G8392, 80G8391, 80G8432, 80G8433, 80G8434, 84B8346, 80G8435, 80G8440, 80G8429 Case Controller Type EKC 224, 80G8429, Case Controller Type EKC 224, Controller Type EKC 224, Type EKC 224, EKC 224

References

Leave a comment

Your email address will not be published. Required fields are marked *