Danfoss 80G8429 Case Controller Type EKC 224
Specifications
- Model: Case controller Type EKC 224
- Power Supply: 115 V AC / 230 V AC, 50/60 Hz
- Rated Power: Less than 0.7 W
- Inputs: Sensor inputs, Digital inputs, Programming key
- Allowed Sensor Types: SELV limited energy
Product Usage Instructions
Installation
- Refer to the installation guide for detailed steps on mounting and dismounting the controller. Ensure proper wiring based on the provided wiring diagrams.
Data Communication
- The EKC 22x controller can be integrated into a Modbus network via the RS-485 adapter (EKA 206) using an interface cable (080N0327). Follow the installation guide for EKA 206 for detailed installation instructions.
Wiring
- Follow the provided wiring diagrams to connect the controller to the power supply and sensors. Use appropriate cables and connectors for secure connections.
Interface
- For data communication, use the RS-485 adapter (EKA 206) and interface cable (080N0327) as specified. Ensure proper configuration for seamless integration into the Modbus network.
Controller Features
- Purpose of Control: Operating temperature sensing control for air-conditioning and refrigeration applications
- Construction: Incorporated control with galvanic isolated low voltage regulated power supply
- Accuracy: High precision control with less than 0.7 W power consumption
FAQ
- Q: How do I mount the controller?
- A: The controller can be mounted using rear mounting with clips as indicated in the dimensions section of the manual.
- Q: What types of inputs are supported by the controller?
- A: The controller supports sensor inputs, digital inputs, and programming key inputs, connected to SELV-limited energy sources.
Identification
Application
Dimensions
Mounting
Wiring diagrams
- Note: Power connectors: wire size = 0.5 – 1.5 mm2, max. tightening torque = 0.4 Nm
- Low voltage signal connectors: wire size = 0.15 – 1.5 mm2, max. tightening torque = 0.2 Nm 2L and 3L must be connected to the same phase.
Data communication
Installation
- The EKC 22x controller can be integrated into a Modbus network via the RS-485 adapter (EKA 206) using an interface cable (080N0327).
- For installation details please refer to the installation guide for EKA 206 – RS485 adapter.
Wiring
Technical data
Features | Description |
Purpose of control | Operating temperature sensing control suitable for incorporation into commercial air-conditioning and refrigeration applications |
Construction of control | Incorporated control |
Power supply | 084B4055 – 115 V AC / 084B4056 – 230 V AC 50/60 Hz, galvanic isolated low voltage regulated power supply |
Rated power | Less than 0.7 W |
Inputs | Sensor inputs, Digital inputs, Programming key Connected to SELV limited energy <15 W |
Allowed sensor types | NTC 5000 Ohm at 25 °C, (Beta value=3980 at 25/100 °C – EKS 211) NTC 10000 Ohm at 25 °C, (Beta value=3435 at 25/85 °C – EKS 221) PTC 990 Ohm at 25 °C, (EKS 111) Pt1000, (AKS 11, AKS 12, AKS 21) |
Accuracy | Measuring range: -40 – 105 °C (-40 – 221 °F) |
Controller accuracy: ±1 K below -35 °C, ±0.5 K between -35 – 25 °C, ±1 K above 25 °C | |
Type of action | 1B (relay) |
Output | DO1 – Relay 1: 16 A, 16 (16) A, EN 60730-1 10 FLA / 60 LRA at 230 V, UL60730-1 16 FLA / 72 LRA at 115 V, UL60730-1 |
DO2 – Relay 2: 8 A, 2 FLA / 12 LRA, UL60730-1 8 A, 2 (2 A), EN60730-1 | |
DO3 – Relay 3: 3 A, 2 FLA / 12 LRA, UL60730-1 3 A, 2 (2 A), EN60730-1 | |
DO4 – Relay 4: 2 A | |
Display | LED display, 3 digits, decimal point and multi-function icons, °C + °F scale |
Operating conditions | -10 – 55 °C (14 – 131 °F), 90% Rh |
Storage conditions | -40 – 70 °C (-40 – +158 °F), 90% Rh |
Protection | Front: IP65 (Gasket integrated) Rear: IP00 |
Environmental | Pollution degree II, non-condensing |
Overvoltage category | II – 230 V supply version – (ENEC, UL recognized) III – 115 V supply version – (UL recognized) |
Resistance to heat and fire | Category D (UL94-V0) Temperature for ball pressure test statement According to Annex G (EN 60730-1) |
EMC category | Category I |
Approvals | UL recognition (US & Canada) (UL 60730-1) CE (LVD & EMC Directive) EAC (GHOST) UKCA UA CMIM ROHS2.0 Hazloc approval for flammable refrigerants (R290/R600a). R290/R600a end-use applications employing under the IEC60079-15 requirements. |
Display operation
The buttons on the front of the display can be operated with short and long (3s) presses.
A | Status indication: LEDs light up at ECO/Night mode, cooling, defrost, ing, and fan running. |
B | Alarm indication: The alarm icon flashes in case of an alarm. |
C | Short press = Navigate back Long press = Initiate pulldown cycle. The display will show “Pud” to confirm the start. |
D | Short press = Navigate up Long press = Switch controller ON/OFF (setting r12 Main switch in ON/OFF position) |
E | Short press = Navigate down Long press = Start the defrosting cycle. The display will show the code “-d-“ to confirm the start. |
F | Short press = Change set point Long press = Go to the parameter menu |
View alarms:
- Temperature and alarm codes alternate ˛ashes until the alarm is resolved. The alarm bell ˛ashes during alarm condition.
Lock keyboard:
- After 5 minutes of no activity, the keypad is locked (if P76=yes).
- When the keypad is locked any button press shows “LoC” in the display.
- Press the UP and DOWN buttons simultaneously for 3 seconds to unlock the keyboard. “until” is displayed for 3 s
Factory resetting
The controller can be set back to factory settings by using the following procedure.
- Power OFF controller
- Keep up “∧” and down “∨” arrow buttons pressed while reconnecting the supply voltage
- When the code “Fac” is shown in the display, select “yes
Note: The OEM factory setting will either be the Danfoss factory settings or a user deÿned factory setting if one has been made. The user can save his setting as OEM factory setting via parameter o67.
Display codes
Display code | Description |
-d- | The defrost cycle is in progress |
Pud | A temperature pulldown cycle has been initiated |
Err | The temperature cannot be displayed due to a sensor error |
— | Shown at the top of the display: The parameter value has reached the max. Limit |
— | Shown at the bottom of the display: The parameter value has reached min. Limit |
Loc | The display keyboard is locked |
URL | The display keyboard has been unlocked |
PS | The access code is required to enter the parameter menu |
Axx/Exx | Alarm or error code flashing with normal temp. readout |
OFF | Control is stopped as the r12 Main switch is set OFF |
On | Control is started as r12 Main switch is set ON (code shown in 3 seconds) |
Fac | The controller is reset to the factory setting |
Navigation
- The parameter menu is accessed by pressing the “SET” key for 3 seconds. If an access protection code “o05” has been deÿned the display will ask for the access code by showing the code “PS”.
- Once the access code has been provided by the user, the parameter list will be accessed.
Get a good start
With the following procedure, you can start regulation very quickly.
- Press the “SET” button for 3 seconds and access the parameter menu (display will show “in”)
- Press the down button “∨” to go to the “cFg” menu (display will show “cFg”)
- Press the right/“>” key to open the conÿguration menu (display will show r12)
- Open the “r12 Main switch” parameter and stop control by setting it OFF (Press SET)
- Open the “o61 application mode” and select the needed application mode (Press SET)
- Open the “o06 Sensor type” and select the temperature sensor type used (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) – (Press “SET”).
- Open the “o02 DI1 Conÿguration” and select the function associated with digital input 1 (Please refer to parameter list) – (Press “SET”).
- Open the “o37 DI2 Conÿguration” and select the function associated with digital input 2 (Please refer to parameter list) –(Press “SET”).
- Open the “o62 Quick setting” parameter and select the presetting that ÿts with the application in use (please refer to the preset table below) – (Press “SET”).
- Open the “o03 Network address” and set the Modbus address if required.
- Navigate back to parameter “r12 Main switch” and set it in the “ON” position to start control.
- Go through the entire parameter list and change the factory settings where needed.
Selection of quick settings
Quick setting | 1 | 2 | 3 | 4 | 5 | 6 | 7 |
Cabinet MT Natural def. Stop on time | Cabinet MT El. def. Stop on time | Cabinet MT El. def. Stop on temp | Cabinet LT El. def. Stop on temp | Room MT El. def. Stop on time | Room MT El. def. Stop on temp | Room LT El. def. Stop on temp | |
r00 Cut-out | 4 °C | 2 °C | 2 °C | -24 °C | 6 °C | 3 °C | -22 °C |
r02 Max Cut-out | 6 °C | 4 °C | 4 °C | -22 °C | 8 °C | 5 °C | -20 °C |
r03 Min Cut-out | 2 °C | 0 °C | 0 °C | -26 °C | 4 °C | 1 °C | -24 °C |
A13 HighLim Air | 10 °C | 8 °C | 8 °C | -15 °C | 10 °C | 8 °C | -15 °C |
A14 LowLim Air | -5 °C | -5 °C | -5 °C | -30 °C | 0 °C | 0 °C | -30 °C |
d01 Def. Method | Natural | Electrical | Electrical | Electrical | Electrical | Electrical | Electrical |
d03 Def.Interval | 6 hour | 6 hour | 6 hour | 12 hour | 8 hour | 8 hour | 12 hour |
d10 DefStopSens. | Time | Time | S5 Sensor | S5 Sensor | Time | S5 Sensor | S5 Sensor |
o02 DI1 Config. | Door FCT. | Door FCT. | Door FCT. |
Programming key
Programming controller with Mass Programming Key (EKA 201)
- Power up the controller. Make sure the controllers are connected to the mains.
- Connect the EKA 201 to the controller using the respective controller interface cable.
- The EKA 201 will automatically start the programming process.
Parameter list
Code | Short text manual | Min. | Max. | Def. | Unit | R/W | EKC 224 Appl. | |||
1 | 2 | 3 | 4 | |||||||
CFg | Configuration | |||||||||
r12 | Main switch (-1=service / 0=OFF / 1=ON) | -1 | 1 | 0 | R/W | * | * | * | * | |
o611) | Selection of application mode (1) AP1: Cmp/Def/Fan/Light (2) AP2: Cmp/Def/Fan/Alarm (3) AP3: Cmp/Al/Fan/Light (4) AP4: Heat/Alarm/Light | 1 | 4 | 1 | R/W | * | * | * | * | |
o061) | Sensor type selection (0) n5 = NTC 5k, (1) n10 = NTC 10k, (2) Pt = Pt1000, (3) Ptc = PTC 1000 | 0 | 3 | 2 | R/W | * | * | * | * | |
o021) | DI1 configuration (0) oFF=not used, (1) Sdc=status, (2) doo=door function, (3) doA=door alarm, (4) SCH=main switch, (5) nig=day/night mode, (6) rFd=reference displacement, (7) EAL=external alarm, (8) dEF=defrost, (9) Pud=pull down, (10) Sc=condenser sensor | 0 | 10 | 0 | R/W | * | * | * | * | |
o371) | DI2 configuration (0) oFF=not used, (1) Sdc=status, (2) doo=door function, (3) doA=door alarm, (4) SCH=main switch, (5) nig=day/night mode, (6) rFd=reference displacement, (7) EAL=external alarm, (8) dEF=defrost, (9) Pud=pull down | 0 | 9 | 0 | R/W | * | * | * | * | |
o621) | Quick presetting of primary parameters 0 = Not used 1 = MT, Natural defrost, stop on time 2 = MT, El defrost, stop on time 3 = MT, El defrost, stop on temp. 4 = LT, El defrost, stop on temp. 5 = Room, MT, El defrost, stop on time 6 = Room, MT, El defrost, stop on temp. 7 = Room, LT, El defrost, stop on temp. | 0 | 7 | 0 | R/W | * | * | * | ||
o031) | Network address | 0 | 247 | 0 | R/W | * | * | * | * | |
r– | Thermostat | |||||||||
r00 | Temperature setpoint | r03 | r02 | 2.0 | °C | R/W | * | * | * | * |
r01 | Di erential | 0.1 | 20.0 | 2.0 | K | R/W | * | * | * | * |
r02 | Max. limitation of setpoint setting | r03 | 105.0 | 50.0 | °C | R/W | * | * | * | * |
r03 | Min. limitation of setpoint setting | -40.0 | r02 | -35.0 | °C | R/W | * | * | * | * |
r04 | Adjustment of the display’s temperature readout | -10.0 | 10.0 | 0.0 | K | R/W | * | * | * | * |
r05 | Temperature unit (°C / °F) | 0 / C | 1 / F | 0 / C | R/W | * | * | * | * | |
r09 | Correction of the signal from the Sair sensor | -20.0 | 20.0 | 0.0 | °C | R/W | * | * | * | * |
r12 | Main switch (-1=service / 0=OFF / 1=ON) | -1 | 1 | 0 | R/W | * | * | * | * | |
r13 | Displacement of reference during night operation | -50.0 | 50.0 | 0.0 | K | R/W | * | * | * | * |
r40 | Thermostat reference displacement | -50.0 | 20.0 | 0.0 | K | R/W | * | * | * | * |
r96 | Pull-down duration | 0 | 960 | 0 | min | R/W | * | * | * | |
r97 | Pull-down limit temperature | -40.0 | 105.0 | 0.0 | °C | R/W | * | * | * | |
A– | Alarm settings | |||||||||
A03 | Delay for temperature alarm (short) | 0 | 240 | 30 | min | R/W | * | * | * | * |
A12 | Delay for temperature alarm at pulldown (long) | 0 | 240 | 60 | min | R/W | * | * | * | * |
A13 | High alarm limit | -40.0 | 105.0 | 8.0 | °C | R/W | * | * | * | * |
A14 | Low alarm limit | -40.0 | 105.0 | -30.0 | °C | R/W | * | * | * | * |
A27 | Alarm delay DI1 | 0 | 240 | 30 | min | R/W | * | * | * | * |
A28 | Alarm delay DI2 | 0 | 240 | 30 | min | R/W | * | * | * | * |
A37 | Alarm limit for condenser temperature alarm | 0.0 | 200.0 | 80.0 | °C | R/W | * | * | * |
Code | Short text manual | Min. | Max. | Def. | Unit | R/W | EKC 224 Appl. | |||
1 | 2 | 3 | 4 | |||||||
A54 | Limit for condenser block alarm and comp. Stop | 0.0 | 200.0 | 85.0 | °C | R/W | * | * | * | |
A72 | Voltage protection enable | 0/No | 1/ Yes | 0/No | R/W | * | * | * | ||
A73 | Minimum cut-in voltage | 0 | 270 | 0 | Volt | R/W | * | * | * | |
A74 | Minimum cut-out voltage | 0 | 270 | 0 | Volt | R/W | * | * | * | |
A75 | Maximum cut-in voltage | 0 | 270 | 270 | Volt | R/W | * | * | * | |
d– | Defrost | |||||||||
d01 | Defrost method (0) non = None, (1) nat = Natural, (2) El = Electrical, (3) gas = Hot gas | 0 | 3 | 2 | R/W | * | * | * | ||
d02 | Defrost stop temperature | 0.0 | 50.0 | 6.0 | °C | R/W | * | * | * | |
d03 | The interval between defrost starts | 0 | 240 | 8 | hour | R/W | * | * | * | |
d04 | Max. defrost duration | 0 | 480 | 30 | min | R/W | * | * | * | |
d05 | Time o set for start of first defrost at start-up | 0 | 240 | 0 | min | R/W | * | * | * | |
d06 | Drip o time | 0 | 60 | 0 | min | R/W | * | * | * | |
d07 | Delay for fan start after defrost | 0 | 60 | 0 | min | R/W | * | * | * | |
d08 | Fan start temperature | -40.0 | 50.0 | -5.0 | °C | R/W | * | * | * | |
d09 | Fan operation during defrosting | 0/O | 1/ On | 1/On | R/W | * | * | * | ||
d101) | Defrost sensor (0=time, 1=Sair, 2=S5) | 0 | 2 | 0 | R/W | * | * | * | ||
d18 | Max. comp. runtime between two defrosts | 0 | 96 | 0 | hour | R/W | * | * | * | |
d19 | Defrost on demand – S5 temperature’s permitted variation during frost build-up. On the central plant choose 20 K (=o ) | 0.0 | 20.0 | 20.0 | K | R/W | * | * | * | |
d30 | Defrost delay after pull-down (0 = OFF) | 0 | 960 | 0 | min | R/W | * | * | * | |
F-– | Fan | |||||||||
F01 | Fan at the top of the compressor (0) FFC = Follow comp., (1) Fao = ON, (2) FPL = Fan pulsing | 0 | 2 | 1 | R/W | * | * | * | ||
F04 | Fan stop temperature (S5) | -40.0 | 50.0 | 50.0 | °C | R/W | * | * | * | |
F07 | Fan pulsing ON cycle | 0 | 180 | 2 | min | R/W | * | * | * | |
F08 | Fan pulsing OFF cycle | 0 | 180 | 2 | min | R/W | * | * | * | |
c– | Compressor | |||||||||
c01 | Min. ON-time | 0 | 30 | 1 | min | R/W | * | * | * | |
c02 | Min. OFF-time | 0 | 30 | 2 | min | R/W | * | * | * | |
c04 | Compressor OFF delay at door open | 0 | 900 | 0 | sec | R/W | * | * | * | |
c70 | Zero crossing selection | 0/No | 1/ Yes | 1/ Yes | R/W | * | * | * | ||
o– | Miscellaneous | |||||||||
o01 | Delay of outputs at start-up | 0 | 600 | 10 | sec | R/W | * | * | * | * |
o021) | DI1configuration (0) oFF=not used, (1) Sdc=status, (2) doo=door function, (3) doA=door alarm, (4) SCH=main switch, (5) nig=day/night mode, (6) rFd=reference displacement, (7) EAL=external alarm, (8) dEF=defrost, (9) Pud=pull down, (10) Sc=condenser sensor | 0 | 10 | 0 | R/W | * | * | * | * | |
o031) | Network address | 0 | 247 | 0 | R/W | * | * | * | * | |
o05 | Access code | 0 | 999 | 0 | R/W | * | * | * | * | |
o061) | Sensor type selection (0) n5 = NTC 5k, (1) n10 = NTC 10k, (2) Pt = Pt1000, (3) Ptc = PTC 1000 | 0 | 3 | 2 | R/W | * | * | * | * | |
o15 | Display resolution (0) 0.1, (1) 0.5, (2) 1.0 | 0 | 2 | 0 | R/W | * | * | * | * | |
o16 | Max. standby time after coordinated defrost | 0 | 360 | 20 | min | R/W | * | * | * |
Code | Short text manual | Min. | Max. | Def. | Unit | R/W | EKC 224 Appl. | |||
1 | 2 | 3 | 4 | |||||||
o371) | DI2 configuration (0) oFF=not used, (1) Sdc=status, (2) doo=door function, (3) doA=door alarm, (4) SCH=main switch, (5) nig=day/night mode, (6) rFd=reference displacement, (7) EAL=external alarm, (8) dEF=defrost, (9) Pud=pull down | 0 | 9 | 0 | R/W | * | * | * | * | |
o38 | Configuration of light function (0) on=always on, (1) dAn=day/night, (2) doo=based on door action, (3) nEt = Network | 0 | 3 | 1 | R/W | * | * | * | ||
o39 | Light control via a network (only if o38=3 (nEt)) | 0/O | 1/ On | 1/ On | R/W | * | * | * | ||
o611) | Selection of application mode (1) AP1: Cmp/Def/Fan/Light (2) AP2: Cmp/Def/Fan/Alarm (3) AP3: Cmp/Al/Fan/Light (4) AP4: Heat/Alarm/Light | 1 | 4 | 1 | R/W | * | * | * | * | |
o621) | Quick presetting of primary parameters 0 = Not used 1 = MT, Natural defrost, stop on time 2 = MT, El defrost, stop on time 3 = MT, El defrost, stop on temp. 4 = LT, El defrost, stop on temp 5 = Room, MT, El defrost, stop on time 6 = Room, MT, El defrost, stop on temp. 7 = Room, LT, El defrost, stop on temp. | 0 | 7 | 0 | R/W | * | * | * | ||
o67 | Replace the controller factory settings with the present settings | 0/No | 1/ Yes | 0/No | R/W | * | * | * | * | |
o91 | Display at defrost (0) Air=Sair temperature / (1) FrE=freeze temperature / (2) -d-=”-d-” is displayed | 0 | 2 | 2 | R/W | * | * | * | ||
P– | Polarity | |||||||||
P75 | Invert alarm relay (1) = Invert relay action | 0 | 1 | 0 | R/W | * | * | * | ||
P76 | Keyboard lock enable | 0/No | 1/ Yes | 0/No | R/W | * | * | * | * | |
u– | Service | |||||||||
u00 | Control state S0: Normal, S1: Wait after defrosting, S2: Min ON timer, S3: Min OFF timer, S4: Drip o , S10: r12 Main switch set OFF, S11: Thermostat cut-out, S14: Defrosting, S15: Fan delay, S17: Door open, S20: Emergency cooling, S25: Manual control, S30: Pulldown cycle, S32: Power up delay, S33: Heating | 0 | 33 | 0 | R | * | * | * | * | |
u01 | Sair Air temperature | -100.0 | 200.0 | 0.0 | °C | R | * | * | * | * |
u09 | S5 Evaporator temperature | -100.0 | 200.0 | 0.0 | °C | R | * | * | * | * |
u10 | Status of DI1 input | 0/O | 1/ On | 0/O | R | * | * | * | * | |
u13 | Night condition | 0/O | 1/ On | 0/O | R | * | * | * | * | |
u37 | Status of DI2 input | 0/O | 1/ On | 0/O | R | * | * | * | * | |
u28 | Actual thermostat reference | -100.0 | 200.0 | 0.0 | R | * | * | * | * | |
u58 | Compressor / Liquid line solenoid valve | 0/O | 1/ On | 0/O | R | * | * | * | ||
u59 | Fan relay | 0/O | 1/ On | 0/O | R | * | * | * | ||
u60 | Defrost relay | 0/O | 1/ On | 0/O | R | * | * | |||
u62 | Alarm relay | 0/O | 1/ On | 0/O | R | * | * | * | ||
u63 | Light relay | 0/O | 1/ On | 0/O | R | * | * | * | ||
u80 | Firmware version readout | R | * | * | * | * | ||||
u82 | Controller code no. | R | * | * | * | * | ||||
u84 | Heat relay | 0/O | 1/ On | 0/O | R | * | ||||
U09 | Sc Condenser temperature | -100.0 | 200.0 | 0.0 | R | * | * | * |
Alarm codes
In an alarm situation, the display will alternate between the readout of the actual air temperature and the readout of the alarm codes of active alarms.
Code | Alarms | Description | Network alarm |
E29 | Sair sensor error | The air temperature sensor is defective or the electrical connection is lost | — Sair Error |
E27 | Def sensor error | S5 Evaporator sensor is defective or the electrical connection is lost | — S5 Error |
E30 | Sc sensor error | Sc Condenser sensor is a defect or electrical connection is lost | — Sc Error |
A01 | High temp alarm | The air temperature in the cabinet is too high | — High t.alarm |
A02 | Low temp alarm | The air temperature in the cabinet is too low | — Low t. Alarm |
A99 | High Volt alarm | The supply voltage is too high (compressor protection) | — High Voltage |
AA1 | Low Volt alarm | The supply voltage is too low (compressor protection) | — Low Voltage |
A61 | Condenser alarm | Condenser temp. too high – check airflow | — Cond Alarm |
A80 | Cond. block alarm | Condenser temp. too high – Manual reset of alarm required) | — Cond Blocked |
A04 | Door alarm | The door has been open for too long | — Door alarm |
A15 | DI Alarm | External alarm from DI input | — DI Alarm |
A45 | Standby Alarm | Control has been stopped by “r12 Main switch” | — Standby mode |
- The condenser block alarm can be reset by setting the r12 Main switch OFF and ON again or by powering down the controller.
Danfoss A/S
- Climate Solutions
- danfoss.com
- +457488 2222
- Any information, including, but not limited to information on the selection of the product, its application or use, product design, weight, dimensions, capacity, or any other technical data in product manuals catalogs descriptions, advertisements, etc., and whether made available in writing, orally, electronically, online or via download, shall be considered informative and is only binding if and to the Danfos reserves the rige iso atterits products without enotice.
- This also apies to products ordered but not die/vered sive ed that such alterations canes, be made without changes to the form, fit, or function of the product.
- All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.
- AN432635050585en-000201
- © Danfoss Climate Solutions 2023.05
Documents / Resources
![]() | Danfoss 80G8429 Case Controller Type EKC 224 [pdf] Installation Guide 80G8429, 80G8446, 80G8390, 80G8392, 80G8391, 80G8432, 80G8433, 80G8434, 84B8346, 80G8435, 80G8440, 80G8429 Case Controller Type EKC 224, 80G8429, Case Controller Type EKC 224, Controller Type EKC 224, Type EKC 224, EKC 224 |