XER-P-STP-EN Cold Room Temperature Controller
“
Product Information
Specifications
- Product Name: XER Cold Room Temperature Controller
- Model: FW rel. 93.01.01
Product Usage Instructions
User Interface
The XER Cold Room Temperature Controller features a
user-friendly interface with various screens, icons, keyboard
input, alarm frame, setpoint modification options, stand-by mode,
and an info menu.
Screens
The controller displays various screens to provide information
on temperature settings and system status.
Icons
Icons are used on the interface to represent different functions
and statuses for easy understanding.
Keyboard
The keyboard allows users to input commands and navigate through
the menu options.
Alarm Frame
Displays alarms and alerts for any issues detected by the
controller.
Setpoint Modification
Users can modify the setpoint temperature using the quick access
or menu access methods provided.
Quick Setpoint Access
Provides a shortcut to quickly adjust the setpoint
temperature.
Allows users to access a detailed menu for setting specific
temperature parameters.
Stand-By Mode
The stand-by mode allows the controller to conserve energy when
not in active use.
Access detailed information about the system and settings
through the info menu.
FAQ
1. How do I dispose of the product properly?
Refer to the Product Disposal (WEEE) section in the user manual
for guidelines on proper disposal methods.
2. How can I quickly adjust the setpoint temperature?
Use the Quick Setpoint Access feature for swift temperature
adjustments.
“`
XER
Cold Room Temperature Controller Installation Guide (FW rel. 93.01.01)
INDEX
1.
IMPORTANT USER INFORMATION………………………………………………………………………………………………………………………………………………… 4
2.
PRODUCT DISPOSAL (WEEE) ……………………………………………………………………………………………………………………………………………………….. 5
3.
USER INTERFACE ……………………………………………………………………………………………………………………………………………………………………….. 6
3.1 SCREENS ………………………………………………………………………………………………………………………………………………………………………………. 6
3.2 ICONS ………………………………………………………………………………………………………………………………………………………………………………….. 6
3.3 KEYBOARD……………………………………………………………………………………………………………………………………………………………………………. 7
3.4 ALARM FRAME ……………………………………………………………………………………………………………………………………………………………………… 8
3.5 USER INTERFACE……………………………………………………………………………………………………………………………………………………………………. 8
3.6 SETPOINT MODIFICATION ………………………………………………………………………………………………………………………………………………………. 8
3.6.1 QUICK SETPOINT ACCESS……………………………………………………………………………………………………………………………………………………. 9
3.6.2 SETPOINT MENU ACCESS……………………………………………………………………………………………………………………………………………………. 9
3.7 STAND-BY MODE …………………………………………………………………………………………………………………………………………………………………… 9
3.8 INFO MENU ………………………………………………………………………………………………………………………………………………………………………….. 9
3.9 HOTKEY UPLOAD AND DOWNLOAD ……………………………………………………………………………………………………………………………………… 10 3.10 PROGRAMMING MENU………………………………………………………………………………………………………………………………………………………… 10
3.10.1 MENU DESCRIPTIONS ………………………………………………………………………………………………………………………………………………….. 10
3.10.2 QUICK PROGRAMMING MODE ACCESS ………………………………………………………………………………………………………………………….. 11
3.10.3 PROGRAMMING MENU STRUCTURE ……………………………………………………………………………………………………………………………… 11
3.10.4 SEE AND MODIFY PARAMETERS ……………………………………………………………………………………………………………………………………. 12
3.10.5 X9: INTELLIGENT PARAMETER SEARCH AND MODIFICATION …………………………………………………………………………………………….. 12
3.10.6 USE THE PASSWORD TO ENTER THE PARAMETER LEVEL “PR2″ …………………………………………………………………………………………. 14
3.10.7 PASSWORD RESET PROCEDURE…………………………………………………………………………………………………………………………………….. 14
4.
REGULATION …………………………………………………………………………………………………………………………………………………………………………… 15
4.1 REGULATION TYPES ……………………………………………………………………………………………………………………………………………………………… 15
4.2 SINGLE ONOFF COMPRESSOR………………………………………………………………………………………………………………………………………………… 15
4.2.1 COOLING/HEATING ACTION ……………………………………………………………………………………………………………………………………………… 15
4.2.2 DEAD BAND ……………………………………………………………………………………………………………………………………………………………………. 15
4.3 DOUBLE ONOFF COMPRESSOR………………………………………………………………………………………………………………………………………………. 15
5.
PUMP DOWN ………………………………………………………………………………………………………………………………………………………………………….. 16
6.
PULL DOWN ……………………………………………………………………………………………………………………………………………………………………………. 16
7.
EVAPORATORS CONFIGURATION ……………………………………………………………………………………………………………………………………………….. 16
7.1 EVAPORATOR DEFROST MANAGEMENT………………………………………………………………………………………………………………………………….. 16
7.1.1 SINGLE EVAPORATOR WITH SINGLE PROBE ………………………………………………………………………………………………………………………… 16
7.1.2 SINGLE EVAPORATOR WITH DOUBLE PROBE……………………………………………………………………………………………………………………….. 16
7.1.3 DOUBLE EVAPORATOR …………………………………………………………………………………………………………………………………………………….. 17
7.2 EVAPORATOR FAN MANAGEMENT…………………………………………………………………………………………………………………………………………. 17
8.
DEFROST OPERATIONS……………………………………………………………………………………………………………………………………………………………… 17
8.1 DEFROST MODES…………………………………………………………………………………………………………………………………………………………………. 17
8.1.1 ELECTRIC DEFROST (tdF=EL) ……………………………………………………………………………………………………………………………………………… 17
8.1.2 HOT GAS DEFROST (tdF=in) ………………………………………………………………………………………………………………………………………………. 17
8.2 OPTIMIZED DEFROST ……………………………………………………………………………………………………………………………………………………………. 18
8.3 DISPLAY VISUALIZATION DURING ANY DEFROST PHASE …………………………………………………………………………………………………………….. 18
8.4 HEATER ELEMENT CONTROL …………………………………………………………………………………………………………………………………………………. 18
9.
CONDENSER FAN……………………………………………………………………………………………………………………………………………………………………… 18
10. AUXILIARY REGULATOR…………………………………………………………………………………………………………………………………………………………….. 18
10.1 AUXILIARY REGULATOR ………………………………………………………………………………………………………………………………………………………… 19
10.2 ONOFF REGULATION WITH DIGITAL OUTPUT …………………………………………………………………………………………………………………………… 19
11. LIGHT OUTPUTS ………………………………………………………………………………………………………………………………………………………………………. 19
12. DIGITAL OUTPUTS ……………………………………………………………………………………………………………………………………………………………………. 19
13. ANALOGUE OUTPUTS……………………………………………………………………………………………………………………………………………………………….. 19
14. ALARM SIGNALLING …………………………………………………………………………………………………………………………………………………………………. 19
14.1.1 Real Time Clock Battery Replacement ……………………………………………………………………………………………………………………………. 21
15. SERIAL COMMUNICATION…………………………………………………………………………………………………………………………………………………………. 21
16. INSTALLATION AND MOUNTING ………………………………………………………………………………………………………………………………………………… 21
16.1 DIMENSIONS ………………………………………………………………………………………………………………………………………………………………………. 21
16.2 DIN RAIL MOUNT …………………………………………………………………………………………………………………………………………………………………. 22
16.3 WALL MOUNT …………………………………………………………………………………………………………………………………………………………………….. 22
17. WIRING DIAGRAMS ………………………………………………………………………………………………………………………………………………………………….. 23
17.1 XER160P OR XER260P …………………………………………………………………………………………………………………………………………………………… 23
17.2 XER140P OR XER240P …………………………………………………………………………………………………………………………………………………………… 24
17.3 XER261P WITH CIRCUIT BREAKER ………………………………………………………………………………………………………………………………………….. 25
17.4 TERMINAL BLOCK DESCRIPTIONS …………………………………………………………………………………………………………………………………………… 26
18. TECHNICAL SPECIFICATIONS ……………………………………………………………………………………………………………………………………………………… 27
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
3/29
1. IMPORTANT USER INFORMATION
· The
symbol is intended to alert the user of a non-insultated voltage soruce within
the product area that is sufficiently high to constitute a risk of electric shock to persons.
· The
symbol is intended to alert the user of important operating and maintenance
(servicing) instructions.
· Copeland Controls S.r.l. reserves the right to modify this user’s manual at any time without prior notice. The documentation can be downloaded from the website
https://webapps.copeland.com/Dixell/Pages/Manuals even prior to purchase.
· This manual is an integral part of the product and must always be kept near the device for easy and quick reference. This document is a summarized version to ease installation. We strongly recommend the reading of the full version which contains the full parameters and functions list. The product cannot be used as a safety device. Please read this manual very carefully be sure you understand the information provided before using the device.
· Verify that the power supply voltage is correct before connecting the device. Do not expose it to water or humidity: use the controller only within the operating limits, avoiding sudden temperature changes and high atmospheric humidity in order to prevent condensation from forming. Recommendations: disconnect all the electrical connections before performing any maintenance task; insert the probe where it cannot be reached by the End User; the device must not be opened; consider the maximum current that can be applied to each relay; make sure that the wires of the probes, of the loads and the electical power supply cables are sufficiently separated from each other, without crossing or intertwining. In case of applications in industrial environments, it may be useful to use the main filters as well as the inductive loads.
· The customer shall bear full responsibility and risk for product configuration in order to achieve the the final installation of the equipment/system. Upon the customer’s request and following a specific agreement, Copeland Controls S.r.l. may be present during the start-up of the final machine/application, as a consultant, however, under no circumstances can the company be held responsible for the correct operation of the final equipment/system.
· Since Copeland Controls S.r.l. products are part of a high-level technology, a qualification and a configuration/programming/commissioning stage is required to best use them. Otherwise, these products may malfunction and Copeland Controls S.r.l. cannot be held responsible. The product must not be used in any way that differs from that stipulated in the documentation.
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
4/29
· The device must always be installed inside an electrical panel that can only be accessed by authorised personnel. For safety purposes, the keyboard must be the only part that can be reached.
· The electrical wiring connections must never be modify while the device is being used. · It is good practice to bear in mind the following indications for all Copeland Controls S.r.l.
products:
o Prevent the electronic circuits from getting wet as contact made with water, humidity or any other type of liquid can damage them. Comply with the temperature and humidity limits specified in the manual in order to store the product correctly.
o The device must not be installed in particularly hot environments as high temperatures can damage the electronic circuits and/or plastic components forming part of the casing. Comply with the temperature and humidity limits specified in the manual in order to store the product correctly.
o Prevent the device from being dropped, knocked or shaken as either can cause irreparable damage.
o Do not clean the device with corrosive chemical products, solvents or aggressive detergents. o The device must not be used in applications that differ from that specified in the following
document.
· Separate the power supply of the device from the rest of the electrical devices connected inside the electrical panel. The secondary of the transformer must never be connected to the earth.
· Copeland Controls S.r.l. reserves the right to change the components of its products, even without notice, ensuring the same and unchanged functionality.”
2. PRODUCT DISPOSAL (WEEE)
In compliance with the Directive 2002/96/EC of the European Parliament and of the Council of January 27th 2003 and to the relative national legislation, please note that:
· There lies the obligation not to dispose of electrical and electronic waste as municipal waste but to separate the waste.
· Public or private collection points must be used to dispose of the goods in accordance with local laws. Furthermore, at the end of the product’s life, it is also possible to return this to the retailer when a new purchase is made.
· This equipment may contain hazardous substances. Improper use or incorrect disposal can have adverse effects on human health and the environment.
· The symbol shown on the product or the package indicates that the product has been placed on the market after August 13th 2005 and must be disposed of as separated waste.
· Should the product be disposed of incorrectly, sanctions may be applied as stipulated in applicable local regulations regarding waste disposal.
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
5/29
3. USER INTERFACE
XER has a button user interface with an alarm frame. Specific screens can be used to enter or activate some functions.
3.1 SCREENS SCREEN
3.2 ICONS
DESCRIPTION Home: this screen shows the regulation temperature value, the measurement unit, the active alarms and the output activation. This is the first screen after power on or after exiting from other screens.
SET point modification: this screen enables the modification of the Set point.
PROGRAMMING mode: this screen enables the modification of the parameter values.
Functions: on this screen is it possible to enable some special features.
Information: these screens show the information relative to I/O (probe, digital inputs and analogue outputs).
Stand-By: in this condition all outputs are deactivated.
HotKey Download: “doL” label and alarm frame animation during download operations (copy from HotKey to the internal memory)
HotKey Upload: “UPL” label and alarm frame animation during upload operations (copy from internal memory to the HotKey)
X9: it is possible to build the label of the parameter to be visualized or modified.
DESCRIPTION
LIGHT/BACK
MODE
FUNCTION
OFF Light output OFF FLASH
ON Light output ON OFF Compressor output OFF
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
6/29
COMPRESSOR
FLASH Anti short cycle delay is running ON Compressor output ON
FAN
OFF Evaporator fan output OFF FLASH Activation delay is running
ON Evaporator fan output ON
OFF Defrost output is OFF
DEFROST
FLASH Activation delay is running
ON Defrost output is ON
ALARM
OFF No alarm is active FLASH
ON Some alarm is active
Celsius Degree
OFF Not used FLASH Not used
ON Measurement units: Celsius degree
OFF Not used
Fahrenheit Degree FLASH Not used
ON Measurement units: Fahrenheit degree
OFF
ONOFF
FLASH
ON The device is in standby mode
3.3 KEYBOARD
ICON
STANDARD
LIGHT or BACK (button “b1”)
DEFROST (button “b2”) DOWN (button “b3”) SET (button “b4”)
UP (button “b5”) STAND-BY (button “b6”)
MODE
Normal 3 sec Normal 3 sec Normal 3 sec Normal 3 sec Normal 3 sec Normal 3 sec
OTHER FUNCTIONS
Depends on par. b1C Depends on par. b1t Depends on. b2C Depends on par. b2t Depends on par. b3C Depends on par. b3t Depends on par. b4C Depends on par. b4t Depends on par. b5C Depends on par. b5t Depends on par. b6C Depends on par. b6t
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
7/29
3.4 ALARM FRAME TYPE OF ALARM Warning Lockout Man trapped alarm
LABEL ON DISPLAY Px, HA, LA, HP2, HA2, LA2,
EA, dA, rtC, rtF; bAt CA, PA, EE, SAF, PdA
tPA,
Gas leakage alarm Cleaning Fan maintenance Sanitization Parameter value modified
Parameter upper limit reached
GAS
CLt FSr, CSr
SAn Parameter value blinks 3
times
Parameter value blinks 1 time
Parameter lower limit reached
Parameter value blinks 1 time
ALARM ICON ON ON ON ON OFF OFF OFF OFF
OFF
OFF
ALARM FRAME BUZZER
OFF
ON
ON
ON
BLINK (500ms on + 500ms off)
ON
BLINK (500ms on + 500ms off)
ON
Rot Right
OFF
OFF
OFF
Rot Right
OFF
Rot Right + 2 blink
OFF
1x BLINK (500ms on +
500ms off) of upper
OFF
part of the frame
1x BLINK (500ms on + 500ms off) of the lower OFF
part of the frame
3.5 USER INTERFACE
S1
S2
S3
UP
UP
DOWN
DOWN
S5
S4
UP
UP
DOWN
DOWN
DOWN
UP
S1: Home screen S2: Direct access to Set point modification S3: Direct access to Programming mode S4: Direct access to special Function activation S5: Direct access to I/O information
Use UP or DOWN button to move through the screens S1…S5. The logic implements a circular browsing: from S1 is possible to go to S5 or to S2 depending on the pressed button. A programmable timeout is implemented to return HOME (S1) from any other screen.
3.6 SETPOINT MODIFICATION
When in HOME screen, it is possible to enter the Setpoint Menu: – By keeping the SET button pressed for 3 sec. – By moving to SET screen and entering the Setpoint menu to modify the current SET value.
The temperature measurement icon (°C or °F) will blink to indicate that the current displayed value is editable.
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
8/29
To exit from Setpoint Menu: – Wait for timeout (see par. SC1) – Press SET button to confirm value and come back to the HOME screen. – Press BACK button (button “b1”) to exit and come back to the HOME screen.
3.6.1 QUICK SETPOINT ACCESS
S1 SET
3 sec 3.6.2 SETPOINT MENU ACCESS
S1
S2
UP
SET
3.7 STAND-BY MODE
S1 OFF
3 sec
When in HOME screen, keep the OFF button pressed for 3 sec to activate stand-by mode. All outputs and alarms are deactivated in Stand-by mode. It is possible to visualize the label “oFF” timely through the par. SC9. With SC9=YES, the label “oFF” will appear 1 sec out of 10.
3.8 INFO MENU
This menu allows the immediate visualization of the available I/Os like probes, digital inputs and analogue outputs when present
UP
UP
DOWN
DOWN
SET BACK UP
DOWN
UP DOWN
SET SET
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
9/29
3.9 HOTKEY UPLOAD AND DOWNLOAD UP
DOWN
SET
SET
Verify
Err
values
End
Both HotKey Upload and Download operations can be activated only after power-on. To start the selected operation, follow these instructions:
1. Device power-off 2. Open the plastic box and insert the HotKey-64K (on the 5-pin ports on the back of the device) 3. Power-on the device and select:
a. UPL to copy the parameters from device memory to the HotKey b. doL to copy the parameters from HotKey to the device memory 4. Press the SET button to start the selected operation 5. The copying procedure will start and the alarm frame will start rotating-right 3 times during the copy operations. 6. At the end of the copying procedure, a message will notify the user that the operation has been competed: a. End: all parameters were copied b. Err: some error occourred during copying operations
3.10 PROGRAMMING MENU
When in HOME screen, it is possible to enter the Programming Menu: – By keeping the SET+DOWN buttons pressed for 3 sec. – By moving to PRG screen and entering the Programming menu to modify the current parameter values.
When into the Programming menu, the temperature measurement icon (°C or °F) will blink to indicate that the current displayed value is editable.
To exit from Programming Menu: – Wait for timeout (see par. SC5) – Press BACK button (button “b1”) until come back to the HOME screen. – Keep the BACK button (button “b1”) pressed for 3 sec to exit and come back to the HOME screen.
3.10.1 MENU DESCRIPTIONS
Parameters are also separated by groups. To access, enter Programming Menu as described in section 3.10.4 and use the UP and DOWN buttons to find GrP. Press SET and search for group labels according to the table below:
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
10/29
Group Label ALL rEG Prb diS dEF FAn AUS dYn ALr oUt inP ES Cnt rtC E2 CoM Ui inF PAS _ _ _
Description All parameters menu Main regulation parameters Probe configuration parameters Visualization parameters Defrost configuration parameters Evaporator and condenser fan configuration parameters Auxiliary regulator parameters Dynamic setpoint for condenser fan Alarm configuration parameters Digital and analogue output configuration parameters Digital input configuration parameters Energy saving configuration parameters Counters, read only values Real Time Clock configuration parameters Memory storage management Serial Communication port configuration parameters User Interface configuration parameters Information, read only parameters Password for entering protected menu parameters X9 Menu
3.10.2 QUICK PROGRAMMING MODE ACCESS
S1 SET+DOWN
3 sec
3.10.3 PROGRAMMING MENU STRUCTURE
UP
UP
DOWN
DOWN
SET BACK
UP
UP
DOWN
DOWN
UP DOWN
UP DOWN
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
11/29
3.10.4 SEE AND MODIFY PARAMETERS
UP
UP
DOWN
DOWN
UP DOWN
SET BACK
UP
UP
DOWN
DOWN
UP DOWN
SET BACK
SET
SET
3.10.5 X9: INTELLIGENT PARAMETER SEARCH AND MODIFICATION
“X9” is XER intelligent parameter navigation mechanism. Every parameter is identified by a unique label that can have two or three alphanumeric characters. When In X9 screen the system is able to drive the user through the available symbols, showing only those referring to existing parameters. For example, if a modification of the “interval between defrosts” parameters is required (label “idF”), these are the steps to follow:
1. Enter the X9 screen 2. Select the first char position (lower segment on the left will blink) 3. Use the UP button to browse through the available characters until char “i” (lowercase) appears 4. Use the DOWN button to move to the second char position (segment in the middle) 5. Use the UP button to browse through the available characters until char “d” appears 6. Use the DOWN button to move on the third char position (segment on the right) 7. Use the UP button to browse through the available characters until char “F” appears 8. Enter the par. value by using the SET button.
NOTE: pay attention to the upper or lower case when browsing through the available characters. For simplicity, here is the complete list of available characters: A, b, C, d, E, F, G, H, i, L, M, n, o, P, q, r, S, t, u, V, Y, 0, 1, 2, 3, 4, 5, 6, 7, 8 and 9.
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
12/29
UP DOWN
SET BACK
UP DOWN
UP DOWN
BACK
UP DOWN UP
SET
BACK BACK BACK
SET BACK
SET
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
13/29
3.10.6 USE THE PASSWORD TO ENTER THE PARAMETER LEVEL “PR2”
UP
UP
DOWN
DOWN
SET BACK
UP or DOWN
ERROR
SET
VERIFY VALUE
CORRECT
When in Pr2, the label of all parameters in Pr1 will have the “decimal point”. The level Pr2 will be accessible until exiting programming mode.
3.10.7 PASSWORD RESET PROCEDURE
The default password value for XER is “000”. It is possible to set a different value for entering the protected parameters (level PR2) by using the par. PSU. Par. PSU is visible and editable only in level PR2.
in If a password reset is required, follow these procedures:
3.10.7.1 Wizmate
– Connect Wizmate to the serial port – Login into Wizmate using the “Administrator” account – Scan the network and then read the existing configuration – Go to PSU parameter and read the current value or modify it as for your requirements – Update the XER parameter map if required
3.10.7.2 HOTKEY
– Upload the existing configuration using a compatible HOTKEY – Login into Wizmate using the “Administrator” account – Read the HOTKEY using the ProgTool – Go to PSU parameter and read the current value or modify it as for your requirements. – Update the XER parameter map if required (download the modified map using the HOTKEY)
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
14/29
4. REGULATION
4.1 REGULATION TYPES
Parameter “tMr” defines the management of the probe inputs for temperature regulation: 1. nu: not used. P1 will be used by default 2. LoE: regulation performed on the minimum value between selected probes 3. HiE: regulation performed on the maximum value between selected probes 4. AvG: regulation performed on weighted average of probes:
=
(01
1
+ 02 (01 +
2 02
+ +
03 03
3 + + 04)
04
4)
Where: · PAx (x=1,2,3,4): select the temperature probes to use (nP, P1, P2, P3 or P4) · C0x (x=1,2,3,4): weight value applied to each probe
Notes: · If probe PAx (x=1,2,3,4) = nP the respective probe is not considered · If probe PAx (x=1,2,3,4) is in error the probe number in error is not considered · If all selected probes for calculating the regulation temperature value are in error, the
compressor output will be controlled following par. Con and CoF.
4.2 SINGLE ONOFF COMPRESSOR 4.2.1 COOLING/HEATING ACTION
The regulation is based on the temperature measured by the regulation temperature value with a tolerance (HY) respect to the set point. · T > SET+HY (cooling) or T < SET-HY (heating):
output oAx=CP1 activation · T < SET (cooling) or T > SET (heating): output
oAx=CP1 deactivation
4.2.2 DEAD BAND
The regulation is based on the temperature measured by the regulation temperature value with a couple of differentials respect to the set point. · T > SET+HY: cooling output activation · T < SET: cooling output deactivation · T < SET-HYd: output oAx=db activation · T > SET: output oAx=db deactivation
Par. rAr set a delay between cooling and heating output activations and vice-versa.
4.3 DOUBLE ONOFF COMPRESSOR
This regulation can be activated when oAx=CP1 and oAy=CP2 and is valid only for ONOFF compressor. It allows the activation of the second compressor according to a step logic (2CC =HAF) or a parallel logic (2CC=FUL). Please refer to the complete manual for more information.
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
15/29
5. PUMP DOWN
PUMP DOWN process removes the liquid from the low pressure side, preventing liquid from entering the compressor during off-cycle and potentially damaging it. It requires a solenoid valve to close the liquid line. This function requires the following parameters to be properly configured:
· oAx (x=1,2,3…)=CP1 or CP2: a digital output set as “compressor” output · oAy (y=1,2,3…)=So1: a digital output set as “solenoid valve” output · Pdn=Y: to enable the PUMP DOWN logic · Pdt>0: maximum time for PUMP DOWN function · ixF (X=1,2)=LPS: low pressure contact to stop the PUMP DOWN · PdA>0: delay before signaling low pressure contact failure
6. PULL DOWN
The pull down activates the compressor with a different setpoint configurable by the parameter CCS and it is activated: · By pressing a button (bxt = CCt) · Automatically after defrost · Automatically after power-on if T>SET+CCS · Automatically when the regulation probe temperature T is:
– T>SET+HY+oHt value in normal mode – T>SET+HES+HYE+oHE value in energy saving mode In these cases, a different set-point value (SET+CCS) will be used. As soon as the room temperature reaches the SET+CCS value, the compressor will stop and the normal regulation will restart. NOTE: · Pull Down function is disabled when CCS=0 or CCt=0. · The CCt parameter sets the maximum activation time for any pull down. When CCt expires, the Pull Down will be immediately stopped and the standard SET-POINT will be restored.
7. EVAPORATORS CONFIGURATION
7.1 EVAPORATOR DEFROST MANAGEMENT
The XER manages the defrost up to two evaporators and uses a combination of six different parameters (MdF, MdS, dFP, dSP, dtE, dtS). The following combinations are available:
1. One evaporator with single probe (MdF, MdS = 0, dFP nu, dSP = nu, dtE, dtS =0); 2. One evaporator with dual probe management (MdF, MdS = 0, dFP nu, dSP nu, dtE, dtS); 3. Two independent evaporators (MdF, MdS, dFPnu, dSP nu, dtE, dtS)
NOTE: If one of defrost probes is not present or in error, the defrost will depend on the second defrost probe (if present and functioning). If both probes are in error or not properly set, the defrost will end by time (par. MdF)
7.1.1 SINGLE EVAPORATOR WITH SINGLE PROBE
For this configuration it is necessary to select the respective defrost probe on parameter dFP and configure the maximum defrost duration on parameter MdF (0÷255 minutes). Parameters relative to a second defrost, like MdS and dSP must be set to 0 or nu. (not used)
7.1.2 SINGLE EVAPORATOR WITH DOUBLE PROBE
For this configuration is necessary to select the respective defrost probes on dFP and dSP (dFPnu and dSPnu), configure maximum defrost duration on MdF (0÷255 minutes) and set MdS =0. The defrost will be activated when at least one of the two probes (par. dFP and dSP) measures a temperature lower than its end defrost set point (par. dtE and dtS) and ends once both probes are above their respective temperature limits, dtE and dtS.
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
16/29
7.1.3 DOUBLE EVAPORATOR
For this configuration is necessary to set the two different defrost probes through parameters dFP and dSP and the maximum defrost duration on MdF and MdS as found in the following table:
End defrost set Defrost timeout Evaporator probe Digital output
EVAPORATOR 1 par. dtE par. MdF par. dFP Relay oAx=dEF
EVAPORATOR 2 par. dtS par. MdS par. dSP Relay oAy=dF2
7.2 EVAPORATOR FAN MANAGEMENT
Evaporators fans are managed through the output set as oAx = FAn. The regulation probe must be configured through the parameter FAP (by default FAP = P2). The list of involved parameters are:
· FAP: to select the control probe · FSt: to select the deactivation setpoint · HYF: differential to restart after deactivation · FnC: to define the working mode:
o C-n: in parallel with compressor output and OFF during defrost. o O-n: always ON, OFF during any defrost o C-Y: in parallel with compressor output and always ON during defrost o o-Y: always on · Fnd: activation delay after any defrost
In case of two evaporators, the second fan will be managed by the output configured as FA2.
8. DEFROST OPERATIONS
Defrost operations can be intiated in the following ways: · EdF=rtC: by using an internal real-time clock (only for models equipped with RTC) · EdF=in: timed defrost, in this case a new defrost will start as soon as the idF timer elapses
In both cases a dripping time can be configured with parameter Fdt.
8.1 DEFROST MODES
Defrost processes are terminated by time or controlled by a temperature probe. When controlled by temperature probe, its time can be optimized by setting od2 = Y (See section 9.3 Optimized Defrost). Available defrost types are: Available defrost types are: · tdF=EL: with an electric heater · tdF=in: by using hot gas cycle
8.1.1 ELECTRIC DEFROST (tdF=EL)
To use this function, one of the following resources must be configured: · oAx=dEF · oAx=HEt (Output for the electric Heaters) · dFP=P2 (Defrost Probe)
In order to have the Heaters (oAx=HEt) working for Defrost purposes, “Htt=dEF” must be configured.
See section 9.4 Heaters Element Control for details.
8.1.2 HOT GAS DEFROST (tdF=in)
To use this function, the following resources must be configured: · oAx=dEF (Output for the 4-way Valve) · dFP=P2 (Defrost Probe)
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
17/29
8.2 OPTIMIZED DEFROST
This function must have the presence of a temperature probe to control the end defrost temperature and to set par. od2=Y. During the defrost phase, the temperature will be monitored to detect the ice on the evaporator, caracterized by a period of constant evaporator temperature. If the MdF time expires before the end defrost condition occurs, the MdF timer will be reloaded once, leading to a maximum defrost time of 2*MdF.
NOTE: The correct position of the evaporator probe is of fundamental importance for this methodology of defrost time optimization It should be placed on the position with the most ice accumulation and where the ice tends to melt last to ensure the evaporator clear of ice once the defrost ends.
8.3 DISPLAY VISUALIZATION DURING ANY DEFROST PHASE
The par. dFd permits to change the display visualization: · dFd = rt: real time temperature · dFd = it: temperature at the beginning of the current defrost · dFd = SEt: set point value used during the current defrost phase · dFd = dEF: label “dEF” during the current defrost phase · dFd = Coo: label “dEF” during the current defrost phase and label “Coo” during dripping phase.
8.4 HEATER ELEMENT CONTROL
This function can be used for: · Avoid freezing of the door gasket in low temperature applications by activating a heating resistance. · Removing ice from the dripping pipes during defrost phase
The function requires: · A relay set as oAx=HEt · A timer (par. tHE) for the cyclical activation of the HEt outputs
The HEt outputs can be controlled with par. Htt: · Htt = nu: function disabled · Htt = dEF: activation of the output only during the pre-defrost, defrost and post-defrost (dripping phases). · Htt = tiM: cyclical activation defined by par. tHE (ON and OFF cycles of equal duration and equal to par. tHE). · Htt = dor: in addition to the cyclical activation defined by par. tHE, the HEt output is forced active for 120 sec after each door opening. At the expiration of 120 seconds, the cyclical activation defined by par. tHE restarts (with first cycle OFF).
9. CONDENSER FAN
To enable the condenser fan management it is required to set a condenser probe (par. FAC). Here are the involved parameters: · FAC: to select the control probe · St2: to select the deactivation setpoint · HY2: differential for restarting fan · FCC: to define the working mode:
o C-n: in parallel with compressor output and OFF during defrost. o o-n: always ON, stopped during defrost o C-Y: in parallel with compressor output and always ON during defrost. o o-Y: always on
10. AUXILIARY REGULATOR
The auxiliary output can be managed by digital inputs (oAx=AUS, ixF=AUS): the output is switched on and off following the relative digital input status.
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
18/29
10.1 AUXILIARY REGULATOR
The auxiliary regulator can be used to manage the auxiliary output. Here are the involved parameters: · ACH: type of regulation for the auxiliary output: Ht=inversely proportional (heating); CL=directly
proportional (cooling). · SAA: set point for regulation band. · SHY: differential for regulation band. · ArP: probe for auxiliary regulator. · Sdd: auxiliary output OFF during any defrost. · 2At: start-up interval at max.
10.2 ONOFF REGULATION WITH DIGITAL OUTPUT
Heating action // Cooling action · Output activation when T<SAA-SHY // T>SAA+SHY · Output deactivation when T>SAA // T<SAA
ACH = Ht
ON
SHY
SAA
OFF
ACH = CL
OFF
SHY
ON
SAA
11. LIGHT OUTPUTS
The light output can be managed by: · When the device ON, if LAU=Y · By door opening, if ixF=dor and CLi=Y · By pressing a button, if set as bxC=LiG · Digital inputs, if set as ixF=LiG · Energy saving, if LdE=Y · Modbus command
12. DIGITAL OUTPUTS
Depending on the model, one or more digital outputs (relays) can be configurated with any of the following functionalities
oAx
Relay output oAx configuration
nu(0); CP1(1); dEF(2); FAn(3); ALr(4); ALM(5); LiG(6); AUS(7); db(8);
onF(9); HES(10); Cnd(11); CP2(12); dF2(13); FA2(14); HEt(15); inv(16); EFn(17); So1(18);
SAn(19)
nu=not used; CP1= compressor 1; dEF=defrost; Fan=evaporator fan; Alr=alarm; Alm = trapped man alarm (sirene activation); LiG=light; AUS=auxiliary relay; db=neutral zone; onF=always ON with instrument ON; HES=energy saving; Cnd=condenser fan; CP2=second onoff compressor; dF2=second defrost; FA2= second evaporator fan; HEt=heater control; inV=inverter output; EFn=air extraction fan; So1=solenoid valve; SAn=sanitization
13. ANALOGUE OUTPUTS
This controller may be equipped with up to two configurable analogue outputs (1An, 2An PWM, 0-10VdC or 4-20mA). Please refer to the full version of this manual if you must configure one of them.
14. ALARM SIGNALLING
Label Cause P1 P1 probe failure P2 P2 probe failure P3 P3 probe failure P4 P4 probe failure
How to solve
Check probe connections Alarm recovery is automatic as soon as condition is solved
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
19/29
HA High temperature inside the coldroom LA Low temperature inside the coldroom
HP2 High temperature pre-alarm
HA2 LA2
Second high temperature alarm for second evaporator probe Second low temperature alarm for second evaporator probe
dA Door open alarm
EA Warning external alarm
CA Lock external alarm
PA Pressure switch alarm
EE Internal memory alarm rtC Real time clock not properly set rtF Real time clock failure (HW problem) bAt Low battery level SAF Anti freezing alarm
tPA Trapped man alarm
Pdt Pump down
PdA Low pressure switch failure
Alarm recovery is automatic as soon as condition is solved. Check if parameters ALP, ALL and ALU have correct configuration probe Alarm recovery is automatic as soon as condition is solved.. Check if AU1 and AH1 are correctly configured
Alarm recovery is automatic as soon as condition is solved. Check if parameters AP2, AL2 and AU2 have correct configuration
Regulation recovery automatic after condition is solved (digital input deactivation) Regulation recovery automatic after condition is solved (digital input deactivation) Regulation recovery automatic after condition is solved (digital input deactivation) Alarm recovery is: · Automatic once the alarm condition is solved (digital
input deactivation) and if the number of alarm activations is less than nPS during interval dxd. · Manual, through power cycling, if the number of alarm activations is larger than nPS during interval dxd.
Alarm recovery is manual and through power cycling.
Enter programming mode and check all the “rtC” parameters Device must be repaired from Copeland Controls S.r.l. Please contact local reseller or Copeland Controls S.r.l. Service for more information Replace battery (see session 13.1) Alarm recovery is automatic as soon as temperature is T>SET.
Alarm recovery is automatic as soon as the digital input (ixF=tPA) is deactivated.
Alarm recovery is automatic as soon as the digital input (ixF=LPS) is deactivated.
Alarm recovery is manual through any button. Alarm output will be deactivated and buzzer muted, but the alarm label (PdA) will stay visible in HOME until system is checked
GAS Gas leakage alarm FSr Evaporator fan maintenance CSr Condenser fan maintenance
dEt Latest defrost ends by time
Alarm recovery is automatic as soon as the digital input (ixF=GAS) is deactivated
Alarm recovery is manual. Enter programming mode and set par. rS1=YES to reset maintenance alarm. Alarm recovery is manual. Enter programming mode and set par. rS2=YES to reset maintenance alarm.
Alarm recovery is: · Automatic if the next defrost ends before the maximum time · Manual byp ressing any button, or via modbus command
The buzzer can be muted by pressing any button and only if parameter tbA=Y.
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
20/29
14.1.1 Real Time Clock Battery Replacement Operation 1. Disconnect power supply and open the controller box
2. Remove the PCB protection cover (fixed with 2 screws)
3. Replace the battery with a new one. Battery model to use is BR1225/BN
15. SERIAL COMMUNICATION
The device supports different baudrates (par. bAU) and parity control (par. PAr). Please check the serial network to adapt them according to the other devices.
16. INSTALLATION AND MOUNTING
XER can be mounted on DIN rail or on a wall and fixed using up to 4 screws (type: D4.5mm x L55mm). The temperature range allowed for correct operation is 0 to 60°C. Avoid places subject to strong vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. 16.1 DIMENSIONS
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
21/29
16.2 DIN RAIL MOUNT 16.3 WALL MOUNT
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
22/29
17. WIRING DIAGRAMS
XER1x0P: models without lateral door for electromechanical devices. XER2xxP: models with lateral door for electromechanical devices. They can use a 16A circuit breaker
Digital outputs
Probe inputs Digital inputs
Analogue outputs Accessory
oA1 oA2
oA3
oA4 oA5 oA6 P1 P2 P3 P4 D.I.1 D.I.2 A.Out1 A.Out2 Circuit Breaker
XER140P Yes Yes Yes
No No Yes Yes Yes No No Yes Yes Optional Optional
No
XER160P Yes Yes Yes
Yes Yes Yes Yes Yes Yes Yes Yes Yes Optional Optional
No
XER240P Yes Yes Yes
No No Yes Yes Yes No No Yes Yes Optional Optional
No
XER260P Yes Yes Yes
Yes Yes Yes Yes Yes Yes Yes Yes Yes Optional Optional
No
XER241P Yes Yes Yes No No Yes Yes Yes No No Yes Yes
Optional Optional
Yes
XER261P Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Optional Optional
Yes
17.1 XER160P OR XER260P
Alarm* Light* Cond. Fan*
Evap. Fan* Def*
Comp*
*The I/O’s legend and drawings refer to factory default configuration; however, all relays, digital inputs and probes are configurable as preferred by the user.
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
23/29
17.2 XER140P OR XER240P
Alarm*
Evap. Fan* Def* Comp
*The I/O’s legend and drawings refer to factory default configuration; however, all relays, digital inputs and probes are configurable as preferred by the user.
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
24/29
17.3 XER261P WITH CIRCUIT BREAKER
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
25/29
17.4 TERMINAL BLOCK DESCRIPTIONS
PIN
Label
Description
1
5Vdc
+5Vdc output, only for X-MOD motion sensor power supply
2
D.i.1
Digital input 1
3
GND
Ground for analogue and digital inputs
4
D.i.2
Digital input 2
5
A.i.1
Analogue input 1 (temperature only)
6
GND
Ground for analogue and digital inputs
7
A.i.2
Analogue input 2 (temperature only)
8
A.i.3
Analogue input 3 (temperature only)
9
GND
Ground for analogue and digital inputs
10
A.i.4
Analogue input 4 (temperature only)
11
A.out1
Analogue output 1, PWM type
12
GND
Ground for analogue and digital inputs
13
A.out2
Analogue output 2, 0-10Vdc or 4-20mA
14
Not Used
15
Not Used
16
GND
Ground for RS485 serial port
17
RS485 (+)
Positive terminal for RS485 (+) serial port
18
RS485 (-)
Negative terminal for RS485 (-) serial port
PIN
Label
Description
20
COM-oA6
Digital ouput 6: common
21
NO-oA6
Digital ouput 6: normally open
22
NC-oA6
Digital ouput 6: normally closed
23
NO-oA5
Digital ouput 5: normally open
24
COM
Digital ouput 5: common
25
NC-oA4
Digital ouput 4: normally closed
26
NO-oA4
Digital ouput 4: normally open
27
N
High voltage power supply: Neutral
28
NO-oA3
Digital ouput 3: normally open
29
N
High voltage power supply: Neutral
30
NO-oA2
Digital ouput 2: normally open
31
N
High voltage power supply: Neutral
32
NO-oA1
Digital ouput 1: normally open
33
N
High voltage power supply: Neutral
34
L
High voltage power supply: Line
35
Not Used
36
N
High voltage power supply: Neutral
COM 1 2 W N
Label COM-1 COM-2 COM-W COM-N TERM. RS485
Description Serial communication port 1 (HOTKEY or TTL) Serial communication port 2 (TTL) (*) Serial communication port W (*) Serial communication port N (*) Terminalization for Serial communication port 1 and 2
(*) Available only on special models
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
26/29
18. TECHNICAL SPECIFICATIONS
FEATURES Housing Dimensions Mounting device Degree of Protection Power Supply Overvoltage Category Rated Power Rated Impulse Voltage Display Buzzer Software Class
Terminal blocks / Terminal Connections
Data Storing
DESCRIPTION
Self-extinguishing PC+ABS
Front 340×226 mm; case depth 98 mm
DIN rail or wall mount
EN 60529
IP54 (front panel only)
230VAC (ENEC) or 100 to 240VAC 10%, 50/60Hz
II
230VAC: 13VA (ENEC) 100-240VAC: 13VA
2500V
Red display, LED type, 3 digits with decimal point and multi-function icons
Internal, always present
A
Low voltage signals: Screw terminal block, wire section between 0,5 and 2,5 mm2 Max tightening force: 0.4 N/m High Voltage signals: Screw terminal block, wire section between 1,5 and 4 mm2 Max tightening force: 0.5 N/m
Real Time Clock: data maintenance up to 6 months with removable non-rechargeable lithium battery. Other parameters: internal flash.
Type of Action
1.B
Pollution Degree
2, non-condensing humidity
Ambient Operating Temperature and
Models without circuit breaker:
0T60°C / 32T140°F; 20-85 rH% (non-condensing humidity)
Humidity
Models with circuit breaker:
0T40°C/32T104°F; 20-85 rH% (non-condensing humidity)
Shipping and storage temperature -25T60°C; 20-85 rH% (non-condensing humidity)
Resistance to Heat
UL 94 V-0
Measurement range Accuracy
Inputs
Relay Outputs without circuit breaker (XER1x0) IEC * NOT for XER140P and XER24xP
Relay Outputs with circuit breaker (XER2x1) IEC * NOT for XER140P and XER24xP
NTC: -40T110°C, resolution 0.1°C or 1°C (selectable) PT1000: -100T150°C, resolution 0.1°C or 1°C (selectable)
NTC, PT1000: ±1% compared to the full scale If NTC probe is used: Class 0.5; less than 1% in the range [-25°C to +10°C].
Up to 4 NTC or PT1000 (configurable)
Up to 2 voltage free contacts; digital inputs connected to SELV Limited energy
oA1
20(8)A, 250Vac
oA2
20(8)A, 250Vac
oA3
10(4)A,250Vac
oA4*
10(4)A,250Vac
oA5*
8(3), 250Vac
oA6
8(3), 250Vac
Ambient temperature: 30°C
Ambient temperature 40°C
oA1
16(8)A,250Vac
14(8)A,250Vac
oA2
16(8)A,250Vac
14(8)A,250Vac
oA3
10(4)A,250Vac
10(4)A,250Vac
oA4*
10(4)A,250Vac
10(4)A,250Vac
oA5*
8(3)A,250Vac
8(3)A,250Vac
oA6
8(3),250Vac
8(3),250Vac
Nominal
Type
Optional Relays (*) Maximum ampacity on terminal 34
oA3
SPST 16A, 250VAC
Inrush type, same currents as the above configurations (with or without circuit breaker)
oA4
SPST 16A, 250VAC
Inrush type, same currents as the above configurations (with or without circuit breaker)
With Circuit Breaker: 16A MAX at 30°C ambient temperature or 14A MAX at 40°C ambient temperature (oA1+oA2+oA3+oA4+oA5+oA6 or oA1+oA2+oA3+oA4) Without Circuit Breaker: 20A MAX (oA1+oA2+oA3+oA4)
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
27/29
FEATURES
Analogue Outputs
I/O port Purpose of control Construction of control Approvals Circuit Breaker (**)
DESCRIPTION
Frequency output: Supply max voltage=12Vdc; Max supply current=2mA; duty
1Ao
cycle 50%; 0 to 166 Hz Accuracy: ±1Hz compared to the full scale
PWM: Supply max voltage=12Vdc; Max supply current=2mA; 0 to 4kHz
4-20mA 2Ao 0-10Vdc; Max supply current = 5mA
Accuracy: ±1% compared to the full scale
HOT-KEY: MAX voltage allowed is 5 VDC. DO NOT CONNECT ANY EXTERNAL POWER SUPPLY.
Operating control
Incorporated control, intended to be used in Class I or Class II equipment
R290/R600a: relays tested according to IEC EN60079:0 and IEC EN60079:15 IEC 60730-1; IEC 60730-2-9
Number of poles: 1+N; Rated Current: 16 A; C characteristic; Id =300mA, Icn= 4.5kA, Standard: IEC/EN 60898-1, IEC/EN 60947-2
(*) See official How-To-Order for available inrush models.
(**): Circuit Breaker is an optional component, selectable through official How-To-Order. Any third-party Circuit with overcurrent protection used (for replacement or for installing operations outside Copeland Controls S.r.l.) MUST HAVE the same or better characteristics.
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
28/29
1592003110 XER-P STP EN v1.0 2025.06.25.docx
XER
29/29
Documents / Resources
![]() | COPELAND XER-P-STP-EN Cold Room Temperature Controller [pdf] Installation Guide XER-P-STP-EN, XER-P-STP-EN Cold Room Temperature Controller, XER-P-STP-EN, Cold Room Temperature Controller, Temperature Controller, Controller |