CET logoModbus® Holding RegistersCET CGAS D Digital Gas DetectorsCET Digital
Gas Detectors
www.critical-environment.com

CGAS-D Digital Gas Detectors

The CGAS-D, CGAS-DP, LPT-M and LPT-P transmitters and the cGas-SC Self Contained Controller may be configured as part of a Modbus® RTU RS-485 network. In order for communication to be successful between devices, be sure your network connection is complete, the network termination switches are set appropriately and all the devices are configured with the same baud rate, character format, etc. Each device will have its own unique Modbus® ID.
NOTES:

  • CGAS-D and CGAS-DP can have up to 2 gas channels (or 1 gas and 1 particulate channel) plus an RH channel and a Temperature channel
  • The cGas-SC can have up to 3 gas channel plus a horn, strobe, buzzer, RH and Temperature channel
  • The LPT-P does not support a relay.
  • LPT-P and LPT-M can have up to 3 gas channels.

If you have specific requirements, have any questions or require clarification about these holding registers, please contact CET for assistance.
Holding Registers From 1 to 50,320

 Register Description Information
1Internal Relay 1 output status (excluding LPT-P)
2Internal Relay 2 output status (cGas-SC only)
3Strobe (cGas-SC only)
4Internal or External Buzzer (cGas-SC only)
30,001Channel 1 Readingpresent reading x scalerLEL, PPM, %VOL, μg/m3
 30,004
30,005
Channel 1 Alarm Status
Channel 2 Reading
present reading x scalerLEL, PPM, %VOL, μg/m3
30,008Channel 2 Alarm Status
30,009 Channel 3 Readingpresent reading x scalerLEL, PPM, %VOL, DegC, DegF, %RH
30,012Channel 3 Alarm Status
30,013Channel 4 Readingpresent reading x scalerLEL, PPM, %VOL, DegC, DegF, %RH
30,016Channel 4 Alarm Status
30,017Channel 5 Readingpresent reading x scalerLEL, PPM, %VOL, μg/m3
30,020Channel 5 Alarm Status
40,101Number of Relays present (excluding LPT-P)
40,103Number of Channels present
41,013 to 41,028Model Name32 bytes
41,035 to 41,042Serial Number16 bytes
41,045Firmware Versionif changed by program, may require Reset
41,113Modbus IDif changed by program, may require Reset
41,114Modbus Baud Rateif changed by program, may require Reset
45,002Relay On Delay (excluding LPT-P)seconds
45,003Relay Off Delay (excluding LPT-P)seconds

CHANGING ANY VALUES IN THE CHANNEL HOLDING REGISTERS WILL VOID ANY CALIBRATION OR LIABILITY FOR CORRECT OPERATION. THESE VALUES ARE FOR REFERENCE ONLY.

Register  Description Sensor Scaler Information
50,004Decimal Placemultiplier (1, 10, 100, 1000)
50,005Sensor Rangedecimals (0, 1, 2)
50,008Low Alarm Set Pointwith scaler factor
50,011Mid Alarm Set Pointwith scaler factor
50,012High Alarm Set Pointwith scaler factor
50,013Gas/Value Namewith scaler factor
50,025 to 50,027Gas/Value Units
50,028 to 50,030eg. LEL, PPM, %VOL, DegC, DegF, %RH
50,033Priority Membership
50,079Channel 1 Warmup Timer

Repeat 50,004 to 50,079 for each channel that is present. Each channel has an offset of 80 from the previous channel’s equivalent register.
© 2024 All rights reserved. Data subject to change without notice.

SAFER AIR EVERYWHERE.
www.critical-enviroment.com
Unit 145, 7391 Vantage Way, Delta, BC V4G 1M3 Canada
Tel: +1.604.940.8741 Toll
Free: +1.877.940.8741
© 2024 All rights reserved. Data subject
to change without notice.

Documents / Resources

CET CGAS-D Digital Gas Detectors [pdf] Instruction Manual
CGAS-D Digital Gas Detectors, CGAS-D, Digital Gas Detectors, Gas Detectors, Detectors

References

Leave a comment

Your email address will not be published. Required fields are marked *