CAMDEN-LOGO

Camden CV-110SPK Standalone Keypad/Prox Access Control

Camden-CV-110SPK-Standalone-Keypad-Prox-Access-Control-PORODUCT-NEW

Standalone Keypad/Prox Access Control

Installation Instructions

Packing List

QtyNameRemarks
111221KeypadUser manual Screwdriver Wall plugsSelf-tapping screws Torx screw  0.8” x 2.4” (20 mm×60 mm)0.24” x 1.2” (6 mm×30 mm)0.16” x 1.1” (4 mm×28 mm)0.12” x 0.24” (3 mm×6 mm)

Camden-CV-110SPK-Standalone-Keypad-Prox-Access-Control-01

Description

The CV-110SPK is a single door multifunction standalone keypad with a wiegand output for interfacing to an access control system or remote card reader. It is suitable for mounting either indoor or outdoor in harsh environments. It is housed in a strong, sturdy and vandal proof Zinc Alloy electroplated case. The electronics are fully potted so the unit is waterproof and conforms to IP68. This unit supports up to 2000 users in either a Card, 4 digit PIN, or a Card + PIN option. The built-in prox card reader supports 125KHZ EM cards. The unit has many extra features including lock output current short circuit protection, wiegand output, and a backlit keypad. These features make the unit an ideal choice for commercial and industrial applications such as factories, warehouses, laboratories, banks and prisons.

Features

  • 2000 users, supports Card, PIN, Card + PIN
  • Backlit keys
  • Zinc Alloy Electroplated anti-vandal case
  • Waterproof, conforms to IP68
  • • Easy to install and program
  • Wiegand 26 output for connection to a controller-
  • Full programming from the keypad
  • Can be used as a stand-alone keypad
  • Wiegand 26 input for connection to external reader
  • Adjustable Door Output time, Alarm time, Door Open time
  • Very low power consumption (30mA)
  • Fast operating speed, <20ms with 2000 users
  • Lock output current short circuit protection
  • Built in light dependent resistor (LDR) for anti-tamper
  • Built in buzzer
  • Red, Yellow and Green LEDS status indicators

Quick Reference Programming Guide

Camden-CV-110SPK-Standalone-Keypad-Prox-Access-Control-02 Camden-CV-110SPK-Standalone-Keypad-Prox-Access-Control-3

Specifications

Operating Voltage12V DC ±10%
User Capacity2,000
Card Reading Distance1.25” to 2.4” (3 cm to 6 cm)
Active Current< 60mA
Idle Current25±5 mA
Lock Output LoadMax 3A
Alarm Output LoadMax 20mA
Operating Temperature-49°F to 140°F (-45°C to 60°C)
Operating Humidity10% – 90% RH
WaterproofConforms to IP 68
Adjustable Door Relay time0 – 99 seconds
Adjustable Alarm Time0 – 3 minutes
Wiegand InterfaceWiegand 26 bit
Wiring ConnectionsElectric Lock, Exit Button, External Alarm, External Reader
Dimensions5 15/16” H x 1 3/4” W x 1” D (150 mm x 44 mm x 25 mm)

Installation

  • Remove the back cover from the keypad using the supplied special screw driver
  • Drill 2 holes on the wall for the Self tapping screws and 1 hole for the cable
  • Put the supplied wall plugs into the two holes
  • Attach the back cover firmly to the wall with the 2 Self tapping screws
  • Thread the cable through the cable hole
  • Attach the keypad to the back cover

Camden-CV-110SPK-Standalone-Keypad-Prox-Access-Control-5

Wiring

ColorFunctionDescription
PinkBELL_ADoorbell
Pale BlueBELL_BDoorbell
GreenD0Wiegand output D0
WhiteD1Wiegand output D1
GreyALARMAlarm negative (alarm positive connected 12 V+)
YellowOPENExit button (the other end connected GND)
BrownD_INDoor Contact switch (the other end connected GND)
Red12V+12V + DC Regulated Power Input
BlackGND12V – DC Regulated Power Input
BlueNORelay Normally Open
PurpleCOMRelay Common
OrangeNCRelay Normally Closed

Common power supply diagram

Camden-CV-110SPK-Standalone-Keypad-Prox-Access-Control-6

To Reset to Factory Default

  • Disconnect power from the unit
  • Press and hold # key while powering the unit back up
  • On hearing two “Beeps” release # key, system is now back factory settings

Note: Only the installer data is restored, user data will not be affected.

Anti-Tamper Alarm

The unit uses a LDR (light dependent resistor) as an anti-tamper alarm. If the keypad is removed from the cover, the tamper alarm will operate.

Sound and Light indication

Operation StatusRed LightGreen LightYellow LightBuzzer
Power onBrightBeep
Stand byBright
Press keypadBeep
Operation successfulBrightBeep
Operation failedBeep/Beep/Beep
Enter into programming modeBright
In the programming modeBrightBeep
Exit from the programming modeBrightBeep
Open the doorBrightBeep
AlarmBrightAlarm

Detailed Programming Guide
User Settings

Camden-CV-110SPK-Standalone-Keypad-Prox-Access-Control-7 Camden-CV-110SPK-Standalone-Keypad-Prox-Access-Control-8 Camden-CV-110SPK-Standalone-Keypad-Prox-Access-Control-9 Camden-CV-110SPK-Standalone-Keypad-Prox-Access-Control-10 Camden-CV-110SPK-Standalone-Keypad-Prox-Access-Control-11 Camden-CV-110SPK-Standalone-Keypad-Prox-Access-Control-12

Door Settings Camden-CV-110SPK-Standalone-Keypad-Prox-Access-Control-13 Camden-CV-110SPK-Standalone-Keypad-Prox-Access-Control-14

Interfacing to an Access Control System

In this mode the keypad provides a 26 bit wiegand output. The wiegand data lines can be connected to any controller which supports the 26 bit wiegand protocol.

In this mode the keypad provides a 26 bit wiegand output. The wiegand data lines can be connected to any controller which supports the 26 bit wiegand protocol.Keypad 8 bit Burst Mode

Every key pressed generates an 8 bit data stream that is transmitted over the wiegand bus.

KeyOutputKeyOutput
011110000610010110
111100001710000111
211010010801111000
311000011901101001
410110100*01011010
510100101#01001011

Camden-CV-110SPK-Standalone-Keypad-Prox-Access-Control-16

5502 Timberlea Blvd., Mississauga, ON Canada L4W 2T7
www.camdencontrols.com Toll Free: 1.877.226.3369
File: Standalone Keypad/Prox Access Control Installation Instructions.indd R3
Revision: 05/03/2018