BROAN FG7TE Series Two Stage Fixed Speed ECM High Efficiency Up flow Gas Furnaces

BROAN FG7TE Series Two Stage Fixed Speed ECM High Efficiency Up flow Gas Furnaces

Introduction

Smaltite®

Two Stage, Fixed Speed ECM,
High Efficiency Up flow Gas Furnaces

Induced Draft – 96% AFUE
Input 60,000
– 115,000 But

The high efficiency up flow gas furnace may be installed free standing in a utility room, basement, or enclosed in an alcove or closet. The extended flush jacket provides a pleasing “appliance appearance.” Design certified by CSA for application in Canada and the United States.

FEATURES and BENEFITS

  • Multi-speed Direct Drive Blower: Energy-efficient brushless DC (ECM) fixed-speed motor offers 16 speeds designed to give a wide range of cooling capacities.
  • Smart Lite® Technology: Auto-adjusts igniter on time to extend igniter life.
  • Hot Surface Igniter: Innovative application of a silicon nitride type igniter.
  • 30 Second Blower Delay: At start-up assures a warm duct temperature at furnace start-up. Adjustable blower off settings (60, 90, 120 and 180 seconds).
  • 30 Second Post Purge: 30 Second Post Purge Increases life of heat exchanger.
  • 60 Second Fixed Cooling Cycle Blower-Off Delay (TDR): Increases cooling performance when matched with a Nortek Global HVAC coil.
  • Color Coded Wire Harness: Designed to fit the components, all with quick-connect fittings for ease of service and replacement.
  • Diagnostic Lights: Dedicated light for flame signal strength and 2 lights in combination to indicate all other fault codes with easy to recognize states without counting flashes.
  • Integrated Control Boards: With connections for electronic air cleaner, humidifier, and dehumidification.
    Ergonomically located for ease of service.
  • 2 Stage Inducer: Optimizes efficiency on first stage heat and reduces sound levels.
  • Heat Exchanger: Heavy gauge aluminized steel primary heat exchanger and stainless steel secondary heat exchanger assures a long life.
  • 100% Fired and Tested: All units and each component are tested on the manufacturing line.
  • Best Packaging in the Industry: Unique corner post design assures product will arrive to the homeowner dent free.
  • Flexible Category IV Venting System: May be vertically or horizontally vented using either a one-pipe or two-pipe system for maximum flexibility in installation.
  • Low Boy Height: Easy to apply in low ceiling applications, works well with taller high SEER coils, easier to handle and install.
  • LP Convertible: Simple burner orifice and regulator spring change for ease of convertibility (as an accessory).
  • Two Piece Door Design: Enhances furnace appearance and uses captured screws to prevent losing door screws.
  • Blower Compartment: Sealed door to reduce air leakage and insulated for ultra quiet operation.
  • Sealed Vestibule: Reduces burner and inducer sound levels.
  • Furnace Air Leakage: These furnaces comply with Energy Star cabinet air leakage requirement of less than or equal to 2%. Keep the conditioned air flowing to where it’s needed.

LOCATION OF FURNACE COMPONENTS

Location Of Furnace Components

DIMENSIONS

*TE 96% Up flow Furnace

Cabinet Size Dim. “A” Dim. “B” Dim. “C”
‘A’ Cabinet 14 1/4 12 5/8 12 7/8
‘B’ Cabinet 17 1/2 15 7/8 16 1/8
‘C’ Cabinet 21 19 3/8 19 5/8
‘D’ Cabinet 24 1/2 22 7/8 23 1/8

NOTES:

Dimensions shown in inches.
  • TOP VIEW
    Dimensions
  • BOTTOM VIEW
    Dimensions
  • LEFT SIDE
    Dimensions
  • FRONT VIEW
    Dimensions
  • RIGHT SIDE
    Dimensions

MODEL IDENTIFICATION CODE

Model Identification Code

SPECIFICATIONS

FG7TE MODEL NUMBERS -035D-E23A1 -060D-E24B1 -080D-E35C1 -100D-E35C1 -115D-E45D1
Input – But (a) 35000 / 23000 60000 / 39000 80000 / 52000 100000 / 65000 115000 / 74750
Heating Capacity – But 33000 / 22000 58000 / 37000 77000 / 50000 96000 / 62000 110000 / 72000
AFUE 96.0 96.0 96.0 96.0 96.0
Motor H.P. – Speed – Type 1/2 – BLDC 3/4 – BLDC 1 – BLDC 1 – BLDC 1 – BLDC
Motor FLA 6.9 8.8 11.5 11.5 11.5
Rated Ext. SP – In. W.C. 0.50 0.50 0.50 0.50 0.50
Temperature Rise Range – F 30-60 30-60 30-60 35-65 40-70
Shipping Weights 101 lb 120 lb 130 lb 135 lb 145 lb
SKU 1037159F 1025958F 1025959F 1025960F 1025961F

Note:

All models are 115V, 60 Hz. Gas Connections are 1/2″ N.P.T. AFUE = Annual Fuel Utilization Efficiency

(a) Ratings to 2,000 ft. Over 2,000 ft. reduce 4% for each 1,000 ft. above sea level.

G7TE-035D-E23A1 (FSHE)

HEATING AIRFLOW (CFM) & TEMPERATURE RISE (°F)
Model Number/ Heating Input MOTOR SWITCH SETTINGS (0=OFF, 1=ON) External Static Pressure (in .w. c.)
0.1 0.2 0.3 0.4 0.5
1 2 3 4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
G7TE-035D-E23A1 35,000 BTU/hr 0 0 0 0
1 0 0 0 560 56 515 60
0 1 0 0 570 55 540 58
1 1 0 0 670 46 635 49 595 52 565 55 525 59
0 0 1 0 700 44 670 46 635 49 600 52 565 55
1 0 1 0 765 41 725 43 690 45 660 47 625 50
0 1 1 0 795 39 755 41 720 43 690 45 650 48
1 1 1 0 845 37 810 38 775 40 740 42 705 44
0 0 0 1 895 35 860 36 825 38 790 39 760 41
1 0 0 1 905 34 870 36 840 37 805 39 770 40
0 1 0 1 950 33 920 34 885 35 850 37 820 38
1 1 0 1 990 31 955 33 925 34 890 35 860 36
0 0 1 1 1010 31 980 32 945 33 910 34 885 35
1 0 1 1 1050 30 1015 31 985 32 955 33 925 34
0 1 1 1 1045 30 1020 31 990 31 960 32
1 1 1 1
COOLING AIRFLOW (CFM)
Model Number/ Heating Input MOTOR SWITCH SETTINGS (0=OFF, 1=ON) External Static Pressure (in. w. c.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
5 6 7 8 CFM CFM CFM CFM CFM CFM CFM CFM
G7TE-035D-E23A1 35,000 BTU/hr 0 0 0 0
1 0 0 0 560 515 475
0 1 0 0 570 540 505 460
1 1 0 0 670 635 595 565 525 485
0 0 1 0 700 670 635 600 565 530 485
1 0 1 0 765 725 690 660 625 585 550 510
0 1 1 0 795 755 720 690 650 615 580 545
1 1 1 0 845 810 775 740 705 675 640 600
0 0 0 1 895 860 825 790 760 725 695 660
1 0 0 1 905 870 840 805 770 740 700 670
0 1 0 1 950 920 885 850 820 785 760 720
1 1 0 1 990 955 925 890 860 830 800 765
0 0 1 1 1010 980 945 910 885 850 820 790
1 0 1 1 1050 1015 985 955 925 895 865 830
0 1 1 1 1080 1045 1020 990 960 930 895 865
1 1 1 1 1105 1075 1045 1015 985 955 920 895

*NOTES: 

  1. Motor switch settings for heating speeds use HEAT switches 1, 2, 3, & 4 and for cooling speeds use COOL switches 5, 6, 7, & 8.
  2. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  3. Data is shown without filter.
  4. Temperature rises in the table are approximate. Actual temperature rises may vary.
  5. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  6. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  7. When in low stage heat, the airflow is approximately 70% of the tables high value (2-stage furnaces only).

G7TE-060D-E24B1 (FSHE)

HEATING AIRFLOW (CFM) & TEMPERATURE RISE (°F)
Model Number/ Heating Input MOTOR SWITCH SETTINGS (0=OFF, 1=ON) External Static Pressure (in. w. c.)
0.1 0.2 0.3 0.4 0.5
1 2 3 4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
G7TE-060D-E24B1 60,000 BTU/hr 0 0 0 0
1 0 0 0
0 1 0 0
1 1 0 0
0 0 1 0
1 0 1 0 940 57 890 60
0 1 1 0 990 54 945 56 905 59
1 1 1 0 1,055 51 1,015 53 970 55 930 57 890 60
0 0 0 1 1,135 47 1,095 49 1,055 51 1,010 53 960 56
1 0 0 1 1,185 45 1,145 47 1,105 48 1,065 50 1,030 52
0 1 0 1 1,250 43 1,210 44 1,170 46 1,135 47 1,095 49
1 1 0 1 1,290 41 1,255 42 1,220 44 1,180 45 1,145 47
0 0 1 1 1,315 41 1,275 42 1,240 43 1,200 44 1,160 46
1 0 1 1 1,350 40 1,315 41 1,280 42 1,245 43 1,205 44
0 1 1 1 1,390 38 1,350 40 1,315 41 1,275 42 1,240 43
1 1 1 1
COOLING AIRFLOW (CFM)
Model Number/ Heating Input MOTOR SWITCH SETTINGS (0=OFF, 1=ON) External Static Pressure (in. w. c.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
5 6 7 8 CFM CFM CFM CFM CFM CFM CFM CFM
G7TE-060D-E24B1 60,000 BTU/hr 0 0 0 0
1 0 0 0
0 1 0 0
1 1 0 0 725
0 0 1 0 810
1 0 1 0 940 890 845 795 750 700
0 1 1 0 990 945 905 860 820 775 735 690
1 1 1 0 1,055 1,015 970 930 890 845 805 760
0 0 0 1 1,135 1,095 1,055 1,010 960 930 890 850
1 0 0 1 1,185 1,145 1,105 1,065 1,030 990 950 910
0 1 0 1 1,250 1,210 1,170 1,135 1,095 1,055 1,020 980
1 1 0 1 1,290 1,255 1,220 1,180 1,145 1,110 1,075 1,040
0 0 1 1 1,315 1,275 1,240 1,200 1,160 1,120 1,085 1,045
1 0 1 1 1,350 1,315 1,280 1,245 1,205 1,170 1,135 1,100
0 1 1 1 1,390 1,350 1,315 1,275 1,240 1,200 1,160 1,125
1 1 1 1 1,420 1,380 1,345 1,310 1,270 1,235 1,200 1,160

*NOTES: 

  1. Motor switch settings for heating speeds use HEAT switches 1, 2, 3, & 4 and for cooling speeds use COOL switches 5, 6, 7, & 8.
  2. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  3. Data is shown without filter.
  4. Temperature rises in the table are approximate. Actual temperature rises may vary.
  5. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  6. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  7. When in low stage heat, the airflow is approximately 70% of the tables high value (2-stage furnaces only).

FG7TE-080D-E35C1 (FSHE)

HEATING AIRFLOW (CFM) & TEMPERATURE RISE (°F)
Model Number/ Heating Input MOTOR SWITCH SETTINGS (0=OFF, 1=ON) External Static Pressure (in. w. c.)
0.1 0.2 0.3 0.4 0.5
1 2 3 4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
FG7TE-080D-E35C1 80,000 BTU/hr 0 0 0 0 1,125 63
1 0 0 0 1,205 59 1,120 63
0 1 0 0 1,305 54 1,225 58 1,150 62
1 1 0 0 1,430 50 1,350 53 1,270 56 1,190 60 1,110 63
0 0 1 0 1,525 47 1,450 49 1,375 52 1,300 55 1,225 57
1 0 1 0 1,620 44 1,540 46 1,465 49 1,390 51 1,315 54
0 1 1 0 1,695 42 1,620 44 1,545 46 1,465 49 1,390 51
1 1 1 0 1,770 40 1,700 42 1,630 44 1,555 46 1,485 47
0 0 0 1 1,875 38 1,805 39 1,730 41 1,655 43 1,580 45
1 0 0 1 1,905 37 1,840 39 1,775 40 1,710 42 1,640 43
0 1 0 1 1,980 36 1,910 37 1,845 39 1,780 40 1,715 41
1 1 0 1 2,025 35 1,960 36 1,895 38 1,830 39 1,765 40
0 0 1 1 2,025 35 1,960 36 1,900 37 1,840 38
1 0 1 1 2,010 35 1,945 37 1,880 37
0 1 1 1 2,035 35 1,980 36
1 1 1 1
COOLING AIRFLOW (CFM)
Model Number/ Heating Input MOTOR SWITCH SETTINGS (0=OFF, 1=ON) External Static Pressure (in. w. c.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
5 6 7 8 CFM CFM CFM CFM CFM CFM CFM CFM
FG7TE-080D-E35C1 80,000 BTU/hr 0 0 0 0 1,125 1,040 960 880 795
1 0 0 0 1,205 1,120 1,040 960 875 795
0 1 0 0 1,305 1,225 1,150 1,070 995 915 840
1 1 0 0 1,430 1,350 1,270 1,190 1,110 1,030 950 865
0 0 1 0 1,525 1,450 1,375 1,300 1,225 1,150 1,075 1,000
1 0 1 0 1,620 1,540 1,465 1,390 1,315 1,240 1,165 1,090
0 1 1 0 1,695 1,620 1,545 1,465 1,390 1,315 1,235 1,160
1 1 1 0 1,770 1,700 1,630 1,555 1,485 1,410 1,340 1,265
0 0 0 1 1,875 1,805 1,730 1,655 1,580 1,510 1,435 1,340
1 0 0 1 1,905 1,840 1,775 1,710 1,640 1,575 1,510 1,445
0 1 0 1 1,980 1,910 1,845 1,780 1,715 1,650 1,580 1,515
1 1 0 1 2,025 1,960 1,895 1,830 1,765 1,700 1,635 1,570
0 0 1 1 2,085 2,025 1,960 1,900 1,840 1,775 1,715 1,655
1 0 1 1 2,135 2,070 2,010 1,945 1,880 1,815 1,750 1,685
0 1 1 1 2,200 2,145 2,090 2,035 1,980 1,925 1,870 1,820
1 1 1 1 2,280 2,225 2,170 2,115 2,065 2,010 1,955 1,900

*NOTES: 

  1. Motor switch settings for heating speeds use HEAT switches 1, 2, 3, & 4 and for cooling speeds use COOL switches 5, 6, 7, & 8.
  2. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  3. Data is shown without filter.
  4. Temperature rises in the table are approximate. Actual temperature rises may vary.
  5. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  6. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  7. When in low stage heat, the airflow is approximately 70% of the tables high value (2-stage furnaces only).

FG7TE-100D-E35C1 (FSHE)

HEATING AIRFLOW (CFM) & TEMPERATURE RISE (°F)
Model Number/ Heating Input MOTOR SWITCH SETTINGS (0=OFF, 1=ON) External Static Pressure (in. w. c.)
0.1 0.2 0.3 0.4 0.5
1 2 3 4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
FG7TE-100D-E35C1 100,000 BTU/hr 0 0 0 0
1 0 0 0
0 1 0 0
1 1 0 0
0 0 1 0
1 0 1 0 1,620 55 1,540 58
0 1 1 0 1,695 52 1,620 55 1,545 58
1 1 1 0 1,770 50 1,700 52 1,630 55 1,555 57 1,485 60
0 0 0 1 1,875 47 1,805 49 1,730 51 1,655 54 1,580 56
1 0 0 1 1,905 47 1,840 48 1,775 50 1,710 52 1,640 54
0 1 0 1 1,980 45 1,910 47 1,845 48 1,780 50 1,715 52
1 1 0 1 2,025 44 1,960 45 1,895 47 1,830 49 1,765 50
0 0 1 1 2,085 43 2,025 44 1,960 45 1,900 47 1,840 48
1 0 1 1 2,135 42 2,070 43 2,010 44 1,945 46 1,880 47
0 1 1 1
1 1 1 1
COOLING AIRFLOW (CFM)
Model Number/ Heating Input MOTOR SWITCH SETTINGS (0=OFF, 1=ON) External Static Pressure (in. w. c.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
5 6 7 8 CFM CFM CFM CFM CFM CFM CFM CFM
FG7TE-100D-E35C1 100,000 BTU/hr 0 0 0 0 1,125 1,040
1 0 0 0 1,205 1,120 1,040
0 1 0 0 1,305 1,225 1,150 1,070 995
1 1 0 0 1,430 1,350 1,270 1,190 1,110 1,030
0 0 1 0 1,525 1,450 1,375 1,300 1,225 1,150 1,075 1,000
1 0 1 0 1,620 1,540 1,465 1,390 1,315 1,240 1,165 1,090
0 1 1 0 1,695 1,620 1,545 1,465 1,390 1,315 1,235 1,160
1 1 1 0 1,770 1,700 1,630 1,555 1,485 1,410 1,340 1,265
0 0 0 1 1,875 1,805 1,730 1,655 1,580 1,510 1,435 1,340
1 0 0 1 1,905 1,840 1,775 1,710 1,640 1,575 1,510 1,445
0 1 0 1 1,980 1,910 1,845 1,780 1,715 1,650 1,580 1,515
1 1 0 1 2,025 1,960 1,895 1,830 1,765 1,700 1,635 1,570
0 0 1 1 2,085 2,025 1,960 1,900 1,840 1,775 1,715 1,655
1 0 1 1 2,135 2,070 2,010 1,945 1,880 1,815 1,750 1,685
0 1 1 1 2,200 2,145 2,090 2,035 1,980 1,925 1,870 1,820
1 1 1 1 2,280 2,225 2,170 2,115 2,065 2,010 1,955 1,900

*NOTES: 

  1. Motor switch settings for heating speeds use HEAT switches 1, 2, 3, & 4 and for cooling speeds use COOL switches 5, 6, 7, & 8.
  2. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  3. Data is shown without filter.
  4. Temperature rises in the table are approximate. Actual temperature rises may vary.
  5. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  6. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  7. When in low stage heat, the airflow is approximately 70% of the tables high value (2-stage furnaces only).

FG7TE-115D-E45D1 (FSHE)

HEATING AIRFLOW (CFM) & TEMPERATURE RISE (°F)
Model Number/ Heating Input MOTOR SWITCH SETTINGS (0=OFF, 1=ON) External Static Pressure (in. w. c.)
0.1 0.2 0.3 0.4 0.5
1 2 3 4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
FG7TE-115D-E45D1 115,000 BTU/hr 0 0 0 0
1 0 0 0
0 1 0 0
1 1 0 0
0 0 1 0
1 0 1 0 1,760 58 1,715 60
0 1 1 0 1,835 56 1,790 57 1,745 59
1 1 1 0 1,885 54 1,840 56 1,790 57 1,745 59 1,700 60
0 0 0 1 1,945 53 1,900 54 1,850 55 1,805 57 1,760 58
1 0 0 1 1,950 52 1,905 54 1,860 55 1,820 56 1,775 58
0 1 0 1 2,075 49 2,030 50 1,990 51 1,945 53 1,900 54
1 1 0 1 2,125 48 2,085 49 2,040 50 2,000 51 1,955 52
0 0 1 1 2,170 47 2,130 48 2,090 49 2,045 50 2,005 51
1 0 1 1 2,215 46 2,180 47 2,140 48 2,105 49 2,070 49
0 1 1 1
1 1 1 1
COOLING AIRFLOW (CFM)
Model Number/ Heating Input MOTOR SWITCH SETTINGS (0=OFF, 1=ON) External Static Pressure (in. w. c.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
5 6 7 8 CFM CFM CFM CFM CFM CFM CFM CFM
FG7TE-115D-E45D1 115,000 BTU/hr 0 0 0 0 1,395 1,350 1,305 1,260 1,210 1,165 1,120
1 0 0 0 1,465 1,420 1,375 1,330 1,290 1,245 1,200 1,155
0 1 0 0 1,555 1,510 1,470 1,425 1,380 1,340 1,295 1,250
1 1 0 0 1,625 1,585 1,540 1,500 1,460 1,415 1,375 1,335
0 0 1 0 1,690 1,650 1,610 1,570 1,530 1,485 1,445 1,405
1 0 1 0 1,760 1,715 1,670 1,625 1,575 1,530 1,485 1,440
0 1 1 0 1,835 1,790 1,745 1,695 1,650 1,605 1,555 1,510
1 1 1 0 1,885 1,840 1,790 1,745 1,700 1,655 1,610 1,565
0 0 0 1 1,945 1,900 1,850 1,805 1,760 1,710 1,665 1,620
1 0 0 1 1,950 1,905 1,860 1,820 1,775 1,735 1,690 1,650
0 1 0 1 2,075 2,030 1,990 1,945 1,900 1,855 1,810 1,770
1 1 0 1 2,125 2,085 2,040 2,000 1,955 1,910 1,870 1,825
0 0 1 1 2,170 2,130 2,090 2,045 2,005 1,965 1,925 1,880
1 0 1 1 2,215 2,180 2,140 2,105 2,070 2,035 2,000 1,965
0 1 1 1 2,225 2,165 2,100 2,040
1 1 1 1 2,170 2,120 2,065

*NOTES:

  1. Motor switch settings for heating speeds use HEAT switches 1, 2, 3, & 4 and for cooling speeds use COOL switches 5, 6, 7, & 8.
  2. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  3. Data is shown without filter.
  4. Temperature rises in the table are approximate. Actual temperature rises may vary.
  5. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  6. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  7. When in low stage heat, the airflow is approximately 70% of the tables high value (2-stage furnaces only).

VENTING

All models are approved for vertical non direct (1 pipe) and direct (2 pipe) venting applications. See Vent Table below for specified sizes and allowable lengths.

FURNACE MODELS (BTU) FURNACE INSTALLATION SINGLE PIPE LENGTH (FT.)

with 1 long radius elbow**

DIRECT VENT,

DUAL PIPE LENGTH (ft.) WITH

1 long radius elbow on each pipe**

OUTLET OUTLET INLET/OUTLET INLET/OUTLET
2” Diameter 3” Diameter 2” Diameter 3” Diameter
60,000 Up flow 90 90 60 90
80,000 Up flow 40 90 40 90
100,000 Up flow 30 90 30 90
115,000 Up flow N/A 90 N/A 90

*NOTES: 

  1. Subtract 2.5 ft. for each additional 2 inch long radius elbow, 5 ft. for each additional 2 inch short radius elbow, 3.5 ft. for each additional 3 inch long radius elbow, and 7 ft. for each additional 3 inch short radius elbow. Subtract 5ft for each 2” tee and 8ft for each 3” tee.
  2. Two 45 degree elbows are equivalent to one 90 degree elbow.
  3. This table applies for elevations from sea level to 2,000 ft. For higher elevations, decrease pipe lengths by 8% per 1,000 ft of altitude.

ACCESSORIES

FG7TE KITS

Description SKU
2″ Concentric Vent Kit (US & Canada Approved) 904952
3″ Concentric Vent Kit (US & Canada Approved) 904953
2″ Side Wall Vent Kit 904617
3″ Side Wall Vent Kit 904347
U.S. LP Conversion Kit (0 to 10,000 ft.) 905028
Canada LP Conversion Kit (0 to 4,500 ft.) 905029
Bottom Return Filter 20 per Box, “B” Cabinet 904916
Bottom Return Filter 20 per Box, “D” Cabinet 904918
Side Return Filter Kit 541036
Neutralizer Kit 902377

Customer Support

Symbols

GENERAL TERMS OF LIMITED WARRANTY

Nortek Global HVAC, LLC will furnish a replacement for any part of this product which fails in normal use and service within the terms and conditions of the warranty.

For complete details of the Limited Warranty, including applicable terms and conditions, see your local installer or contact the Nortek Global HVAC, LLC warranty department for a copy.

Before purchasing this appliance, read important energy cost and efficiency information available from your retailer. Specifications and illustrations subject to change without notice and without incurring obligations. Printed in U.S.A (07/2021)

469F-0721 (Replaces 469F-0619)

www.broanhvac.net

Brogan® trademark used under license. © Nortek Global HVAC, LLC. All Rights Reserved.

Logo

Documents / Resources

BROAN FG7TE Series Two Stage Fixed Speed ECM High Efficiency Upflow Gas Furnaces [pdf] User Manual
FG7TE-035D-E23A1, FG7TE-060D-E24B1, FG7TE Series Two Stage Fixed Speed ECM High Efficiency Upflow Gas Furnaces, FG7TE Series, Two Stage Fixed Speed ECM High Efficiency Upflow Gas Furnaces, Fixed Speed ECM High Efficiency Upflow Gas Furnaces, ECM High Efficiency Upflow Gas Furnaces, Efficiency Upflow Gas Furnaces, Upflow Gas Furnaces, Gas Furnaces, Furnaces