BROAN FG7TE Series Two Stage Fixed Speed ECM High Efficiency Up flow Gas Furnaces

BROAN FG7TE Series Two Stage Fixed Speed ECM High Efficiency Up flow Gas Furnaces

Introduction

Smaltite®

Two Stage, Fixed Speed ECM,
High Efficiency Up flow Gas Furnaces

Induced Draft – 96% AFUE
Input 60,000
– 115,000 But

The high efficiency up flow gas furnace may be installed free standing in a utility room, basement, or enclosed in an alcove or closet. The extended flush jacket provides a pleasing “appliance appearance.” Design certified by CSA for application in Canada and the United States.

FEATURES and BENEFITS

  • Multi-speed Direct Drive Blower: Energy-efficient brushless DC (ECM) fixed-speed motor offers 16 speeds designed to give a wide range of cooling capacities.
  • Smart Lite® Technology: Auto-adjusts igniter on time to extend igniter life.
  • Hot Surface Igniter: Innovative application of a silicon nitride type igniter.
  • 30 Second Blower Delay: At start-up assures a warm duct temperature at furnace start-up. Adjustable blower off settings (60, 90, 120 and 180 seconds).
  • 30 Second Post Purge: 30 Second Post Purge Increases life of heat exchanger.
  • 60 Second Fixed Cooling Cycle Blower-Off Delay (TDR): Increases cooling performance when matched with a Nortek Global HVAC coil.
  • Color Coded Wire Harness: Designed to fit the components, all with quick-connect fittings for ease of service and replacement.
  • Diagnostic Lights: Dedicated light for flame signal strength and 2 lights in combination to indicate all other fault codes with easy to recognize states without counting flashes.
  • Integrated Control Boards: With connections for electronic air cleaner, humidifier, and dehumidification.
    Ergonomically located for ease of service.
  • 2 Stage Inducer: Optimizes efficiency on first stage heat and reduces sound levels.
  • Heat Exchanger: Heavy gauge aluminized steel primary heat exchanger and stainless steel secondary heat exchanger assures a long life.
  • 100% Fired and Tested: All units and each component are tested on the manufacturing line.
  • Best Packaging in the Industry: Unique corner post design assures product will arrive to the homeowner dent free.
  • Flexible Category IV Venting System: May be vertically or horizontally vented using either a one-pipe or two-pipe system for maximum flexibility in installation.
  • Low Boy Height: Easy to apply in low ceiling applications, works well with taller high SEER coils, easier to handle and install.
  • LP Convertible: Simple burner orifice and regulator spring change for ease of convertibility (as an accessory).
  • Two Piece Door Design: Enhances furnace appearance and uses captured screws to prevent losing door screws.
  • Blower Compartment: Sealed door to reduce air leakage and insulated for ultra quiet operation.
  • Sealed Vestibule: Reduces burner and inducer sound levels.
  • Furnace Air Leakage: These furnaces comply with Energy Star cabinet air leakage requirement of less than or equal to 2%. Keep the conditioned air flowing to where it’s needed.

LOCATION OF FURNACE COMPONENTS

Location Of Furnace Components

DIMENSIONS

*TE 96% Up flow Furnace

Cabinet SizeDim. “A”Dim. “B”Dim. “C”
‘A’ Cabinet14 1/412 5/812 7/8
‘B’ Cabinet17 1/215 7/816 1/8
‘C’ Cabinet2119 3/819 5/8
‘D’ Cabinet24 1/222 7/823 1/8

NOTES:

Dimensions shown in inches.
  • TOP VIEW
    Dimensions
  • BOTTOM VIEW
    Dimensions
  • LEFT SIDE
    Dimensions
  • FRONT VIEW
    Dimensions
  • RIGHT SIDE
    Dimensions

MODEL IDENTIFICATION CODE

Model Identification Code

SPECIFICATIONS

FG7TE MODEL NUMBERS-035D-E23A1-060D-E24B1-080D-E35C1-100D-E35C1-115D-E45D1
Input – But (a)35000 / 2300060000 / 3900080000 / 52000100000 / 65000115000 / 74750
Heating Capacity – But33000 / 2200058000 / 3700077000 / 5000096000 / 62000110000 / 72000
AFUE96.096.096.096.096.0
Motor H.P. – Speed – Type1/2 – BLDC3/4 – BLDC1 – BLDC1 – BLDC1 – BLDC
Motor FLA6.98.811.511.511.5
Rated Ext. SP – In. W.C.0.500.500.500.500.50
Temperature Rise Range – F30-6030-6030-6035-6540-70
Shipping Weights101 lb120 lb130 lb135 lb145 lb
SKU1037159F1025958F1025959F1025960F1025961F

Note:

All models are 115V, 60 Hz. Gas Connections are 1/2″ N.P.T. AFUE = Annual Fuel Utilization Efficiency

(a) Ratings to 2,000 ft. Over 2,000 ft. reduce 4% for each 1,000 ft. above sea level.

G7TE-035D-E23A1 (FSHE)

HEATING AIRFLOW (CFM) & TEMPERATURE RISE (°F)
Model Number/ Heating InputMOTOR SWITCH SETTINGS (0=OFF, 1=ON)External Static Pressure (in .w. c.)
0.10.20.30.40.5
1234CFMRISECFMRISECFMRISECFMRISECFMRISE
G7TE-035D-E23A1 35,000 BTU/hr0000
10005605651560
01005705554058
11006704663549595525655552559
00107004467046635496005256555
10107654172543690456604762550
01107953975541720436904565048
11108453781038775407404270544
00018953586036825387903976041
10019053487036840378053977040
01019503392034885358503782038
11019903195533925348903586036
001110103198032945339103488535
1011105030101531985329553392534
01111045301020319903196032
1111
COOLING AIRFLOW (CFM)
Model Number/ Heating InputMOTOR SWITCH SETTINGS (0=OFF, 1=ON)External Static Pressure (in. w. c.)
0.10.20.30.40.50.60.70.8
5678CFMCFMCFMCFMCFMCFMCFMCFM
G7TE-035D-E23A1 35,000 BTU/hr0000
1000560515475
0100570540505460
1100670635595565525485
0010700670635600565530485
1010765725690660625585550510
0110795755720690650615580545
1110845810775740705675640600
0001895860825790760725695660
1001905870840805770740700670
0101950920885850820785760720
1101990955925890860830800765
00111010980945910885850820790
101110501015985955925895865830
0111108010451020990960930895865
11111105107510451015985955920895

*NOTES: 

  1. Motor switch settings for heating speeds use HEAT switches 1, 2, 3, & 4 and for cooling speeds use COOL switches 5, 6, 7, & 8.
  2. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  3. Data is shown without filter.
  4. Temperature rises in the table are approximate. Actual temperature rises may vary.
  5. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  6. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  7. When in low stage heat, the airflow is approximately 70% of the tables high value (2-stage furnaces only).

G7TE-060D-E24B1 (FSHE)

HEATING AIRFLOW (CFM) & TEMPERATURE RISE (°F)
Model Number/ Heating InputMOTOR SWITCH SETTINGS (0=OFF, 1=ON)External Static Pressure (in. w. c.)
0.10.20.30.40.5
1234CFMRISECFMRISECFMRISECFMRISECFMRISE
G7TE-060D-E24B1 60,000 BTU/hr0000
1000
0100
1100
0010
10109405789060
0110990549455690559
11101,055511,01553970559305789060
00011,135471,095491,055511,0105396056
10011,185451,145471,105481,065501,03052
01011,250431,210441,170461,135471,09549
11011,290411,255421,220441,180451,14547
00111,315411,275421,240431,200441,16046
10111,350401,315411,280421,245431,20544
01111,390381,350401,315411,275421,24043
1111
COOLING AIRFLOW (CFM)
Model Number/ Heating InputMOTOR SWITCH SETTINGS (0=OFF, 1=ON)External Static Pressure (in. w. c.)
0.10.20.30.40.50.60.70.8
5678CFMCFMCFMCFMCFMCFMCFMCFM
G7TE-060D-E24B1 60,000 BTU/hr0000
1000
0100
1100725
0010810
1010940890845795750700
0110990945905860820775735690
11101,0551,015970930890845805760
00011,1351,0951,0551,010960930890850
10011,1851,1451,1051,0651,030990950910
01011,2501,2101,1701,1351,0951,0551,020980
11011,2901,2551,2201,1801,1451,1101,0751,040
00111,3151,2751,2401,2001,1601,1201,0851,045
10111,3501,3151,2801,2451,2051,1701,1351,100
01111,3901,3501,3151,2751,2401,2001,1601,125
11111,4201,3801,3451,3101,2701,2351,2001,160

*NOTES: 

  1. Motor switch settings for heating speeds use HEAT switches 1, 2, 3, & 4 and for cooling speeds use COOL switches 5, 6, 7, & 8.
  2. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  3. Data is shown without filter.
  4. Temperature rises in the table are approximate. Actual temperature rises may vary.
  5. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  6. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  7. When in low stage heat, the airflow is approximately 70% of the tables high value (2-stage furnaces only).

FG7TE-080D-E35C1 (FSHE)

HEATING AIRFLOW (CFM) & TEMPERATURE RISE (°F)
Model Number/ Heating InputMOTOR SWITCH SETTINGS (0=OFF, 1=ON)External Static Pressure (in. w. c.)
0.10.20.30.40.5
1234CFMRISECFMRISECFMRISECFMRISECFMRISE
FG7TE-080D-E35C1 80,000 BTU/hr00001,12563
10001,205591,12063
01001,305541,225581,15062
11001,430501,350531,270561,190601,11063
00101,525471,450491,375521,300551,22557
10101,620441,540461,465491,390511,31554
01101,695421,620441,545461,465491,39051
11101,770401,700421,630441,555461,48547
00011,875381,805391,730411,655431,58045
10011,905371,840391,775401,710421,64043
01011,980361,910371,845391,780401,71541
11012,025351,960361,895381,830391,76540
00112,025351,960361,900371,84038
10112,010351,945371,88037
01112,035351,98036
1111
COOLING AIRFLOW (CFM)
Model Number/ Heating InputMOTOR SWITCH SETTINGS (0=OFF, 1=ON)External Static Pressure (in. w. c.)
0.10.20.30.40.50.60.70.8
5678CFMCFMCFMCFMCFMCFMCFMCFM
FG7TE-080D-E35C1 80,000 BTU/hr00001,1251,040960880795
10001,2051,1201,040960875795
01001,3051,2251,1501,070995915840
11001,4301,3501,2701,1901,1101,030950865
00101,5251,4501,3751,3001,2251,1501,0751,000
10101,6201,5401,4651,3901,3151,2401,1651,090
01101,6951,6201,5451,4651,3901,3151,2351,160
11101,7701,7001,6301,5551,4851,4101,3401,265
00011,8751,8051,7301,6551,5801,5101,4351,340
10011,9051,8401,7751,7101,6401,5751,5101,445
01011,9801,9101,8451,7801,7151,6501,5801,515
11012,0251,9601,8951,8301,7651,7001,6351,570
00112,0852,0251,9601,9001,8401,7751,7151,655
10112,1352,0702,0101,9451,8801,8151,7501,685
01112,2002,1452,0902,0351,9801,9251,8701,820
11112,2802,2252,1702,1152,0652,0101,9551,900

*NOTES: 

  1. Motor switch settings for heating speeds use HEAT switches 1, 2, 3, & 4 and for cooling speeds use COOL switches 5, 6, 7, & 8.
  2. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  3. Data is shown without filter.
  4. Temperature rises in the table are approximate. Actual temperature rises may vary.
  5. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  6. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  7. When in low stage heat, the airflow is approximately 70% of the tables high value (2-stage furnaces only).

FG7TE-100D-E35C1 (FSHE)

HEATING AIRFLOW (CFM) & TEMPERATURE RISE (°F)
Model Number/ Heating InputMOTOR SWITCH SETTINGS (0=OFF, 1=ON)External Static Pressure (in. w. c.)
0.10.20.30.40.5
1234CFMRISECFMRISECFMRISECFMRISECFMRISE
FG7TE-100D-E35C1 100,000 BTU/hr0000
1000
0100
1100
0010
10101,620551,54058
01101,695521,620551,54558
11101,770501,700521,630551,555571,48560
00011,875471,805491,730511,655541,58056
10011,905471,840481,775501,710521,64054
01011,980451,910471,845481,780501,71552
11012,025441,960451,895471,830491,76550
00112,085432,025441,960451,900471,84048
10112,135422,070432,010441,945461,88047
0111
1111
COOLING AIRFLOW (CFM)
Model Number/ Heating InputMOTOR SWITCH SETTINGS (0=OFF, 1=ON)External Static Pressure (in. w. c.)
0.10.20.30.40.50.60.70.8
5678CFMCFMCFMCFMCFMCFMCFMCFM
FG7TE-100D-E35C1 100,000 BTU/hr00001,1251,040
10001,2051,1201,040
01001,3051,2251,1501,070995
11001,4301,3501,2701,1901,1101,030
00101,5251,4501,3751,3001,2251,1501,0751,000
10101,6201,5401,4651,3901,3151,2401,1651,090
01101,6951,6201,5451,4651,3901,3151,2351,160
11101,7701,7001,6301,5551,4851,4101,3401,265
00011,8751,8051,7301,6551,5801,5101,4351,340
10011,9051,8401,7751,7101,6401,5751,5101,445
01011,9801,9101,8451,7801,7151,6501,5801,515
11012,0251,9601,8951,8301,7651,7001,6351,570
00112,0852,0251,9601,9001,8401,7751,7151,655
10112,1352,0702,0101,9451,8801,8151,7501,685
01112,2002,1452,0902,0351,9801,9251,8701,820
11112,2802,2252,1702,1152,0652,0101,9551,900

*NOTES: 

  1. Motor switch settings for heating speeds use HEAT switches 1, 2, 3, & 4 and for cooling speeds use COOL switches 5, 6, 7, & 8.
  2. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  3. Data is shown without filter.
  4. Temperature rises in the table are approximate. Actual temperature rises may vary.
  5. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  6. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  7. When in low stage heat, the airflow is approximately 70% of the tables high value (2-stage furnaces only).

FG7TE-115D-E45D1 (FSHE)

HEATING AIRFLOW (CFM) & TEMPERATURE RISE (°F)
Model Number/ Heating InputMOTOR SWITCH SETTINGS (0=OFF, 1=ON)External Static Pressure (in. w. c.)
0.10.20.30.40.5
1234CFMRISECFMRISECFMRISECFMRISECFMRISE
FG7TE-115D-E45D1 115,000 BTU/hr0000
1000
0100
1100
0010
10101,760581,71560
01101,835561,790571,74559
11101,885541,840561,790571,745591,70060
00011,945531,900541,850551,805571,76058
10011,950521,905541,860551,820561,77558
01012,075492,030501,990511,945531,90054
11012,125482,085492,040502,000511,95552
00112,170472,130482,090492,045502,00551
10112,215462,180472,140482,105492,07049
0111
1111
COOLING AIRFLOW (CFM)
Model Number/ Heating InputMOTOR SWITCH SETTINGS (0=OFF, 1=ON)External Static Pressure (in. w. c.)
0.10.20.30.40.50.60.70.8
5678CFMCFMCFMCFMCFMCFMCFMCFM
FG7TE-115D-E45D1 115,000 BTU/hr00001,3951,3501,3051,2601,2101,1651,120
10001,4651,4201,3751,3301,2901,2451,2001,155
01001,5551,5101,4701,4251,3801,3401,2951,250
11001,6251,5851,5401,5001,4601,4151,3751,335
00101,6901,6501,6101,5701,5301,4851,4451,405
10101,7601,7151,6701,6251,5751,5301,4851,440
01101,8351,7901,7451,6951,6501,6051,5551,510
11101,8851,8401,7901,7451,7001,6551,6101,565
00011,9451,9001,8501,8051,7601,7101,6651,620
10011,9501,9051,8601,8201,7751,7351,6901,650
01012,0752,0301,9901,9451,9001,8551,8101,770
11012,1252,0852,0402,0001,9551,9101,8701,825
00112,1702,1302,0902,0452,0051,9651,9251,880
10112,2152,1802,1402,1052,0702,0352,0001,965
01112,2252,1652,1002,040
11112,1702,1202,065

*NOTES:

  1. Motor switch settings for heating speeds use HEAT switches 1, 2, 3, & 4 and for cooling speeds use COOL switches 5, 6, 7, & 8.
  2. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  3. Data is shown without filter.
  4. Temperature rises in the table are approximate. Actual temperature rises may vary.
  5. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  6. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  7. When in low stage heat, the airflow is approximately 70% of the tables high value (2-stage furnaces only).

VENTING

All models are approved for vertical non direct (1 pipe) and direct (2 pipe) venting applications. See Vent Table below for specified sizes and allowable lengths.

FURNACE MODELS (BTU)FURNACE INSTALLATIONSINGLE PIPE LENGTH (FT.)

with 1 long radius elbow**

DIRECT VENT,

DUAL PIPE LENGTH (ft.) WITH

1 long radius elbow on each pipe**

OUTLETOUTLETINLET/OUTLETINLET/OUTLET
2” Diameter3” Diameter2” Diameter3” Diameter
60,000Up flow90906090
80,000Up flow40904090
100,000Up flow30903090
115,000Up flowN/A90N/A90

*NOTES: 

  1. Subtract 2.5 ft. for each additional 2 inch long radius elbow, 5 ft. for each additional 2 inch short radius elbow, 3.5 ft. for each additional 3 inch long radius elbow, and 7 ft. for each additional 3 inch short radius elbow. Subtract 5ft for each 2” tee and 8ft for each 3” tee.
  2. Two 45 degree elbows are equivalent to one 90 degree elbow.
  3. This table applies for elevations from sea level to 2,000 ft. For higher elevations, decrease pipe lengths by 8% per 1,000 ft of altitude.

ACCESSORIES

FG7TE KITS

DescriptionSKU
2″ Concentric Vent Kit (US & Canada Approved)904952
3″ Concentric Vent Kit (US & Canada Approved)904953
2″ Side Wall Vent Kit904617
3″ Side Wall Vent Kit904347
U.S. LP Conversion Kit (0 to 10,000 ft.)905028
Canada LP Conversion Kit (0 to 4,500 ft.)905029
Bottom Return Filter 20 per Box, “B” Cabinet904916
Bottom Return Filter 20 per Box, “D” Cabinet904918
Side Return Filter Kit541036
Neutralizer Kit902377

Customer Support

Symbols

GENERAL TERMS OF LIMITED WARRANTY

Nortek Global HVAC, LLC will furnish a replacement for any part of this product which fails in normal use and service within the terms and conditions of the warranty.

For complete details of the Limited Warranty, including applicable terms and conditions, see your local installer or contact the Nortek Global HVAC, LLC warranty department for a copy.

Before purchasing this appliance, read important energy cost and efficiency information available from your retailer. Specifications and illustrations subject to change without notice and without incurring obligations. Printed in U.S.A (07/2021)

469F-0721 (Replaces 469F-0619)

www.broanhvac.net

Brogan® trademark used under license. © Nortek Global HVAC, LLC. All Rights Reserved.

Logo

Documents / Resources

BROAN FG7TE Series Two Stage Fixed Speed ECM High Efficiency Upflow Gas Furnaces [pdf] User Manual
FG7TE-035D-E23A1, FG7TE-060D-E24B1, FG7TE Series Two Stage Fixed Speed ECM High Efficiency Upflow Gas Furnaces, FG7TE Series, Two Stage Fixed Speed ECM High Efficiency Upflow Gas Furnaces, Fixed Speed ECM High Efficiency Upflow Gas Furnaces, ECM High Efficiency Upflow Gas Furnaces, Efficiency Upflow Gas Furnaces, Upflow Gas Furnaces, Gas Furnaces, Furnaces

References

Leave a comment

Your email address will not be published. Required fields are marked *