Autonics - logo4-Digit Multi Panel Meters
MT4W Series
INSTRUCTION MANUAL
TCD220015AA

Thank you for choosing our Autonics product.
Read and understand the instruction manual and manual thoroughly before using the product.
For your safety, read and follow the below safety considerations before using.
For your safety, read and follow the considerations written in the instruction manual, other manuals and Autonics website.
Keep this instruction manual in a place where you can find easily.
The specifications, dimensions, etc. are subject to change without notice for product improvement. Some models may be discontinued without notice.
Follow Autonics website for the latest information.

Safety Considerations

  • Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards.
  • Autonics - icon symbol indicates caution due to special circumstances in which hazards may occur.
    Autonics - icon Warning Failure to follow instructions may result in serious injury or death.
  1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime / disaster prevention devices, etc.) Failure to follow this instruction may result in personal injury, economic loss or fire.
  2. Do not use the unit in the place where flammable / explosive / corrosive gas, high humidity, direct sunlight, radiant heat, vibration, impact or salinity may be present.
    Failure to follow this instruction may result in explosion or fire.
  3. Install on a device panel to use.
    Failure to follow this instruction may result in fire or electric shock.
  4. Do not connect, repair, or inspect the unit while connected to a power source.
    Failure to follow this instruction may result in fire or electric shock.
  5. Check ‘Connections’ before wiring.
    Failure to follow this instruction may result in fire.
  6. Do not disassemble or modify the unit.
    Failure to follow this instruction may result in fire or electric shock.

Autonics - icon Caution Failure to follow instructions may result in injury or product damage.

  1. When connecting the power / measurement input and relay output, use AWG 24 (0.20 mm2) to AWG 15 (1.65 mm2)cable or over and tighten the terminal screw with a tightening torque of 0.98 to 1.18 N m.
    Use the wiring suitable for the load current capacity.
    Failure to follow this instruction may result in fire or malfunction due to contact failure.
  2. Use the unit within the rated specifications.
    Failure to follow this instruction may result in fire or product damage.
  3. Use a dry cloth to clean the unit, and do not use water or organic solvent.
    Failure to follow this instruction may result in fire or electric shock.
  4. Keep the product away from metal chip, dust, and wire residue which flow into the unit.
    Failure to follow this instruction may result in fire or product damage.

Cautions during Use

  • Follow instructions in ‘Cautions during Use’.
    Otherwise, It may cause unexpected accidents.
  • Power supply should be insulated and limited voltage / current or Class 2, SELV power supply device.
  • Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power.
  • Use twisted pair wire for communication line.
  • Keep away from high voltage lines or power lines to prevent inductive noise.
    In case installing power line and input signal line closely, use line filter or varistor at power line and shielded wire at input signal line.
    Do not use near the equipment which generates strong magnetic force or high frequency noise.

Connection with the line filter

Autonics MT4W Series Digital Multi Panel Meter -

Connection with the varistor

Autonics MT4W Series Digital Multi Panel Meter - Autonics MT4W Series Digital Multi Panel Meter

  • This unit may be used in the following environments.
    – Indoors (in the environment condition rated in ‘Specifications’)
    – Altitude max. 2,000 m
    – Pollution degree 2
    – Installation category II

Ordering Information

This is only for reference, the actual product does not support all combinations.
For selecting the specified model, follow the Autonics website.

Autonics MT4W Series Digital Multi Panel Meter - Autonics MT4W Series Digital Multi Panel Meter1

  1. Input type
    DV: DC voltage 01)
    DA: DC current
    AV: AC voltage 02)
    AA: AC current 02)
  2. Power supply
    1: 12 – 24 VDCSKIL QC5359B 02 20V Dual Port Charger - icon 5 ± 10 %
    4: 100 – 240 VAC∼ ± 10 % 50 / 60 Hz
  3. Preset output + Sub output
 Preset outputSub output
NNone (indicator)
0RelayTransmission (DC 4 – 20 mA)
1Relay
2NPN open collectorBCD Dynamic
3PNP open collectorBCD Dynamic
4NPN open collectorTransmission (DC 4 – 20 mA)
5PNP open collectorTransmission (DC 4 – 20 mA)
6NPN open collectorLow speed serial
7PNP open collectorLow speed serial
8NPN open collectorRS485 Communication
9PNP open collectorRS485 Communication
  1.  To measure the current over DC 5 A, please select DV type because the shunt should be used.
  2. In case of selecting frequency display, no output will be provided even if it is output support model.

Product Components

  • Product
  • Bracket × 2
  • Instruction manual
  • Unit sticker × 1

Manual

For proper use of the product, refer to the manuals and be sure to follow the safety considerations in the manuals.
Download the manuals from the Autonics website.

Software

Download the installation file and the manuals from the Autonics website.
• DAQMaster
It is the comprehensive device management program for Autonics’ products, providing parameter setting, monitoring and data management.

Dimensions

  • Unit: mm, For the detailed drawings, follow the Autonics website.
    • Indicator / Relay preset output model

Autonics MT4W Series Digital Multi Panel Meter - model1

• NPN / PNP open collector preset output model

Autonics MT4W Series Digital Multi Panel Meter - model

Autonics MT4W Series Digital Multi Panel Meter - mode2

Cautions during Wiring

Use the Copper-conductor wire with the temperature class 60 ℃.

  • Unit: mm, Use terminals of size specified below.
  • Contact the manufacture for the socket and cable.

Autonics MT4W Series Digital Multi Panel Meter - model2

Hirose connectorHIF3BA-20PA-2.54DS
Hirose connector socketHIF3BA-20D-2.54R

Autonics MT4W Series Digital Multi Panel Meter - model3

Connections

Autonics MT4W Series Digital Multi Panel Meter - model4

Specifications

ModelMT4W-DV-□□MT4W-DA-□□MT4W-AV-□□MT4W-AA-□□
Input typeDC voltageDC currentAC voltage 01)AC current 01)
Max. allowable input110 % F.S. for each measured input range
Display method7-segment (red) LED (character height: 14.2 mm)
Display accuracyDependent on the ambient temperature
23 ± 5 ℃± 0.1 % F.S. rdg ± 2 digit± 0.1 % F.S. rdg ± 2 digit 02)± 0.3 % F.S. rdg ± 3 digit± 0.3 % F.S. rdg ± 3 digit
-10 to 50 ℃± 0.5 % F.S. rdg ± 3 digit
Max. display range-1999 to 9999 (4 digit)
A / D conversion

method

ΣΔ (Sigma Delta) ADC
Sampling cycle50 ms16.6 ms
Unit weight

(packaged)

≈ 211 g (≈ 326 g)
ApprovalAutonics - icon30
  1. Available frequency display, Display accuracy (23 ± 5 ℃): ± 0.1 % F.S. rdg ± 2 digit
  2. 5 A terminal: ± 0.3 % F.S. rdg ± 3 digit
  3. Except power supply 12 – 24 VDCSKIL QC5359B 02 20V Dual Port Charger - icon 5model
Preset outputNone (indicator) / Relay / NPN open collector / PNP open collector output model
RelayContact capacity: 250 VAC∼ 3 A, 30 VDCSKIL QC5359B 02 20V Dual Port Charger - icon 53 A Contact composition: N.O (1a)
NPN / PNP open collectorOutput capacity: ≤ 12 – 24 VDCᜡ ± 2 VDCSKIL QC5359B 02 20V Dual Port Charger - icon 5, 50 mA resistive load
Sub outputNone (indicator) / BCD Dynamic / Transmission (DC 4 – 20 mA) / Low speed serial / RS485 Communication output model
BCD Dynamic / Low speed serialNPN open collector output
Output capacity: ≤ 12 – 24 VDCSKIL QC5359B 02 20V Dual Port Charger - icon 5, 50 mA resistive load
Transmission (DC 4 – 20 mA)Resolution: 1/12,000 (load resistance: ≤ 600 Ω) Response time: ≤ 450 ms
RS485 communicationProtocol: Modbus RTU
ModelMT4W-□□-1□MT4W-□□-4□
Power supply12 – 24 VDCᜡ ± 10 %100 – 240 VAC∼ ± 10 % 50 / 60

Hz

Power consumption5 W5 VA
Insulation resistanceBetween external terminal and case: ≥ 100 MΩ (500 VDCSKIL QC5359B 02 20V Dual Port Charger - icon 5 megger)
Dielectric strengthBetween external terminal and case: 2,000 VAC∼50 / 60 Hz for 1 min
Noise immunity± 2 kV square wave noise (pulse width: 1 ㎲) by the noise simulator
Vibration0.75 mm double amplitude at frequency of 10 to 55 Hz (for 1 min) in each X, Y, Z direction for 2 hours
Vibration

(malfunction)

0.5 mm double amplitude at frequency of 10 to 55 Hz (for 1 min) in each X, Y, Z direction for 10 min
Shock300 m/s2 (≈ 30 G) in each X, Y, Z direction for 3 times
Shock (malfunction)100 m/s2 (≈ 10 G) in each X, Y, Z direction for 3 times
Relay life cycleMechanical: ≥ 20,000,000 operations

Electrical: ≥ 100,000 operations (250 VAC∼ 3A resistive load)

Ambient temp.-10 to 50 ℃, storage: -20 to 60 ℃ (freezing or condensation)
Ambient humi.35 to 85 %RH, storage: 35 to 85 %RH (freezing or condensation)
Insulation typeSymbol: LG 27ART10AKPL Rollable Smart Touch Screen - Icon 21, double or reinforced insulation (dielectric strength between the measurement input part and the power part: 1 kV)

Communication Interface

■ RS485

Comm. protocolModbus RTU
Application standardCompliance with EIA RS485
Max. connection31 units (address: 01 to 99)
Comm. synchronous methodAsynchronous
Comm. method2-wire half duplex
Comm. distance≤ 800 m
Comm. speed1,200 / 1,400 / 4,800 / 9,600 / 19,200 / 38,400 bps
Start bit1-bit (fixed)
Data bit8-bit (fixed)
Parity bitNone, Even, Odd
Stop bit1-bit, 2-bit
EEPROM life cycle≈ 1,000,000 operations (Erase / Write)

Mode Setting

Autonics MT4W Series Digital Multi Panel Meter - model5

Parameter Setting

  • Some parameters are activated / deactivated depending on the model or setting of other parameters. Refer to the description of each parameter.
  • If any key is not entered for 60 sec in each parameter, it returns to RUN mode.
  • After returning to RUN mode, press the [MODE] key within 2 sec, it returns to previous parameter.
  • [MODE] key: Saves current setting value and moves to the next parameter.
    [◀] key: Checks fixed value / Changes setting digits.
    [▲], [▼] key: Changes setting values.

■ Parameter 1 group

ParameterMarkDefaultsSetting rangeDisplay condition
1-1 Input rangeAutonics - icon1Autonics - icon2[DC voltage model], [AC voltage model] •    Refer to Input Range and Display Range
Autonics - icon3[DC current model], [AC current model] •    Refer to Input Range and Display Range
1-2 Display methodAutonics - icon4Autonics - icon5STND: standard, SCAL: scale, FREQ: frequency 01)
1-3  Measurement method 

Autonics - icon6

 

 

 

Autonics - icon7

 

 

[AC voltage model], [AC current model] T.RMS: True RMS, A.RMS: Average RMS, AVGAutonics - icon8 

 

1-2

Display method: STND, SCAL

Max. display 1-4 value (fixed) 

Autonics - icon5

Autonics - icon9[DC voltage model], [AC voltage model] Max. value of display range 

 

 

 

1-2 Display method: STND

Autonics - icon10[DC current model], [AC current model] Max. value of display range
High-limit 1-5 display value gradient correctionAutonics - icon11Autonics - icon120.100 to 5.000 %
Low-limit 1-6 display value deviation correction 

Autonics - icon13

 

Autonics - icon14

 

-99 to 99

Decimal 1-7 point positionAutonics - icon15Autonics - icon16[DC voltage model], [AC voltage model] 0, 0.0, 0.00, 0.000 

 

1-2 Display method: SCAL & * 1-7 Decimal point position: 0.0, 0.00, 0.000

Autonics - icon17[DC current model], [AC current model] 0, 0.0, 0.00, 0.000
1-8 High-limit scaleAutonics - icon18Display value against max. measurement input*
1-9 Low-limit scaleAutonics - icon19Display value against min. measurement input*
High-limit 1-10 display value gradient correction 

Autonics - icon20

 

Autonics - icon21

 

0.100 to 5.000 %

Low-limit 1-11 display value deviation correction 02)Autonics - icon22Autonics - icon14-99 to 99
 

Decimal 1-12 point position 03)

Autonics - icon15Autonics - icon16[AC voltage model] 0, 0.0, 0.00, 0.000 

 

 

1-2

Display method: FREQ

Autonics - icon17[AC current model] 0, 0.0, 0.00, 0.000
High-limit 1-13 display value gradient correctionAutonics - icon25Autonics - icon260.100 to 9.999
1-14 Exponent of INBAutonics - icon27Autonics - icon2810-0: 100, 10-1: 10-1, 10-2: 10-2, 10 1: 101
  1. Displays at AC voltage or AC current model only.
  2. Low-limit display value deviation correction range is within -99 to 99 for D0, D-1
  3. Display range is variable according to decimal point position.
DotDisplay rangeFrequency measurement range
-1999 to 99991 to 9999 Hz
Autonics - icon16-199.9 to 999.90.1 to 999.9 Hz
Autonics - icon29-19.99 to 99.990.10 to 99.99 Hz
Autonics - icon24-1.999 to 9.9990.100 to 9.999 Hz

■ Parameter 2 group

ParameterMarkDefaultsSetting rangeDisplay condition
 2-1Output operation modeAutonics - icon71Autonics - icon72[Except indicator model] OFF, L.ST, H.ST, LH.ST, HH.ST, LL.ST, LD.ST
•    Refer to Output Operation Mode
 

 2-2  HysteresisAutonics - icon73  Autonics - icon74 [Except indicator model] Within 10 % of max. display range, digit2-1 Output operation mode: except OFF
 2-3Startup compensation timeAutonics - icon75Autonics - icon76[Except indicator model] 0.0 to 99.9 sec 
 2-4Peak monitoring delay timeAutonics - icon77Autonics - icon78 00 to 30 sec 
2-5Display cycleAutonics - icon79Autonics - icon820.1 to 5.0 sec
 2-6Keys for zero adjustmentAutonics - icon83
Autonics - icon84NO, YES
•    YES: Press the [◀] + [▲] keys for 3 sec to adjust zero.
 
 2-7 External input terminalAutonics - icon85Autonics - icon86[Except indicator model] HOLD, ZERO
•    If the external input terminal is short-circuited for 50 ms or more, it operates with the set function.
 
 2-8  High-limit value of transmission output  

Autonics - icon87

Autonics - icon88[DC voltage & Transmission (DC 4 – 20 mA) output model],
[AC voltage & Transmission (DC 4 – 20 mA) output model] Max. value of display range
 

 

Autonics - icon89[DC current & Transmission (DC 4 – 20 mA) output model], [AC current & Transmission (DC 4 – 20 mA) output model] Max. value of display range
 2-9 Low-limit value of transmission outputAutonics - icon90Autonics - icon91[DC voltage & Transmission (DC 4 – 20 mA) output model],
[AC voltage & Transmission (DC 4 – 20 mA) output model] Min. value of display range
 

 

 

Autonics - icon92[DC current & Transmission (DC 4 – 20 mA) output model], [AC current & Transmission (DC 4 – 20 mA) output model] Min. value of display range
2-10Comm.AddressAutonics - icon93Autonics - icon94[RS485 Comm. output model] 01 to 99
2-11Comm. speedAutonics - icon95Autonics - icon96[RS485 Comm. output model] 38.4k, 19.2k, 9600, 4800, 2400, 1200 bps
2-12Parity bitAutonics - icon97Autonics - icon98[RS485 Comm. output model] NONE, EVEN, ODD
2-13Stop bitAutonics - icon99Autonics - icon10[RS485 Comm. output model] 2, 1 bit
2-14Response waiting timeAutonics - icon100Autonics - icon101[RS485 Comm. output model] 5 to 99 sec
 2-15 LockAutonics - icon102Autonics - icon72OFF: unlock, LOC1: lock parameter 1, LOC2: lock parameter 1, 2, LOC3: lock parameter 0, 1 and 2 

■ Parameter 0 group

ParameterMarkDefaultsSetting rangeDisplaycondition
Output high- 0-1 limit output
setting value
Autonics - icon104Autonics - icon105[DC voltage & Preset setting model] -5 to 110 % of display range
[AC voltage & Preset setting model] 0 to 110 % of display range
2-1 Output operation mode: except OFF
Autonics - icon106[DC current & Preset setting model] -5 to 110 % of display range
[AC current & Preset setting model] 0 to 110 % of display range
Output low- 0-2 limit output
setting value
Autonics - icon107Autonics - icon108[DC voltage & Preset setting model] -5 to no % of display range
[AC voltage & Preset setting model] 0 to 110 % of display range
2-1 Output operation mode: except OFF
Autonics - icon109[DC current & Preset setting model] -5 to 110 % of display range
[AC current & Preset setting model] 0 to 110 % of display range
Display max. 0-3 peak valueAutonics - icon110Autonics - icon16[DC voltage], [AC voltage] Max. peak value in run mode2-1 Output operation mode: except OFF &
2-4 Peak monitoring delay time: except 00
Autonics - icon24[DC current], [AC current] Max. peak value in run mode
Display min. 0-4 ca.
peak value
Autonics - icon112Autonics - icon16[DC voltage], [AC voltage] Min. peak value in run mode
Autonics - icon24[DC current], [AC current] Min. peak value in run mode

01) Reset: Press any one of [◀], [▼], [▲] keys.

Input Range and Display Range

When the max. input value is over the 100 %, it may result in input terminal damage.
■ DC voltage model

Input rangeDisplay rangeInput impedance
Diaplay method: STND (fixed)Diaplay method: SCAL 01)
0 – 500 VDCSKIL QC5359B 02 20V Dual Port Charger - icon 50.0 to 500.0Autonics - icon31Autonics - icon1134.33348 MΩ
0 – 100 VDCSKIL QC5359B 02 20V Dual Port Charger - icon 50.0 to 100.0Autonics - icon324.33348 MΩ
0 – 50 VDCSKIL QC5359B 02 20V Dual Port Charger - icon 50.00 to 50.00Autonics - icon33433.48 kΩ
0 – 10 VDCSKIL QC5359B 02 20V Dual Port Charger - icon 50.00 to 10.00Autonics - icon34433.48 kΩ
0 – 5 VDCSKIL QC5359B 02 20V Dual Port Charger - icon 50.000 to 5.000Autonics - icon3543.48 kΩ
0 – 1 VDCSKIL QC5359B 02 20V Dual Port Charger - icon 50.000 to 1.000Autonics - icon3643.48 kΩ
0 – 250 mVDCSKIL QC5359B 02 20V Dual Port Charger - icon 50.0 to 250.0Autonics - icon372.28 kΩ
0 – 50 mVDCSKIL QC5359B 02 20V Dual Port Charger - icon 50.00 to 50.00Autonics - icon382.28 kΩ

01) Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input range to measure.
When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.
■ DC current model

Input rangeDisplay rangeInput impedance
Diaplay method: STND (fixed)Diaplay method: SCAL 01)
0 – 5 A0.000 to 5.000Autonics - icon39Autonics - icon1130.022 Ω
0 – 2 A0.000 to 2.000Autonics - icon400.022 Ω
0 – 500 mA0.0 to 500.0Autonics - icon410.222 Ω
0 – 200 mA0.0 to 200.0Autonics - icon420.222 Ω
0 – 50 mA0.00 to 50.00Autonics - icon432.222 Ω
4 – 20 mA4.00 to 20.00Autonics - icon442.222 Ω
0 – 5 mA0.000 to 5.000Autonics - icon4522.222 Ω
0 – 2 mA0.000 to 2.000Autonics - icon4622.222 Ω

01) Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input range to measure.
When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.
■ AC voltage model

Input rangeDisplay rangeInput impedance
Diaplay method: STND (fixed)Diaplay method: SCAL 01)
0 – 500 VAC∼0.0 to 500.0Autonics - icon47Autonics - icon1135.01092 MΩ
0 – 250 VAC∼0.0 to 250.0Autonics - icon485.01092 MΩ
0 – 110 VAC∼ 02)0.0 to 440.0Autonics - icon491.11092 MΩ
0 – 50 VAC∼0.00 to 50.00Autonics - icon501.11092 MΩ
0 – 20 VAC∼0.00 to 20.00Autonics - icon51200.92 kΩ
0 – 10 VAC∼0.00 to 10.00Autonics - icon52200.92 kΩ
0 – 2 VAC∼0.000 to 2.000Autonics - icon5320.92 kΩ
0 – 1 VAC∼0.000 to 1.000Autonics - icon5420.92 kΩ

01) Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input range to measure.
When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.
02) In case of 0 to 110 VAC∼ of AC voltage range and using P.T (potential transformer) for 440 VAC∼ / 110 VAC∼, if 110 VAC∼ is input, and the unit displays 440 VAC∼ automatically by preset scale value for P.T user’s convenient.

Input rangeDisplay rangeInput impedance
Diaplay method: STND (fixed)Diaplay method: SCAL 01)
0 – 5 A0.000 to 5.000Autonics - icon55Autonics - icon1130.02 Ω
0 – 2.5 A0.000 to 2.500Autonics - icon560.02 Ω
0 – 1 A0.000 to 1.000Autonics - icon570.102 Ω
0 – 500 mA0.0 to 500.0Autonics - icon580.202 Ω
0 – 250 mA0.0 to 250.0Autonics - icon600.202 Ω
0 – 100 mA0.0 to 100.0Autonics - icon611.022 Ω
0 – 50 mA0.00 to 50.00Autonics - icon621.022 Ω

01) Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input range to measure.
When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.

Output Operation Mode

  • H.SET or L.SET is displayed according to the output operation mode setting. In case of output operation mode as OFF, H.SET and L.SET are not displayed.
  • When changing output operation mode, high-limit / low-limit output setting value, hysteresis are reset.

Autonics MT4W Series Digital Multi Panel Meter - model6

Reset

  1. Press the [◀] + [▲] + [▼] keys for over 5 sec. in run mode, INIT flashes for 0.5 sec.
  2. Press the direction keys to flash NO for 0.5 sec in turn.
  3. Change the setting value as YES by pressing the direction keys.
  4. Press the [MODE] key to reset all parameter values as default and to return to run mode.

Error

Error display is released automatically when it is in the measured and display range.

DisplayDescriptionTroubleshooting
Autonics - icon64Flashes when measurement input is exceeded the max. allowable input (110 %) 

Disconnect power supply and check the cables.

Autonics - icon65Flashes when measurement input is exceeded the min. allowable input (-10 %)
Autonics - icon66Turns ON when display input is exceeded high-limit scale setting value or max. display range (9999) 

Reset within the display

range.

Autonics - icon67Turns ON when display input is exceeded low-limit scale setting value or min. display range (-1999)
Autonics - icon68Turns ON when input frequency is exceeded the

max. display value of measured range

Autonics - icon69Flashes twice when it exceeds zero range (±99) and returns to run modeReset within the zero range.
01) Displays at DC input model only.

18, Bansong-ro 513Beon-gil, Haeundae-gu, Busan, Republic of Korea, 48002
www.autonics.com | +82-2-2048-1577 | sales@autonics.com

Autonics - logo

Documents / Resources

Autonics MT4W Series Digital Multi Panel Meter [pdf] Instruction Manual
MT4W-AA-1N, MT4W Series Digital Multi Panel Meter, Digital Multi Panel Meter, Multi Panel Meter, Meter

References

Leave a comment

Your email address will not be published. Required fields are marked *