CEMELI TCN4S-24R Temperature Controller User Manual

Model: TCN4S-24R

1. Introduction

This manual provides comprehensive instructions for the installation, operation, and maintenance of the CEMELI TCN4S-24R Temperature Controller. Please read this manual thoroughly before using the device to ensure proper and safe operation. Keep this manual for future reference.

2. Product Overview

2.1 Key Features

  • Dual Digital Display (PV/SV) for simultaneous viewing of Process Value and Set Value.
  • High-speed 100ms sampling rate for accurate temperature monitoring.
  • Display accuracy of ±0.5%.
  • Supports multiple control methods: ON/OFF Control, P, PI, PD, and PID Control.
  • Flexible output options: Switchable between Relay Output (250VAC~ 3A) and SSR Drive Output (12VDC).
  • Equipped with two independent alarm outputs (Alarm 1/2).
  • Compact 1/16 DIN (W48 x H48mm) design with large display panels for enhanced readability.
  • Wide input specification: Thermocouple (K, J, T, R, S, L) and RTD (DPt100, Cu50).
  • Power supply: 100-240VAC, 50/60Hz.

2.2 Front Panel and Dimensions

The front panel features dual 4-digit 7-segment LED displays for Process Value (PV) and Set Value (SV), along with control buttons.

Front view of CEMELI TCN4S-24R Temperature Controller

Figure 1: Front view of the TCN4S-24R Temperature Controller, showing the dual digital displays for PV and SV, and control buttons (MODE, left arrow, down arrow, up arrow).

Side view of CEMELI TCN4S-24R Temperature Controller

Figure 2: Side view of the TCN4S-24R Temperature Controller, illustrating its compact 1/16 DIN size and mounting clips.

3. Specifications

ParameterSpecification
Display Method4-Digit 7-Segment LED Display (PV/SV)
Control MethodON/OFF Control, P, PI, PD, PID Control
Input SpecificationThermocouple: K(CA), J(IC), T(CC), R(PR), S(PR), L(IC); RTD: DPt100, Cu50
Sampling Cycle100ms
Control OutputRelay (250VAC~ 3A) or SSR Drive (12VDC) [ON/OFF]
Option OutputAlarm 1/2
Power Supply100-240VAC, 50/60Hz
DimensionsDIN W48 x H48mm (1/16 DIN)
Item Weight50 Grams (approx. 1.76 ounces)

4. Setup

4.1 Installation

The TCN4S-24R is designed for panel mounting in a standard 1/16 DIN cutout (45x45mm). Ensure adequate space for ventilation and wiring connections at the rear of the unit. Secure the controller using the provided mounting brackets.

  • Cut a panel opening of 45mm x 45mm.
  • Insert the controller into the opening from the front.
  • Attach the mounting brackets to the sides of the controller and tighten the screws to secure it firmly in place.

4.2 Wiring Connections

Refer to the wiring diagram on the side of the unit and the detailed terminal view for correct connections. Ensure all power is disconnected before performing any wiring.

Wiring diagram for CEMELI TCN4S-24R Temperature Controller

Figure 3: Wiring diagram located on the side of the TCN4S-24R unit, detailing connections for SSR output, relay output, alarm outputs, sensor input (TC/RTD), and power supply.

Close-up of wiring terminals on CEMELI TCN4S-24R Temperature Controller

Figure 4: Close-up view of the screw terminals on the rear of the TCN4S-24R, showing numbered connections for various inputs and outputs.

Key Terminal Connections:

  • Terminals 1 & 2: SSR OUT (12VDC ±2V, 20mA Max) / AL1 OUT (250VAC 1A1a) - Note: These terminals are shared for SSR output and Alarm 1. Configuration determines function.
  • Terminals 3 & 4: Relay OUT (250VAC 3A1a)
  • Terminals 7 & 8: AL2 OUT (250VAC 1A1a)
  • Terminals 9, 10, 11: TC (Thermocouple) / RTD (Resistance Temperature Detector) Input. Connect sensor according to type (e.g., K-type thermocouple to 9 and 10, RTD to 9, 10, 11).
  • Terminals 5 & 6: Power Supply (100-240VAC, 50/60Hz)

Caution: Incorrect wiring can damage the unit or connected equipment. Always consult the wiring diagram and ensure proper polarity and voltage.

5. Operating Instructions

5.1 Basic Operation

Upon power-up, the controller will display the Process Value (PV) on the upper display and the Set Value (SV) on the lower display.

  • PV (Process Value): Shows the current measured temperature.
  • SV (Set Value): Shows the desired target temperature.
  • MODE Button: Used to cycle through parameters and enter setting modes.
  • Up/Down Arrows: Used to adjust numerical values in setting modes.
  • Left Arrow: Used to shift cursor position during numerical input.

5.2 Setting the Set Value (SV)

  1. Press the MODE button briefly until the SV display starts flashing.
  2. Use the Up and Down arrow buttons to adjust the SV to the desired temperature. Use the Left arrow to move between digits.
  3. Press the MODE button again to confirm the setting and exit the SV adjustment mode. The SV display will stop flashing.

5.3 Advanced Settings (PID Parameters, Alarm Settings)

To access advanced settings such as PID parameters, input type, and alarm configurations, press and hold the MODE button for several seconds until the parameter menu appears. Navigate through the parameters using the MODE button and adjust values with the arrow buttons. Refer to the full manufacturer's manual for detailed parameter descriptions and adjustment procedures.

6. Maintenance

The CEMELI TCN4S-24R Temperature Controller is designed for reliable operation with minimal maintenance. Follow these guidelines to ensure longevity:

  • Cleaning: Periodically clean the front panel with a soft, dry cloth. Do not use abrasive cleaners or solvents.
  • Inspection: Regularly inspect wiring connections for looseness or signs of damage. Ensure the unit is free from dust and debris, especially around ventilation slots.
  • Environment: Operate the controller within its specified environmental conditions (temperature, humidity) to prevent malfunction.

Warning: Disconnect all power before performing any cleaning or inspection that involves opening the unit or accessing internal components.

7. Troubleshooting

This section addresses common issues you might encounter with the TCN4S-24R Temperature Controller. For problems not listed here, please contact technical support.

ProblemPossible CauseSolution
No Power / Display OffNo power supply, incorrect wiring, blown fuse.Check power connections (Terminals 5 & 6). Verify power source voltage. Inspect internal fuse if accessible (consult qualified technician).
PV Display Error (e.g., "HHHH", "LLLL")Sensor open circuit, sensor short circuit, incorrect sensor type setting, sensor out of range.Check sensor wiring (Terminals 9, 10, 11). Ensure sensor type matches controller settings. Replace faulty sensor.
Output Not ActivatingIncorrect control mode, faulty output wiring, output component failure, SV not reached.Verify control mode (ON/OFF, PID). Check output wiring (Relay/SSR). Ensure SV is set correctly and PV is within control range. Test output component (e.g., relay, SSR).
Temperature FluctuationPID parameters not tuned, external disturbances, sensor placement.Perform PID auto-tuning. Ensure sensor is placed correctly and stably. Minimize external temperature fluctuations.

8. Warranty and Support

Specific warranty details for the CEMELI TCN4S-24R Temperature Controller are not provided within the product information. For warranty claims, technical support, or service inquiries, please contact your point of purchase or the manufacturer directly. Keep your purchase receipt as proof of purchase.