Acogedor HWP-T804-01-23-HL-P

Acogedor Liquid Level Controller Instruction Manual

Model: HWP-T804-01-23-HL-P

1. Product Overview

The Acogedor HWP-T804-01-23-HL-P is a sophisticated 4-20mA Pressure Sensor and Liquid Level Transmitter Sensor Controller designed for precise measurement and control of liquid levels. It integrates digital filtering technology for strong anti-interference capabilities, ensuring reliable performance in various industrial and environmental applications. Its user-friendly design allows for easy installation and maintenance.

Acogedor HWP-T804-01-23-HL-P Liquid Level Controller, front and side view

This image displays the Acogedor HWP-T804-01-23-HL-P Liquid Level Controller, showcasing its front panel with the digital display and bar graph, along with a clear view of its side profile.

2. Key Features

  • Advanced Digital Filtering: Utilizes digital filtering technology for robust anti-interference, effectively suppressing low-frequency disturbances and irregular interference sources during measurement.
  • Ease of Installation: Designed with common installation sizes, making it compatible with existing domestic and international instruments for straightforward setup, maintenance, and exchange.
  • Efficient Heat Dissipation: Features a porous design that ensures good permeability and superior heat dissipation, contributing to stable and reliable long-term operation.
  • High Measurement Accuracy: Provides precise pressure value measurements, ensuring stable and credible data for critical applications.
  • Broad Application Range: Widely applicable in diverse environments including water plants, sewage treatment facilities, urban water supply systems, high-level pools, wells, mines, industrial water systems, oil ponds, hydrogeology, reservoirs, and rivers.

3. Product Components and Panel Introduction

Familiarize yourself with the various parts of the controller to ensure proper operation and configuration.

Front Panel

Labeled diagram of the Acogedor HWP-T804-01-23-HL-P controller front panel

An annotated diagram detailing each component of the front panel, including the measuring bar display, measured value (PV) display, and the functions of the SET, Add, Reduce, and Displacement keys, along with various control indicators.

  • Measuring Bar Display: Shows various measurement parameters.
  • Measured Value (PV) Display: Digital readout of the current measurement.
  • Indicator Lights (AHH, AH, AL, ALL): Indicate alarm states (beyond upper limit, upper limit, lower limit, under lower limit).
  • SET Button: Enters setting mode.
  • Add Key: Increases values during setting.
  • Reduce Key: Decreases values during setting.
  • Displacement Key: Used for navigating through settings or shifting digits.

Rear Panel Terminals

Rear view of Acogedor HWP-T804-01-23-HL-P controller showing terminal block

A detailed view of the rear terminal block of the controller, indicating the various input and output connections for power, sensors, and control signals.

The rear panel features a terminal block for all electrical connections. Refer to the wiring diagram in the Setup section for detailed connection instructions.

4. Specifications

Technical specifications for the HWP-T804-01-23-HL-P Liquid Level Controller:

ParameterValue
ModelHWP-T804-01-23-HL-P
MaterialABS (Housing), Metal (Internal Components)
Power Supply VoltageAC 220V 50HZ
Measurement Accuracy0.5% FS
Power Consumption≤5W
Measuring Range-1999~1999 Words
Resolution0.001, 0.01, 0.1, 1
Sampling Cycle3 Times/Sec
OutputFour-Way Relay Alarm Control Output
Thermal InputPt100, Cu50
Thermocouple SupportB, S, E, K, J, T, R, N
Standard Current Input0-10/0-20/4-20mA
Standard Voltage Input0-5/1-5V
Resistance Input0-400Ω
Non-Standard Voltage Input0-100mV
Frequency0-3KHz, Amplitude>4V, Rectangular or Sine Wave
Standard Voltage Output0-5V, 1-5V (Load RL>250kΩ)
Analog Standard Current Output0-10mA (Load RL<750Ω)
Package Dimensions6.57 x 4.65 x 3.74 inches
Item Weight1.14 Pounds

5. Setup and Installation

Proper installation is crucial for the accurate and safe operation of the liquid level controller. Please follow these guidelines carefully.

5.1 Safety Precautions

  • Ensure the power supply is disconnected before performing any wiring or installation.
  • All wiring should be performed by qualified personnel in accordance with local electrical codes.
  • Verify the power supply voltage matches the device's requirements (AC 220V 50HZ).

5.2 Mounting

The controller is designed for panel mounting. Refer to the dimensional drawing for precise cutout and mounting hole requirements.

Dimensional drawing and rear wiring diagram of the Acogedor HWP-T804-01-23-HL-P controller

This technical drawing provides the physical dimensions of the controller and illustrates the layout of the rear wiring terminals, crucial for installation planning.

5.3 Wiring Instructions

Connect the pressure sensor and power supply to the rear terminal block as per the diagrams below. Ensure all connections are secure to prevent intermittent operation or damage.

Wiring diagrams for 4-20mA two-wire and 0-5V/10V three-wire pressure sensors

This diagram illustrates the two primary wiring configurations: a two-wire current output (4-20mA) connection and a three-wire voltage output (0-5V/10V) connection, showing how to connect the pressure sensor to the meter.

  • Two-Wire Current Output (4-20mA) Sensor:
    • Connect the sensor's Positive (1 pin) to the 24V DC power supply.
    • Connect the sensor's Signal (2 pin) 4-20mA output to the meter's current input.
    • Red wire: 24V DC. Black wire: current output.
  • Three-Wire Voltage Output (0-5V/10V) Sensor:
    • Connect the sensor's Positive (1 pin) to the 24V DC power supply.
    • Connect the sensor's Signal (2 pin) 0-5V/10V output to the meter's voltage input.
    • Connect the sensor's Public (3 pin) to the meter's common ground.
    • Red wire: 24V DC. Yellow wire: power supply-. Black wire: voltage output+.

Ensure the correct input type (current or voltage) is selected in the controller's settings to match your sensor.

6. Operation

Once installed and wired, the controller is ready for operation. The front panel provides visual feedback and control options.

6.1 Power On

After connecting the AC 220V 50HZ power supply, the controller will power on and initiate its self-test sequence. The digital display (PV) will show the measured value, and the bar graph will indicate the level.

6.2 Reading the Display

  • PV Display: Shows the current measured value numerically.
  • Measuring Bar Display: Provides a visual representation of the measured level, typically ranging from 0 to 100.
  • Indicator Lights: Illuminate to signal specific alarm conditions (AHH, AH, AL, ALL) based on configured setpoints.

6.3 Setting Parameters

To configure alarm setpoints, input types, or other operational parameters, use the front panel buttons:

Close-up of control buttons on the Acogedor HWP-T804-01-23-HL-P controller

This image provides a close-up of the SET, Add, Reduce, and Displacement buttons on the front panel, showing their design and labels.

  1. Press the SET button to enter the parameter setting mode. The display will change to show the first configurable parameter.
  2. Use the Add (▲) and Reduce (▼) keys to adjust the value of the currently displayed parameter.
  3. Use the Displacement (◄) key to move between digits within a parameter value or to navigate to the next parameter.
  4. Press SET again to save the changes and move to the next parameter, or to exit the setting mode if all parameters have been configured.

Refer to the detailed programming guide (if available separately) for specific parameter codes and their functions.

7. Maintenance

The Acogedor HWP-T804-01-23-HL-P controller is designed for low maintenance. Regular checks can help ensure its longevity and accurate performance.

7.1 Cleaning

  • Periodically wipe the front panel with a soft, dry cloth to remove dust and grime.
  • Do not use abrasive cleaners or solvents, as these can damage the display or housing.

7.2 Heat Dissipation

The unit features a porous design for heat dissipation. Ensure that the vents on the side of the unit are not obstructed to allow for proper airflow.

Side view of Acogedor HWP-T804-01-23-HL-P controller highlighting heat dissipation vents

A side profile of the controller, emphasizing the porous design for effective heat dissipation, which contributes to stable operation.

7.3 Connection Checks

  • Periodically inspect all wiring connections at the rear terminal block to ensure they remain tight and free from corrosion.
  • Check the sensor cable for any signs of damage or wear.

8. Troubleshooting

This section provides solutions to common issues you might encounter with the liquid level controller.

ProblemPossible CauseSolution
Controller does not power on.No power supply; incorrect wiring; faulty power source.Verify AC 220V 50HZ power is connected to the correct terminals. Check circuit breaker/fuse. Ensure wiring is secure and correct as per Section 5.3.
Incorrect or unstable readings.Sensor not connected properly; incorrect input type setting; sensor malfunction; electrical interference.Check sensor wiring (Section 5.3). Verify the controller's input type setting matches the sensor (e.g., 4-20mA or 0-5V). Inspect sensor for damage. Ensure proper grounding and shielding to minimize interference.
Alarm indicators not functioning as expected.Alarm setpoints incorrectly configured; relay output wiring issue.Review and adjust alarm setpoints using the SET button (Section 6.3). Check wiring for relay outputs if external devices are controlled.
Buttons unresponsive or difficult to use.Dust or debris accumulation; internal fault.Gently clean around the buttons. If the issue persists, contact support.

If the problem persists after attempting these troubleshooting steps, please contact customer support for further assistance.

9. Warranty and Support

Specific warranty details for the Acogedor HWP-T804-01-23-HL-P Liquid Level Controller are not provided in this manual. For information regarding warranty coverage, terms, and conditions, please refer to the product packaging or contact the manufacturer directly.

Customer Support

For technical assistance, troubleshooting beyond this manual, or inquiries about replacement parts, please contact Acogedor customer support through their official channels. Have your product model number (HWP-T804-01-23-HL-P) and purchase details ready when contacting support.

© 2024 Acogedor. All rights reserved.

This manual is subject to change without notice.

Related Documents - HWP-T804-01-23-HL-P

Preview JETEC JTK-620 Submersible Level Transmitter - Technical Specifications and Features
Detailed technical specifications, features, wiring diagram, dimensions, and order information for the JETEC JTK-620 submersible level transmitter. This IP68 rated transmitter uses a ceramic sensor and provides a 4-20mA output signal.
Preview RKL-01 Submersible Liquid Level Transmitter - RIKA Specifications
Detailed specifications, features, applications, and technical data for the RIKA RKL-01 Submersible Liquid Level Transmitter, designed for accurate liquid level measurement in various industrial and environmental applications.
Preview EchoBeam LR80 Series 80 GHz Radar Level Transmitter Quick Start Guide
Quick start guide for the Flowline EchoBeam LR80 Series radar level transmitter. Includes installation, wiring, configuration, and troubleshooting instructions for liquid and solid level measurement.
Preview YD9731 Ultrasonic Liquid Level Transmitter User Manual
User manual for the INTOIOT YD9731 ultrasonic liquid level transmitter, detailing technical specifications, product models, dimensions, communication protocols (RS485, 4-20mA, DC0-10V), and application examples.
Preview Endress+Hauser Deltapilot M Series: Brief Operating Instructions for Hydrostatic Level Measurement
This document provides brief operating instructions for the Endress+Hauser Deltapilot M series (FMB50, FMB51, FMB52, FMB53) hydrostatic level and pressure transmitters. Learn about installation, wiring, operation, and commissioning for these industrial process instruments. For detailed information, refer to the full Operating Instructions available via www.endress.com/deviceviewer.
Preview Dinel ULM-53 Ultrasonic Level Meters: Technical Data and Specifications
Comprehensive technical datasheet for Dinel ULM-53 ultrasonic level meters, detailing features, specifications, applications, electrical connections, order codes, and safety information for continuous liquid level measurement in industrial environments.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.