DANOPLUS KB0297
DANOPLUS CO2 Controller Instruction Manual
Model: KB0297
1. Introduction
This manual provides detailed instructions for the installation, operation, and maintenance of the DANOPLUS CO2 Controller. This device is designed to accurately monitor carbon dioxide levels and control CO2 generation or ventilation systems in various environments such as greenhouses, grow rooms, offices, and homes. Please read this manual thoroughly before using the product to ensure safe and optimal performance.

Figure 1.1: The DANOPLUS CO2 Controller with its main display unit and remote NDIR CO2 sensor.

Figure 1.2: The CO2 Controller is suitable for a wide range of applications, including agricultural and indoor air quality management.
2. Product Features
The DANOPLUS CO2 Controller offers a comprehensive set of features for precise CO2 management:
- Wide LCD Screen: Displays CO2 levels, trend charts, and settings clearly.
- 0-5000 ppm Measuring Range: Suitable for various CO2 monitoring needs.
- Trend Chart Recording: Records CO2 levels per minute, hour, day, or week for analysis.
- Plant Mode & Human Mode: Dedicated modes for controlling CO2 generators in grow rooms or ventilation systems for indoor air quality.
- Audible Alarm: Alerts users when CO2 levels exceed a user-defined threshold.
- Auto Day & Night Detection: Automatically adjusts operation based on light conditions, turning off CO2 output during the night.
- Altitude Adjustable: Calibration for altitudes from 50 to 500 meters (164 to 1640 feet).
- Piggyback Socket: Integrated power outlet for connecting CO2 generators or ventilation fans.
- Long Sensor Cable: 14.8 feet (4.5 m) cable for flexible sensor placement.

Figure 2.1: Overview of the main features of the DANOPLUS CO2 Controller.
3. Package Contents
Please verify that all items listed below are included in your package:
- 1 x CO2 Meter (Controller + Remote NDIR CO2 Sensor)
- Screws and Tapes for mounting
- English Instruction Manual

Figure 3.1: Contents of the DANOPLUS CO2 Controller package.
4. Setup
4.1 Mounting the Controller and Sensor
- Choose a suitable location for the main controller unit, ensuring it is easily accessible for viewing and adjustments.
- Mount the controller using the provided screws or tapes.
- Position the remote NDIR CO2 sensor in the area where CO2 levels need to be monitored. Ensure it is not obstructed and has good air circulation. The 14.8 feet (4.5 m) cable allows for flexible placement.
- Connect the remote sensor cable to the main controller unit.
- Plug the controller's power adapter into a standard AC outlet (AC100~240VAC).

Figure 4.1: The remote NDIR CO2 sensor with its long cable for optimal placement.
4.2 Initial Calibration (Altitude Adjustment)
The controller supports altitude adjustment for accurate readings. If operating at a significant altitude, adjust this setting:
- Access the menu on the controller.
- Navigate to the altitude setting.
- Adjust the altitude from 50 to 500 meters (164 to 1640 feet) as required for your location.
- Confirm the setting to save.

Figure 4.2: The controller display indicating altitude adjustment mode.
5. Operating Instructions
5.1 Power On and Warm-up
After connecting the power, the device will perform a 30-second warm-up. During this time, the display will show a countdown or similar indication. Once warm-up is complete, it will begin displaying current CO2 readings.
5.2 Understanding the Display
The wide LCD screen displays real-time CO2 concentration, maximum and minimum recorded values, and a trend chart. It also shows the set target CO2 levels (Center and Zone).
5.3 Setting Operating Modes (Plant Mode / Human Mode)
The controller features two primary operating modes:
- Plant Mode: Designed for environments like grow rooms or greenhouses where CO2 enrichment is desired. In this mode, the controller activates a connected CO2 generator when levels fall below the set target.
- Human Mode: Intended for indoor spaces like offices or homes to maintain healthy air quality. In this mode, the controller activates a ventilation system when CO2 levels exceed the set target.
To switch between modes:
- Press the 'Menu' button to enter the settings.
- Navigate to the 'Mode' option.
- Select either 'Plant Mode' or 'Human Mode' using the arrow buttons.
- Press 'Enter' to confirm your selection.

Figure 5.1: Visual representation of Plant Mode and Human Mode operation.
5.4 Setting CO2 Target Levels (Center and Zone)
The controller uses 'Center' and 'Zone' values to define the desired CO2 range and control output.
- Center: The ideal CO2 concentration you wish to maintain.
- Zone: The acceptable deviation from the Center value. The controller will activate/deactivate output when CO2 levels move outside the (Center +/- Zone/2) range.
To set these values:
- Press the 'Menu' button.
- Navigate to 'Set Center' and 'Set Zone' options.
- Use the arrow buttons to adjust the values.
- Press 'Enter' to save each setting.
5.4.1 Output Control in Plant Mode
In Plant Mode, the controller activates the connected CO2 generator when the CO2 reading falls below the lower threshold and deactivates it when it rises above the upper threshold.
- Output Power ON: When CO2 reading < (Set Center - (1/2) x Set Zone)
- Output Power OFF: When CO2 reading > (Set Center + (1/2) x Set Zone)
Example: If Set Center = 1200 ppm and Set Zone = 400 ppm:
- Output Power ON (Activate CO2 generator/regulator) when CO2 reading ≤ 1000 ppm (1200 - (1/2) * 400).
- Output Power OFF (Shut off CO2 generator/regulator) when CO2 reading ≥ 1400 ppm (1200 + (1/2) * 400).

Figure 5.2: Output control logic for Plant Mode.
5.4.2 Output Control in Human Mode
In Human Mode, the controller activates the connected ventilation fan when the CO2 reading exceeds the upper threshold and deactivates it when it falls below the lower threshold.
- Output Power OFF: When CO2 reading < (Set Center - (1/2) x Set Zone)
- Output Power ON: When CO2 reading > (Set Center + (1/2) x Set Zone)
Example: If Set Center = 1200 ppm and Set Zone = 400 ppm:
- Output Power OFF (Shut off Ventilation fan) when CO2 reading ≤ 1000 ppm (1200 - (1/2) * 400).
- Output Power ON (Activate Ventilation fan) when CO2 reading ≥ 1400 ppm (1200 + (1/2) * 400).

Figure 5.3: Output control logic for Human Mode.
5.5 Audible Alarm
The controller features an audible alarm that activates when the CO2 level exceeds a user-defined threshold. This threshold can be adjusted in the menu settings.
- Press the 'Menu' button.
- Navigate to the 'Alarm Threshold' setting.
- Adjust the CO2 ppm threshold using the arrow buttons.
- Press 'Enter' to save.
5.6 Auto Day & Night Detection
The remote sensor includes a photocell for automatic day and night detection. This feature allows the controller to automatically turn off the CO2 generator/regulator (in Plant Mode) or adjust ventilation (in Human Mode) by turning off the output power during the night, conserving energy and preventing unnecessary operation.

Figure 5.4: Automatic day and night detection via the remote sensor's photocell.
6. Maintenance
To ensure the longevity and accuracy of your DANOPLUS CO2 Controller, follow these maintenance guidelines:
- Cleaning: Regularly wipe the main unit and sensor with a soft, dry cloth. Do not use abrasive cleaners or solvents.
- Sensor Care: Keep the NDIR CO2 sensor free from dust and debris. Avoid exposing it to direct water spray or high humidity conditions beyond its operating range.
- Environmental Conditions: Operate the device within the specified operating conditions (0~50°C, 5-95% RH, non-condensing) to prevent damage.
- Storage: When not in use for extended periods, store the controller in a cool, dry place within the specified storage conditions (-20~60°C, 5-95% RH, non-condensing).
7. Troubleshooting
If you encounter issues with your CO2 Controller, refer to the following common problems and solutions:
| Problem | Possible Cause | Solution |
|---|---|---|
| Controller not powering on | No power supply; loose connection | Check power cable connection; ensure outlet is functional. |
| Inaccurate CO2 readings | Sensor obstruction; incorrect altitude setting; sensor malfunction | Ensure sensor is clear; verify altitude setting (Section 4.2); contact support if issue persists. |
| Output device (generator/fan) not activating | Incorrect mode selected; CO2 levels within target range; device not plugged into piggyback socket; faulty output device | Verify operating mode (Section 5.3); check CO2 target settings (Section 5.4); ensure output device is correctly plugged into the controller's socket; test output device independently. |
| Audible alarm constantly on/off | Alarm threshold set too low/high; high/low ambient CO2 levels | Adjust alarm threshold (Section 5.5) to a suitable level for your environment. |
| Day/Night detection not working | Photocell obstructed; insufficient light for detection | Ensure photocell on the remote sensor is clear and exposed to ambient light. |
If the problem persists after attempting these solutions, please contact DANOPLUS customer support for further assistance.
8. Specifications
| Parameter | Value |
|---|---|
| Measuring Range | 0-5000 ppm |
| Resolution | 1ppm (0-1000); 5ppm (1000-2000); 10ppm (>2000) |
| Accuracy | CO2 below 3000ppm ±50ppm or ±5% of reading (whichever is greater); CO2 above 3000ppm ±7% of reading |
| Warm-up Time | 30 seconds |
| Response Time CO2 | <2 min for 63% of step change or <4.6 min for 90% step change |
| Operating Condition | 0~50°C, 5-95% RH (avoid condensation) |
| Storage Condition | -20~60°C, 5-95% RH (avoid condensation) |
| Power Supply | AC100~240VAC |
| Sensor Type | Non Dispersive Infrared (NDIR) |
| Product Dimensions | 19.69"D x 6.22"W x 4.17"H |
| Item Weight | 0.8 Pounds (12.8 ounces) |
| Model Number | KB0297 |
| UPC | 619317590304 |
9. Warranty and Support
DANOPLUS products are manufactured to high-quality standards. For warranty information, technical support, or service inquiries, please refer to the contact information provided with your purchase documentation or visit the official DANOPLUS website. Please retain your proof of purchase for warranty claims.