1. Introduction
The Simplex 4090-9001 Individual Addressable Module (IAM) is a supervised device designed for use with Simplex IDNET fire alarm control panels. This module provides supervised monitoring of a normally open or normally closed contact, allowing the fire alarm system to monitor various external devices such as flow switches, tamper switches, or other alarm initiating devices. Its compact design and addressable capabilities ensure efficient and reliable integration into a comprehensive fire detection and alarm system.
This manual provides essential information for the proper installation, operation, and maintenance of the 4090-9001 IAM. Please read all instructions carefully before proceeding with installation or operation.
2. Safety Information
Always adhere to local codes, ordinances, and regulations when installing and operating this device. Failure to do so may result in property damage, injury, or death. Only qualified personnel should install and service this equipment.
General Precautions:
- ELECTRICAL HAZARD: Disconnect electrical field power when making any internal adjustments or repairs. All repairs must be performed by a Simplex authorized service representative.
- ESD CAUTION: Do not open or service this device unless properly grounded. Electrostatic discharge (ESD) can damage components. Handle with care.
- Ensure all wiring is correctly terminated and secured according to wiring diagrams and local electrical codes.
- Do not expose the module to moisture or extreme temperatures outside its specified operating range. This device is intended for indoor dry applications only.
- Verify compatibility with your existing Simplex IDNET system before installation.

Figure 2.1: Simplex 4090-9001 module shown with its installation instructions sheet, highlighting the importance of reviewing all documentation before installation.
3. Setup and Installation
The 4090-9001 IAM is designed for easy installation within standard electrical boxes or compatible enclosures. Follow these steps for proper setup.
3.1 Physical Installation
- Mount the module in a suitable electrical box or enclosure, ensuring it is securely fastened. The module is designed for indoor dry applications.
- Ensure adequate space for wiring and ventilation around the module.
3.2 Wiring Connections
Refer to the module's label and the specific installation instructions (part number 574-331 Rev G, as indicated on the module) for detailed wiring diagrams. The module features terminals for IDNET input/output and supervised contact connections.

Figure 3.1: Front view of the Simplex 4090-9001 module, clearly showing the IDNET input/output terminals (1-4) and the module's model number and revision information.
- Connect the IDNET communication lines to terminals 1 (IDNET IN -) and 2 (IDNET IN +).
- Connect the IDNET communication lines to terminals 3 (IDNET OUT -) and 4 (IDNET OUT +) for daisy-chaining to other IDNET devices.
- Connect the supervised contact circuit to the designated terminals (typically M1 and the associated input). Ensure proper polarity and the use of an End-of-Line Resistor (EOLR) as specified by Simplex for supervision.
- All circuits are power-limited.
3.3 Addressing
The 4090-9001 is an addressable module. Its address is set electronically by the Simplex fire alarm control panel during system configuration. Refer to the control panel's programming manual for details on assigning and verifying module addresses.
4. Operation
The Simplex 4090-9001 IAM operates as an interface between a supervised initiating device circuit and the IDNET communication loop of a Simplex fire alarm control panel.
4.1 Supervised Monitoring
The module continuously monitors the connected contact circuit for changes in state (open or closed, depending on configuration) and for fault conditions (e.g., open circuit, short circuit) using an End-of-Line Resistor (EOLR). Upon detecting an alarm condition (e.g., contact closure for a flow switch) or a fault, the module communicates this status change to the fire alarm control panel via the IDNET loop.
- Normal State: The module reports a normal status to the control panel.
- Alarm State: When the supervised contact changes state (e.g., closes for an alarm), the module transmits an alarm signal to the control panel.
- Trouble State: If a wiring fault (open or short) is detected on the supervised circuit, the module transmits a trouble signal to the control panel.
5. Maintenance
The Simplex 4090-9001 IAM is designed for reliable, long-term operation with minimal maintenance. However, periodic inspection and cleaning are recommended as part of a comprehensive fire alarm system maintenance program.
5.1 Cleaning
If the module accumulates dust or dirt, gently wipe the exterior with a soft, dry cloth. Do not use abrasive cleaners, solvents, or excessive moisture. Ensure the module is powered down before cleaning.
5.2 Inspection
During routine system inspections, visually check the module for any signs of physical damage, loose connections, or environmental stress. Verify that the module's status indicator (if present) is operating normally according to the system's operational guidelines.

Figure 5.1: Side view of the Simplex 4090-9001 module, showing the UL Listed label, indicating compliance with safety standards.
6. Troubleshooting
This section provides guidance for common issues that may arise with the 4090-9001 IAM. For complex problems, contact a qualified Simplex service technician.
| Problem | Possible Cause | Solution |
|---|---|---|
| Module not recognized by control panel. | Incorrect wiring; Address not assigned or incorrect; Faulty module. | Verify IDNET wiring (terminals 1-4). Check control panel programming for correct address assignment. Test module with a known good unit if possible. |
| Supervised circuit shows trouble. | Open circuit; Short circuit; Incorrect EOLR; Faulty contact device. | Check wiring for breaks or shorts. Verify correct EOLR value and installation. Test the connected contact device. |
| Module reports false alarms. | Intermittent contact closure; Electrical noise; Faulty module. | Inspect the connected device for intermittent operation. Check for sources of electrical interference. Consult Simplex technical support. |
7. Specifications
| Attribute | Detail |
|---|---|
| Brand | Simplex |
| Model Number | 4090-9001 |
| Product Dimensions | 9 x 4 x 8 inches |
| Item Weight | 2.08 ounces |
| Power Source | Corded Electric (via IDNET loop) |
| Sensor Type | Photoelectric (refers to general fire alarm system components, not the module itself which monitors contacts) |
| Alarm Type | Audible (refers to general fire alarm system components, not the module itself which monitors contacts) |
| Application | Indoor Dry Application |
| Compatibility | Simplex IDNET Fire Alarm Control Panels |
| UL Listing | Fire Alarm Equipment Listed |
8. Warranty Information
Simplex products are manufactured to high quality standards. For specific warranty terms and conditions, please refer to the warranty statement provided with your purchase or contact Simplex customer service. Keep your proof of purchase for warranty claims.
9. Support
For technical assistance, product inquiries, or service requests, please contact Simplex customer support or your authorized Simplex distributor. Provide the product model number (4090-9001) and any relevant system information when seeking support.
Manufacturer: Simplex
Part Number: 4090-9001
UPC: 753359764849
For additional resources and documentation, visit the official Simplex website or refer to the instruction manual 574-331 Rev G (if available digitally).





