1. Introduction
This manual provides essential information for the proper installation, operation, and maintenance of the Honeywell SK 6700 50-Point Addressable Fire Alarm Control Panel. This advanced system is designed to detect and alert occupants to fire conditions, ensuring safety and compliance with fire safety regulations. Please read this manual thoroughly before attempting any procedures.
2. Safety Information
Adherence to the following safety guidelines is crucial for preventing injury, property damage, and ensuring the reliable operation of the fire alarm system.
- Installation and servicing must be performed by qualified personnel in accordance with all national and local codes and standards.
- Disconnect all power sources, including battery backup, before servicing the panel to prevent electrical shock.
- Ensure proper grounding of the control panel.
- Use only approved components and wiring methods as specified by Honeywell.
- Regularly test the system as per manufacturer recommendations and local codes to ensure proper functionality.
3. Product Overview
The Honeywell SK 6700 is a 50-point addressable fire alarm control panel capable of expanding to an overall point capacity of up to 100 points. It features a built-in Signaling Line Circuit (SLC) and supports connectivity for up to 17 panels within a single linked system using copper wire or fiber-optic cable. The panel includes a dual-line POTs and IP communicator, with optional cellular side-cars for enhanced communication capabilities.

This image displays the front of the Honeywell SK 6700 Fire Alarm Control Panel. The panel is red with a dark gray control interface on the upper right, featuring a green LCD screen and navigation buttons. A key lock is visible on the right side of the panel.
4. Setup
Proper setup is critical for the reliable operation of your fire alarm system. Consult the detailed installation manual for specific wiring diagrams and local code requirements.
- Mounting the Panel: Securely mount the control panel to a wall using appropriate hardware, ensuring it is level and accessible for servicing.
- Power Connection: Connect the main AC power supply to the designated terminals. Ensure the power source meets the panel's voltage and current requirements.
- Battery Backup Installation: Install the backup batteries according to the polarity markings. These batteries provide power during AC power failures.
- SLC Wiring: Connect addressable devices (smoke detectors, heat detectors, manual pull stations) to the Signaling Line Circuit (SLC) terminals following the provided wiring diagrams.
- NAC Wiring: Connect Notification Appliance Circuits (NACs) to horns, strobes, and other notification devices.
- Communication Connections: Connect telephone lines, Ethernet cables, or cellular communicators as required for remote monitoring and reporting.
- System Programming: Power on the panel and program all connected devices, zones, and system parameters using the panel's interface or a compatible programming tool.
- Initial Testing: Conduct a thorough system test to verify all devices and functions are operating correctly.
5. Operating Instructions
The SK 6700 panel provides a user-friendly interface for monitoring and managing the fire alarm system.
5.1 Panel Display and Navigation
The LCD display shows system status, events, and menu options. Use the navigation buttons (Up, Down, Left, Right, Enter) to scroll through menus and select options.
5.2 Acknowledging Alarms/Troubles
- When an alarm or trouble condition occurs, the panel's audible indicator will sound, and the display will show the event.
- Press the ACKNOWLEDGE button to silence the panel's internal audible indicator and acknowledge the event. The event will remain displayed until resolved.
5.3 Silencing Alarms
- After an alarm has been acknowledged, press the SILENCE button to silence all connected notification appliances (horns, strobes).
- The panel will continue to indicate the alarm condition on the display.
5.4 Resetting the System
- Once the cause of an alarm or trouble has been resolved and the alarm has been silenced, press the RESET button.
- The system will attempt to clear all active alarms and return to a normal, supervisory state. If the condition persists, the alarm will reactivate.
6. Maintenance
Regular maintenance ensures the longevity and reliability of your fire alarm control panel.
- Weekly: Visually inspect the panel for any damage or unusual indicators. Check that the 'Normal' indicator is illuminated.
- Monthly: Perform a functional test of a few selected devices (e.g., a smoke detector, a manual pull station) to ensure they communicate with the panel.
- Annually: Have a qualified technician perform a comprehensive inspection and test of the entire system, including all detectors, notification appliances, and communication paths. This includes battery load testing and replacement as needed.
- Cleaning: Keep the panel's exterior clean and free of dust. Use a soft, dry cloth. Do not use abrasive cleaners or solvents.
7. Troubleshooting
This section provides solutions for common issues. For complex problems, contact a qualified service technician.
| Problem | Possible Cause | Solution |
|---|---|---|
| Panel displays 'Trouble' | Wiring fault, device malfunction, low battery, AC power loss. | Check the display for specific trouble codes. Verify AC power. Inspect wiring for breaks or shorts. Test and replace faulty devices or batteries. |
| False Alarms | Dust in detectors, improper detector placement, environmental factors (steam, cooking fumes). | Clean detectors. Relocate detectors if necessary. Ensure proper ventilation in areas prone to false alarms. |
| Panel not powering on | No AC power, faulty power supply, disconnected battery. | Verify AC power connection and circuit breaker. Check power supply unit. Ensure batteries are correctly connected and charged. |
| Communication failure | Telephone line issue, network problem, cellular signal loss. | Check telephone line, network cable, or cellular signal strength. Contact your service provider if external lines are faulty. |
8. Specifications
| Feature | Detail |
|---|---|
| Brand | Honeywell |
| Model Number | SK 6700 |
| Point Capacity | 50-point addressable, expandable up to 100 points |
| Signaling Line Circuits (SLC) | 1 built-in |
| Panel Connectivity | Up to 17 panels (copper wire or fiber-optic cable) |
| Communicator | Built-in dual-line POTs and IP communicator, optional cellular side-cars |
| Item Weight | 15 Pounds |
| Power Source | Optic Cable (for communication, primary power is AC with battery backup) |
| Color | Red |
| Alarm Type | Audible |
| UPC | 783196014203 |
| ASIN | B07GBMJY4B |
9. Warranty and Support
Honeywell provides a limited warranty for the SK 6700 Fire Alarm Control Panel. For specific warranty terms and conditions, please refer to the warranty documentation included with your product or visit the official Honeywell website. For technical support, service, or to locate an authorized dealer, please contact Honeywell customer service or your local distributor.