1. Introduction
The Lithonia Lighting EXG LED EL M6 is a green thermoplastic LED emergency exit sign designed for commercial and industrial applications. It features a durable, impact-resistant housing and an integrated backup battery to ensure illumination during power outages. This manual provides essential information for the safe installation, operation, and maintenance of your exit sign.
2. Safety Information
WARNING: Risk of electric shock. Disconnect power before installation or servicing. Installation must be performed by a qualified electrician in accordance with all national and local electrical codes and ordinances.
- Ensure the power supply is turned off at the circuit breaker before beginning any work.
- Do not install near gas or electric heaters.
- Mount the fixture securely in locations and at heights where it will not be subjected to tampering by unauthorized personnel.
- The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
- Do not use this equipment for other than its intended use.
- All servicing should be performed by qualified service personnel.
3. Package Contents
Verify that all components are present and undamaged before proceeding with installation:
- EXG LED EL M6 Emergency Exit Sign Fixture
- Rechargeable Ni-Cad Battery (pre-installed or separate)
- Extra Faceplate for double-face conversion
- Mounting Hardware (screws, anchors)
- Instruction Manual
4. Setup and Installation
The EXG LED EL M6 exit sign is designed for universal mounting. Follow these steps for proper installation:
- Prepare for Installation: Turn off power at the circuit breaker. Select a suitable mounting location that complies with local building and fire codes.
- Mounting Options: This fixture supports universal mounting (ceiling, wall, or end mount). Use the appropriate mounting hardware for your chosen surface.
- Wiring: Connect the AC input wires to the building's electrical supply according to the wiring diagram provided inside the fixture. Ensure proper grounding.
- Battery Connection: If the battery is not pre-connected, plug the battery connector into the circuit board.
- Chevron Directional Indicators: The universal chevrons (arrows) are easily removable. Remove the appropriate chevrons to indicate the direction of egress as required by your installation.
- Double-Face Conversion (Optional): If a double-face sign is required, remove the existing faceplate and install the extra faceplate provided. Ensure the internal light source illuminates both faces evenly.
- Secure the Fixture: Close and secure the housing cover.
- Restore Power: Turn on power at the circuit breaker. The sign should illuminate, and the battery should begin charging.

Figure 1: Lithonia Lighting EXG LED EL M6 Emergency Exit Sign with green 'EXIT' text and directional arrows.

Figure 2: Dimensions of the EXG LED EL M6 exit sign, showing approximate length of 11.6 inches and height of 7.5 inches.
5. Operating Instructions
Once properly installed and powered, the Lithonia Lighting EXG LED EL M6 operates automatically:
- Normal Operation: When AC power is present, the LED 'EXIT' sign will be continuously illuminated. The internal Ni-Cad battery will be charged and maintained at full capacity.
- Emergency Operation: In the event of an AC power failure, the exit sign will automatically switch to battery backup mode, providing illumination for a minimum of 90 minutes.
- Test Button: A test button is typically located on the side or bottom of the fixture. Pressing this button simulates an AC power failure, allowing you to verify the emergency lighting function. The sign should remain illuminated while the button is pressed.
6. Maintenance
Regular maintenance ensures the reliability and longevity of your emergency exit sign:
- Monthly Test: Press the test button for at least 30 seconds. The 'EXIT' sign should remain illuminated. Release the button; the sign should return to AC operation.
- Annual Test: Disconnect AC power to the unit for a full 90 minutes. The 'EXIT' sign should remain illuminated for the entire duration. Reconnect AC power after the test.
- Cleaning: Clean the thermoplastic housing and faceplate periodically with a soft, damp cloth. Do not use abrasive cleaners or solvents.
- Battery Replacement: The Ni-Cad battery has a limited lifespan. If the unit fails to meet the 90-minute emergency illumination requirement during testing, the battery may need replacement. Contact qualified service personnel for battery replacement.
7. Troubleshooting
If your emergency exit sign is not functioning correctly, refer to the following table:
| Problem | Possible Cause | Solution |
|---|---|---|
| Sign does not illuminate (AC power present) | No AC power to the fixture; Loose wiring; Faulty LED driver. | Check circuit breaker; Verify wiring connections; Contact qualified service personnel. |
| Sign does not illuminate in emergency mode (AC power off) | Battery not connected; Battery not charged; Faulty battery; Faulty circuit board. | Ensure battery is connected; Allow 24 hours for initial charge; Replace battery; Contact qualified service personnel. |
| Sign illuminates for less than 90 minutes in emergency mode | Battery not fully charged; Aging battery. | Allow 24 hours for full charge; Replace battery. |
8. Specifications
- Model: EXG LED EL M6
- Brand: Lithonia Lighting
- Light Type: LED
- Color: Green Text
- Material: Thermoplastic (Impact Resistant, Scratch Resistant, Corrosion Proof)
- Mounting Type: Universal (Wall, Ceiling, End)
- Item Weight: Approximately 2 Pounds
- Dimensions (L x W): 11.6 inches x 7.5 inches
- Battery: Rechargeable Ni-Cad Battery
- Emergency Illumination: 90 minutes minimum
- Standards Met: UL924, NFPA 101, NEC, OSHA, UL Listed (Damp Location)
- Visibility: 6-inch high letters with 3/4-inch stroke, visible from up to 100 feet