1. Introduction
This manual provides detailed instructions for the installation, operation, and maintenance of the Copeland XR02CX-5N0C1 Temperature Controller. This device is designed for precise temperature management in freezer and refrigerator applications, offering reliable control for various cooling systems.

2. Specifications
| Parameter | Value |
|---|---|
| Model | XR02CX-5N0C1 |
| Output Type | Single output (compressor control, shutdown defrosting) |
| Power Supply | 230Vac ± 10%/50-60Hz (Refer to nameplate for other options like 12Vac/dc, 24Vac/dc, 110Vac) |
| Power Consumption | Maximum 3VA |
| Display | 2 red digital tubes, 14.2mm high |
| Temperature Input | 1 NTC input, measurement range -40 ℃ to 110 ℃ |
| Digital Input | Passive switch quantity |
| Output Relay (Compressor) | SPST A, 250Vac; 20 (8) A 250Vac (Max instantaneous 20A, Rated 8A) |
| Shell Material | ABS matte flame-retardant plastic |
| Dimensions (Front) | 32x74mm |
| Depth | 60mm |
| Installation Size | Panel opening of 71x29mm |
| Protection Level | Overall IP20, Front panel IP65 |
| Origin | Mainland China |
| Certification | CE |
3. Setup and Installation
Careful installation is crucial for the proper functioning and longevity of the temperature controller. Ensure all power is disconnected before proceeding with installation.
3.1 Mounting the Controller
- Prepare a panel opening with dimensions of 71x29mm.
- Insert the controller into the opening from the front.
- Secure the controller using the provided mounting clips on the sides.

3.2 Electrical Connections
Refer to the wiring diagram on the product label for precise connections. Incorrect wiring can damage the unit or connected equipment.

Wiring Diagram Interpretation (refer to Figure 3):
- Terminals 1-2: Hot Key connection.
- Terminals 3-4: Digital Input.
- Terminals 6-7: Supply (Power Input). For 230V models, connect 230V AC here.
- Terminals 8-9: Compressor (Comp) Relay Output. Connect your compressor load here.
- Probe NTC: Connect the NTC temperature sensor to the designated terminals (typically labeled "Room" or similar, often separate from the main terminal block or indicated by specific symbols).
Ensure the power supply matches the controller's specified voltage (e.g., 230V AC for this model). The output relay for the compressor is rated for 20(8)A at 250Vac, meaning it can handle a maximum instantaneous current of 20A and a rated continuous current of 8A.
4. Operating Instructions
The XR02CX-5N0C1 controller features a simple interface for temperature monitoring and setting.
4.1 Display and Buttons

The front panel (Figure 5) includes:
- Digital Display: Shows the current temperature and programming parameters.
- SET Button: Used to enter and confirm parameter settings.
- UP Arrow Button: Used to increase values or navigate menus.
- DOWN Arrow Button: Used to decrease values or navigate menus.
- AUX Button: Auxiliary function button, specific use may vary based on configuration.
4.2 Setting the Setpoint Temperature
- Press the SET button briefly to display the current setpoint.
- Use the UP or DOWN arrow buttons to adjust the setpoint to your desired temperature.
- Press the SET button again to confirm and save the new setpoint.
4.3 Accessing and Modifying Parameters
Advanced parameters allow customization of control logic, defrost cycles, and alarm settings. Consult the full technical manual for a complete list of parameters and their functions.
- To enter the programming menu, press and hold the SET button for several seconds until a parameter code appears.
- Use the UP or DOWN arrow buttons to scroll through the parameter codes.
- Press SET to view the value of the selected parameter.
- Use the UP or DOWN arrow buttons to modify the parameter value.
- Press SET to confirm the new value and move to the next parameter, or exit the menu.
5. Maintenance
The Copeland XR02CX-5N0C1 controller is designed for reliable operation with minimal maintenance. However, periodic checks can ensure optimal performance.
- Cleaning: Periodically clean the front panel with a soft, damp cloth. Do not use abrasive cleaners or solvents. Ensure no liquid enters the unit.
- Connections: Annually check all electrical connections for tightness and signs of corrosion. Loose connections can lead to intermittent operation or damage.
- Sensor Check: Verify the NTC temperature sensor is securely in place and free from physical damage. Ensure its placement accurately reflects the temperature to be controlled.
- Ventilation: Ensure adequate airflow around the controller, especially if it's installed in an enclosed space, to prevent overheating.
Warning: Disconnect all power to the controller and connected equipment before performing any maintenance or inspection.
6. Troubleshooting
This section provides solutions to common issues encountered with the XR02CX-5N0C1 controller.
| Problem | Possible Cause | Solution |
|---|---|---|
| Controller display is off | No power supply; incorrect wiring. | Check power connections (Terminals 6-7) and ensure voltage matches specifications. Verify circuit breaker. |
| Temperature reading is inaccurate or "P1" error | Faulty NTC sensor; sensor disconnected or short-circuited. | Check NTC sensor wiring. Replace sensor if damaged or faulty. |
| Compressor not turning on/off as expected | Incorrect setpoint; relay fault; wiring issue to compressor. | Verify setpoint and differential settings. Check compressor wiring (Terminals 8-9). If relay clicks but compressor doesn't start, check compressor itself. |
| Controller not responding to button presses | Unit frozen; internal fault. | Power cycle the unit. If issue persists, contact support. |
7. User Tips
- Initial Setup: Always double-check the power supply voltage before connecting the controller to avoid damage. The XR02CX-5N0C1 comes in various voltage options, so confirm the label.
- Sensor Placement: For accurate temperature control, position the NTC sensor in a location that best represents the average temperature of the controlled environment, away from direct airflow or heat sources.
- Parameter Backup: If you make extensive changes to the advanced parameters, it's good practice to note them down. This can save time during troubleshooting or if the unit needs to be reset.
8. Warranty and Support
For warranty information, technical support, or service inquiries, please contact your authorized Copeland distributor or the point of purchase. Ensure you have your product model number (XR02CX-5N0C1) and serial number (if applicable) ready when contacting support.