STATIC VOLTAGE REGULATOR
USER MANUAL
SAFETY NOTICES
- Contacting with live parts may result in serious wounds and even death.
- Electrical safety precautions should be taken before any set up, maintenance or measurement operation.
- Do not perform connection, measurement and maintenance operations alone. Keep one person with you who can help you in any emergency situation.
- Do not use the device without a protective ground connection.
- Electrical connections should only be performed by professional electricians.
- Read this manual carefully before using the device and save it for later reference.
- Ensure that ambient conditions are met with the regulations described in this manual.
- Ensure that cooling fan ventilation holes are open.
- Failure to provide the required ambient conditions will result in problems with the device.
- Do not perform any operations which you are unsure about.
- When you encounter a problem in any step throughout this guide, do not skip to next step. Contact our support department for help.
DEVICE OVERVIEW
*Device overview includes optional elements. Your device might not have all of the parts shown in image.
FIRST CONTROLS
- Check the device for any damage which may have occurred during shipping processes.
- Check the device nameplate to ensure that the information is consistent with your purchase order.
GENERAL WORKING MECHANISM
These devices use tapped transformers and Silicon Controlled Rectifiers (SCRs or thyristors) to regulate voltage. Proper taps are selected on individual transformers of each phase and independent voltage regulation between phases is accomplished. An electronic system controls the whole system with the help of a microcontroller. The electronic system requires initial power to start up. After the electronic system gets power, it starts self-tests and then controls the regulation system against any problems. If electronic system finds no problem, it continues with the rest of the steps to start the regulation.
TECHNICAL INFORMATION
5.1. Electrical Properties
| PARAMETER | MIN | NOMINAL | MAX | UNIT | |
| S | Power | – | – | See label | KVA |
| Vin | Input voltage | 172 | 230 | 264 | V (AC P-N) |
| Vout | Output voltage | 225 | 230 | 235 | V (AC P-N) |
| f | Input Frequency | 45 | 50 | 65 | Hz |
5.2. Ambient Conditions
| PARAMETER | MIN | NOMINAL | MAX | UNIT | |
| T | Temperature | -10 | 20 | 40 | °C |
| RH | Relative Humidity | – | 50 | 90 | % |
| Alt | Altitude | – | – | 2000 | m |
5.3. Optional Systems and Parts in the Device
Control and protection elements contained in your device are indicated with (x) mark in below table.
| Optional Systems and Parts | |
| Input Breaker | X |
| Output Breaker | |
| Output Contactor | X |
| Manual Bypass Switch | X |
| Isolated Transformers | |
SINGLE LINE DIAGRAM
Below single line diagram contains optional Manual Bypass Switch and optional Output Breaker too. See above table to determine if your device has these optional parts.
- Input Breaker.
- Output Contactor.
- Manual Bypass Switch (optional).
- Regulation System Components.
- Output Breaker (optional).
SWITCHING and PROTECTION ELEMENTS
Not all of the elements explained in this part might be present in your device. See technical information part to determine which elements are contained in your device.
7.1. Input Breaker – Standard
Input Breaker controls the input power to regulation system. It also provides protection against overload or short circuit situations.
Whenever a user turns on this breaker, the regulation system gets power. Turning on the Input Breaker will not immediately supply power to output terminals. Output power will be available after the device completes self-tests.
7.2. Output Breaker – Optional
Optional Output Breaker provides manual control of the output power of the regulation system. This breaker also provides protection against overloads or short circuits.
7.3. Manual Bypass Switch – Standard
Manual Bypass Switch controls the manual bypass system. For detailed explanations about this switch see Manual Bypass System part.
7.4. Output Contactor – Standard
Output Contactor is controlled by the electronic control system. This contactor is turned on when the regulation system is ready. This way regulated energy is transferred to the output terminals.
The contactor operates automatically. When conditions are back (that means for instance in case of over voltage output contactor trips and stabilizer always measures voltages and when voltage back to stabilizer limits then stabilizer starts operation automatically.
If stabilizer keeps the same failure 3 times, then stabilizer waits 3 minutes; if it continues to take the same errors again (up to 10 times) then it stops 30 minutes. (when conditions are back then it starts automatically).
In case of over & under voltage: since stabilizer always measures the voltages. stabilizer does not operate the contactor again until the voltages are within the limits.
MANUAL BYPASS SYSTEM
Manual Bypass System is optionally included in the device. See technical information part to determine if your device has this system.
Manual Bypass System control is achieved by a rotary transfer switch which has 3 different modes.
There will be output power interruption when Manual Bypass System mode is changed. Turn off your loads and turn off the external output breaker before changing the mode of Manual Bypass System.
8.1.1. Bypass Mode
When Manual Bypass Switch is turned to label Bypass (or Line) the manual bypass mode is activated. In this mode regulation system is bypassed and input terminals are directed to output terminals. In case of a fault in regulation system or whenever loads are wanted to be fed with unregulated mains power this mode can be selected. Turning off the Input Breaker or Output Breaker will not affect the operation of the manual bypass mode. These breakers cannot break the output power while in manual bypass mode. See single line diagrams. In manual bypass mode it is possible to turn off the input breaker and shut down the device to save the no load power consumption of the device.
Output voltage values seen on front panel are not the actual output terminal voltage values in manual bypass mode, these voltage values are the output voltage values of regulation system.
8.1.2. Output Off Mode
When Manual Bypass Switch is turned to label Output Off (0 or off), the output terminals are isolated. In this mode input power to the regulation system is not turned off, only output power to loads is turned off. See single line diagrams.
8.1.3. Regulator Mode
When Manual Bypass Switch is turned to “Regulator” position, the regulation system is directed to output terminals. In this mode there will be regulated power at the output terminals. Output voltage values seen on front panel are actual output terminal voltage values in regulator mode.
INSTALLATION LOCATION
- No liquid or solid objects should enter into the device. Check the enclosure protection of the device and decide on a suitable location.
- Ensure that ambient conditions are met in the location. See Technical Information part for ambient conditions.
- Ensure that the conditions below are met for the location where you intend to place the device.
- The location should not take direct sunlight.
- There will be at least 2 meters between the device and any combustible material.
- There will be at least 25 cm between the device and any other object or wall.
- There will be at least 50 cm space behind the device to the wall.
- There will be at least 50 cm space in front of any fan airflow outlet of the device.
- There will be no flammable liquid or gas container in the location.
- Generator connection to the system should be after the device.
- Power factor correction device connection to the system should be between devicand loads.
- Contact the support department if any of the above conditions are not possible to be met.

MAKING THE CONNECTIONS OF THE DEVICE
- Below block diagram shows the recommended status of the electrical system and external protection elements after you have installed the regulator.
- The external input breaker can be the main input breaker of the building.
- An external output breaker is recommended for safety of the system.
The steps starting with the sign (OP) indicate that this step is related to an optional element. Skip to next step if you do not have this optional element.- Use a reliable true RMS multimeter to perform measurements.
- Turn off your loads.
- Turn off the main input breaker of the building.
- Turn off the external input breaker if you have it in your system.
- Using a reliable multimeter, ensure that there is no energy on the conductors which will be connected to the input terminals of the device.
- Turn off the Input Breaker of the device.
- (OP) Turn off the Optional Output Breaker of the device.
- (OP) Turn the Optional Manual Bypass Switch to Output Off (0 or Off) position.
- Turn off the external output breaker if you have it in your system.
- See Appendix 1 for properties of the conductors to be connected to the device.
- See Appendix 2 for information about the input output and other terminals of the device.
- Connect input, output and protective ground conductors to their terminals and tighten their screws with proper amount of torque.
- See Appendix 3 for tightening torque values.
- After you have completed connections, check the labels and conductors again.
SUPPLYING POWER TO LOADS
- Complete the steps below in order to supply power to loads.
- The steps starting with the sign (OP) indicate that this step is related to an optional element. Skip to next step if you do not have this optional element.
- Use a reliable true RMS multimeter to perform measurements.
- Ensure that the breakers mentioned in the Making the Connections of the Device part are turned off.
- Ensure that the input, output and protective ground connections are completed properly as described in the Making the Connections of the Device part.
- Turn on the main input breaker of the building and turn on the external input breaker if you have it in your system. This will supply power to input terminals of the device.
- Measure voltage at the input terminals of the device. Ensure that voltage at the input terminals is at the expected value.
- Measure voltage at output terminals; ensure that there is no energy at the output terminals.
- (OP) Continue with following sub steps if your device has a Manual Bypass Switch. Skip to the next step if it does not have a Manual Bypass Switch.
6.1. Turn the manual bypass switch to bypass mode. This will direct the power at input terminals to output terminals.
6.2. Measure voltage at output terminals. Ensure that voltage at output terminals is same as voltage at input terminals.
6.3. Turn the Manual Bypass Switch into “REGULATOR” mode. - Turn on the Input Breaker. This will power up the regulation system and the front panel.
- Electronic system starts self-tests after the regulation system is powered up. These controls last in 10 to 30 seconds. After self tests are completed, regulated power is automatically directed to output terminals.
- While optional Manual Bypass Switch is at regulator mode, there will be no power at output terminals until the startup self-tests are completed.
- (OP) In devices which contain optional Output Breaker, regulated power to output terminals can be controlled manually. After starting up the regulation system, turn on the optional Output Breaker to direct the regulated power to output terminals.
- Measure voltage at output terminals. Ensure that output voltage is within the limits indicated in the Technical Information part.
- Turn on the external output breaker if you have it in your system.
- Turn on your loads.
- After turning on the loads control the load percentage value shown on the front panel. Ensure that load percentage value is below 100%. See Front Panel and LCD section for information about front panel.
- If load percentage value is not below 100% you will have to disconnect some of your loads. If this is not possible, contact support department.
- After turning on the loads and ensuring that there is no problem, enter the input, output voltage and load percentage value to the commissioning form. Sign a copy of commissioning form and send it to support department. This is required for alidation of device warranty.
TURNING OFF THE DEVICE
- Turn off your loads before turning off the device.
- Turn off the external output breaker if you have it in your system.
- Turn off the optional Output Breaker.
- Turn off the Input Breaker. This will cut off the power to the regulation system.
- Turn off the external input breaker if you have it in your system.
- After turning off the Input Breaker it is possible to feed the loads with unregulated mains power by turning the optional Manual Bypass Switch to bypass mode.
FRONT PANEL and LCD
13.1. General Information
- The front panel of the device starts working when the Input Breaker is turned on and the regulation system is energized.
- “INPUT” labeled light indicates that input power to the device and its main control board is present.
- “OUTPUT” labeled light shows the status of the main control board of the device. If the light is on, then the main control board of this phase has completed self-tests and turned on the Output Contactor.
- The “FAULT” red light turns on when the regulation system has a problem. Go to ongoing Fault Screen and Fault Records in the front panel LCD and check the fault codes. See fault codes part in this manual for explanations of the fault codes.
13.2. LCD Screen
13.2.1 General Information
- Screen number: The string at the upper right corner indicates the screen number being shown (M1, M2…).
- Switching between screens: Use “Up and “Down” buttons on the front panel to switch between screens.
- Selecting an option or entering a submenu: Press and hold “Up” or “Down” button to enter into a submenu or select an option.
- Cursor symbol ( > ) at the beginning of a row indicates that this row has an option which can be changed.
- Edit option symbol ( = ) at the beginning of a row indicates that the option or value on this row is selected and can be changed by pressing “Up” or “Down” buttons.
- Press and hold “Up” or “Down” button to change the edit option symbol to cursor symbol.
- Select Save & Exit option to save, apply and exit the settings you have made.
13.2.2 M1 – Input Output Voltage and Load Percentage Screen
- Displays the input, output voltages and the load percentage of the regulation system.
13.2.3 M2 – Frequency Screen
- Displays the input line frequency measured by the electronic system.
- This value is displayed for only information purposes. The device cannot change the frequency.
- The device will work in any frequency value inside the range indicated in the electrical properties table.
13.2.4 M3 – Ongoing Fault Screen
- Displays the ongoing fault of the regulation system. Check Fault Codes part in this manual for the explanation of the fault code.
13.2.5 M4 – Fault Records Entrance Screen
- Fault records list can be accessed from this screen.
- Press and hold “Up” or “Down” button to enter into the fault records menu.
- Press “Up” or “Down” button to switch between fault code records.
- See Fault Codes part in this manual for explanation of fault codes.
- Press and hold “Up” or “Down” button to exit from fault records menu to main menu.
- Clearing Fault Records: While on Faults Screen press and hold “Up” or “Down” button to enter into fault records menu. Do not release “Up” or “Down” button after entering into fault records menu. After a few seconds the fault records will be cleared.
13.2.6 M4.X – Fault M. (Fault Records List)
- This screen allows checking the records of previous fault codes.
- Whenever a fault occurred, its fault code is recorded in this screen.
- Lower number indicates the more recently occurred fault.
13.2.7 M5 – Settings Entrance Screen
- Settings can be accessed from this screen.
- Press and hold “Up” or “Down” button to enter into the settings.
13.2.8 M5.1 Out Val Setting
- The first setting in the setting menu is Out Val. This is the regulation system target output voltage value.
- Change this value to your preferred output voltage value.
13.2.9 M5.2 Offset
- The second setting in the settings menu is Offset. This is the target output voltage sensitivity value.
- The output voltage can go plus minus this amount of voltage from Out Val voltage. If this setting is set too low which might be beyond the capability of the device, the regulation system can behave unexpectedly. Do not change this value unless instructed by the technical service personnel.
13.2.1 M6 Sys Info
This menu shows device firmware versions and EEPROM options. It is informative only. There are no user changeable settings
CONTROLS AFTER INSTALLATION
- After the first installation, turn on as much load as possible which will not exceed load percentage shown on front panel over 100%.
- Wait for a few hours for ambient temperature to stabilize. Ensure that the temperature stays inside the allowed range indicated in the Technical Specifications part.
- Check the environmental conditions once in 6 months.
- Check cooling fan airflow holes once in 6 months to ensure that they are not blocked. The cooling fans might be controlled by a thermic switch which turns on fans at a certain temperature level.
- These fans might not start running when you start up the device.
TROUBLESHOOTING
15.1. Fault Codes
Below table explains the fault codes and recommended actions. See next section for information about other situations.
Error Format; yaaa
y: for 1 means L1 Phase
y: for 2 means L2 Phase
y: for 3 means L3 Phase
y: for 4 means General Failure
aaa: means specific error code
EXAMPLE: 2010 means L2 Phase current zero failure
| Code | Description | Code | Description |
| y000 | No Error | y027 | Current Zero Failure 7 number Thyristor |
| y001 | Input Voltage very high | y028 | Current Zero Failure 8 number Thyristor |
| y002 | Input Voltage high | y029 | Current Zero Failure 9 number Thyristor |
| y003 | Input Voltage very low | y030 | Thyristor Open Circuit Failure 1x number Thyristor |
| y004 | Input Voltage low | y031 | Thyristor Open Circuit Failure 1 number Thyristor |
| y005 | Output voltage very high | y032 | Thyristor Open Circuit Failure 2 number Thyristor |
| y006 | Output voltage high | y033 | Thyristor Open Circuit Failure 3 number Thyristor |
| y007 | Output voltage very low | y034 | Thyristor Open Circuit Failure 4 number Thyristor |
| y008 | Output voltage low | y035 | Thyristor Open Circuit Failure 5 number Thyristor |
| y010 | Current Zero Failure | y036 | Thyristor Open Circuit Failure 6 number Thyristor |
| y011 | Thyristor Open Circuit input | y037 | Thyristor Open Circuit Failure 7 number Thyristor |
| y012 | Thyristor Open Circuit output | y038 | Thyristor Open Circuit Failure 8 number Thyristor |
| y013 | Thyristor Fuse Off | y039 | Thyristor Open Circuit Failure 9 number Thyristor |
| y015 | Short Circuit Failure | y040 | Input Square Wave Low Failure |
| y016 | Remote ByPass | y041 | Input Square Wave High Failure |
| y017 | Over Temperature | y042 | Load Higher than %100 |
| y018 | Current Zero Failure İnput Thyristor (SCR) | y043 | Load Higher than %125 |
| y019 | Current Zero Failure Output Thyristor | y044 | Load Higher than %150 |
| y020 | Current Zero Failure 1x number Thyristor | y045 | Load Higher than %175 |
| y021 | Current Zero Failure 1 number Thyristor | y046 | Load Higher than %200 |
| y022 | Current Zero Failure 2 number Thyristor | y047 | Wait Other Phase |
| y023 | Current Zero Failure 3 number Thyristor | y060 | Communication Error Between Mainboard and Front panel |
| y024 | Current Zero Failure 4 number Thyristor | y3xx | System hardware failures, please inform us |
| y025 | Current Zero Failure 5 number Thyristor | y4xx | System hardware failures, please inform us |
| y026 | Current Zero Failure 6 number Thyristor | y9xx | Device Protect itself. Device will Wait “xx” minute, because of 3 times same error |
15.2. Other Situations
15.2.1. Output voltage is not at the desired level.
- Control the SETOUT setting in settings menu.
- Input voltage level might be out of range of allowed limits. If input voltage level is not within the limits desired output voltage cannot be generated.
- There can be a voltage measurement calibration problem. This can happen after a long period of device working time. See below explanation.
15.2.2. Front panel displaying wrong voltage values.
- Measure input and output voltages from the input and output terminals with a multimeter. Compare measured values with the front panel displayed values.
- A voltage measurement calibration on the mainboards might be required if there are more than 3 volts difference between multimeter measurement and front panel displayed values.
- Voltage calibration operation will require opening the covers of the device. Contact support department for detailed instructions.
15.2.3. Front panel displaying wrong load percentage value.
- Load percentage value shown on front panel is only for the electronic system to detect overloads. There can be up to 10% deviation from actual value.
- If the deviation is more than 10%, load calibration on mainboards is required. Contact support department for detailed instructions.
15.2.4. Building lights are flickering.
- This problem occurs when device settings are not set properly.
- Contact the support department to solve this problem.
15.2.5. Comm Error string on the front panel.
- Front panel cannot communicate with the mainboard.
- See fault codes table.
15.2.6. Front panel does not display one or more of the voltage values.
- One or more of the regulation system components might be damaged.
- Contact support department.
APPENDICES
16.1. Appendix 1 – Input and Output Conductor Properties
- Below table contains information about the cross-sectional area of the conductors to be connected to device terminals.
- Cross sectional area values indicated in this table are recommended minimum values.
- Find the conductor cross sectional area corresponding to your device power rating.
- Neutral and protective earth cable sizes are the same with input phase cable sizes.
- Input and output conductor sizes are different because input and output voltage and currents are different.
| Power per phase (kVA) | Input Conductor Size (mm2) | Output Conductor Size (mm2) |
| <= 3 | 5 | 3 |
| 5 | 8 | 6 |
| 8 | 14 | 10 |
| 10 | 20 | 15 |
| 15 | 30 | 23 |
| 20 | 40 | 30 |
| 30 | 61 | 45 |
| 40 | 81 | 61 |
| 50 | 101 | 76 |
16.2. Appendix 2 – Input and Output Terminal Configurations
16.2.1 General Rules
- Input conductors will be connected to terminals with label INPUT. Output conductors will be connected to terminals with label OUTPUT.
- Phase connection terminals are labeled as L.
- Neutral connection terminals are labeled as N or Neutral.
- Protective Earth connection terminal is labeled as PE.
16.2.2 Screw Terminals
Terminals and labels at the back of the device are shown above.- Terminal screw diameter might change according to device power. Measure terminal screw diameters and determine the tightening torque value from Appendix 3.
- Stranded wires must be crimped with cord end terminals before connecting to screw terminals.
16.2.3 Appendix 3 – Tightening Torque Values
Diameter row on the below table indicates the diameter of the bolt or screw in millimeter.
| Diameter | Tightening Torque (N.m) | Diameter | Tightening Torque (N.m) | |
| M3 | 1.14 | M7 | 15 | |
| M3.5 | 1.8 | M8 | 22 | |
| M4 | 2.7 | M10 | 44 | |
| M4.5 | 3.9 | M12 | 76 | |
| M5 | 5.4 | M14 | 122 | |
| M6 | 9.2 | M16 | 190 |
16.3. Appendix 4 – Enclosure Protection Class
16.3.1 IP Protection Class
| Level | First digit identifies the protection level against solid objects. | Second digit identifies the protection level against liquids |
| 0 | No protection | No protection |
| 1 | Protection against objects larger than 50 mm. | Protection against liquid dripping from above. |
| 2 | Protection against objects larger than 12.5 mm. | Protection against liquid dripping from above when device is inclined towards any side at 15° or more. |
| 3 | Protection against objects larger than 2.5 mm. | Protection against spray of liquid from above when device is inclined towards any side at 60° or more. |
| 4 | Protection against objects larger than 1 mm. | Protection against liquid that sprayed or poured from anyangle to the device. |
| 5 | Limited protection against objects as small as dust particles. | Protection against liquid that sprayed with a 6.3 mm radius nozzle to the device from any angle. |
| 6 | Full protection against objects as small as dust particles. | Protection against liquid that sprayed with a 12.5 mm radius nozzle with pressure to the device from any angle. |
16.3.2. Example:
IP20 protection class indicates that the device has protection against only solid objects larger than 12.5 mm. There is no protection against liquids.
APPENDIX 5: MODBUS TABLE (MODBUS-RTU COMMUNICATION IS OPTIONAL ON IMP1 RANGE)
| Modbus Map | |||||||
| Device ID | Default 1 (Adjustable by Front panel and Modbus) | ||||||
| Baud Rate | Default 38400bps (Adjustable by Front panel and Modbus) | ||||||
| Parity | None (Adjustable by Front panel and Modbus) | ||||||
| Stop Bits | 1 Stop Bit (Adjustable by Front panel and Modbus) | ||||||
| Supported Functions | write Multiple Holding Registers(0x10), Write Single Holding Registers(0x06), Read Holding Registers(0x03) | ||||||
| Holding Register Map | |||||||
| Addresses | UPDATE DATE | Data Name | Data Types | Reading / Writing |
Descriptions | ||
| Single stabilizer | VOR (Parallel Stabilizer) | ||||||
| 0 | x | x | 01/01/2017 | Device Status | unsigned 16 bits | R | 0:Off, 1:On |
| 1 | x | x | 01/01/2017 | L1 – input Voltage (V) | unsigned 16 bits | R | |
| 2 | x | x | 01/01/2017 | L2 – input Voltage (V) | unsigned 16 bits | R | |
| 3 | x | x | 01/01/2017 | L3 – input Voltage (V) | unsigned 16 bits | R | |
| 4 | x | x | 01/01/2017 | L1 – Output Voltage (V) | unsigned 16 bits | R | |
| 5 | x | x | 01/01/2017 | L2 – Output Voltage (V) | unsigned 16 bits | R | |
| 6 | x | x | 01/01/2017 | L3 – Output Voltage (V) | unsigned 16 bits | R | |
| 7 | x | x | 01/01/2017 | L1 – Load (%) | unsigned 16 bits | R | |
| 8 | x | x | 01/01/2017 | L2 – Load(%) | unsigned 16 bits | R | |
| 9 | x | x | 01/01/2017 | L3 – Load(%) | unsigned 16 bits | R | |
| 10 | x | x | 01/01/2017 | L1 – Frequency (Hz) | unsigned 16 bits | R | Divide 10 |
| 11 | x | x | 01/01/2017 | L2 – Frequency (Hz) | unsigned 16 bits | R | Divide 10 |
| 12 | x | x | 01/01/2017 | L3 – Frequency (Hz) | unsigned 16 bits | R | Divide 10 |
| 13 | x | 01/01/2017 | L1 – Common Output Voltage (V) | unsigned 16 bits | R | ||
| 14 | x | 01/01/2017 | L2 – Common Output Voltage (V) | unsigned 16 bits | R | ||
| 15 | x | 01/01/2017 | L3 – Common Output Voltage (V) | unsigned 16 bits | R | ||
| 21 | x | x | 07/12/2021 | FrontPanel Firmware Version – Highest (A) | Unsigned 16 bits | R | A.B.C |
| 22 | x | x | 07/12/2021 | FrontPanel Firmware Version – Middle (B) | Unsigned 16 bits | R | |
| 23 | x | x | 07/12/2021 | FrontPanel Firmware Version – Lowest ( C) | Unsigned 16 bits | R | |
| 25 | x | 10/06/2021 | Working Mode – Paralel Devices | unsigned 16 bits | R | 0: Invalid 1:Master 2:Slave | |
| 26 | x | 01/01/2017 | Number of Common Connections | unsigned 16 bits | R | ||||
| 27 | x | 10/06/2021 | Number of Communication Devices | unsigned 16 bits | R | ||||
| 29 | x | x | 07/12/2021 | L1 Mainboard Firmware Version – Highest (A) | Unsigned 16 bits | R | A.B.C | ||
| 30 | x | x | 07/12/2021 | L1 Mainboard Firmware Version – Middle (B) | Unsigned 16 bits | R | |||
| 31 | x | x | 07/12/2021 | L1 Mainboard Firmware Version – Lowest ( C) | Unsigned 16 bits | R | |||
| 32 | x | x | 07/12/2021 | L2 Mainboard Firmware Version – Highest (A) | Unsigned 16 bits | R | A.B.C | ||
| 33 | x | x | 07/12/2021 | L2 Mainboard Firmware Version – Middle (B) | Unsigned 16 bits | R | |||
| 34 | x | x | 07/12/2021 | L2 Mainboard Firmware Version – Lowest ( C) | Unsigned 16 bits | R | |||
| 35 | x | x | 07/12/2021 | L3 Mainboard Firmware Version – Highest (A) | Unsigned 16 bits | R | A.B.C | ||
| 36 | x | x | 07/12/2021 | L3 Mainboard Firmware Version – Middle (B) | Unsigned 16 bits | R | |||
| 37 | x | x | 07/12/2021 | L3 Mainboard Firmware Version – Lowest ( C) | Unsigned 16 bits | R | |||
| 39 | x | 01/01/2022 | Mainboard Active SCR – L1 | unsigned 16 bits | R | ||||
| 40 | x | 01/01/2022 | Mainboard Active SCR – L2 | unsigned 16 bits | R | ||||
| 41 | x | 01/01/2022 | Mainboard Active SCR – L3 | unsigned 16 bits | R | ||||
| 45 | x | 01/01/2022 | Web Server IP Number Area 1 | unsigned 16 bits | R | xxx.000.000.000 | |||
| 46 | x | 01/01/2022 | Web Server IP Number Area 2 | unsigned 16 bits | R | 000.xxx.000.000 | |||
| 47 | x | 01/01/2022 | Web Server IP Number Area 3 | unsigned 16 bits | R | 000.000.xxx.000 | |||
| 48 | x | 01/01/2022 | Web Server IP Number Area 4 | unsigned 16 bits | R | 000.000.000.xxx | |||
| 49 | X | 01/01/2022 | Device ID | unsigned 16 bits | R | Device ID number for paralel connections | |||
| 50 | 17/04/2024 | Led Status of Line (Touch Screen) | unsigned 16 bits | R | |||||
| 51 | 17/04/2024 | Led Status of DVR (Touch Screen) | unsigned 16 bits | R | |||||
| 52 | 17/04/2024 | Led Status of ByPass (Touch Screen) | unsigned 16 bits | R | |||||
| 53 | 17/04/2024 | Led Status of Output (Touch Screen) | unsigned 16 bits | R | |||||
| 54 | 17/04/2024 | Load Average (Touch Screen) | unsigned 16 bits | R | |||||
| 60 | 04/09/2024 | General Failure Warning Code | unsigned 16 bits | R | |||||
| 61 | 04/09/2024 | Input Voltage Warning Code | unsigned 16 bits | R | |||||
| 62 | 04/09/2024 | Output Voltage Warning Code | unsigned 16 bits | R | |||||
| 63 | 04/09/2024 | Load Warning Code | unsigned 16 bits | R | |||||
| 64 | 04/09/2024 | OVT Warning Code | unsigned 16 bits | R | |||||
| 65 | 04/09/2024 | For Input Control Device=Input Breaker Condition For Output Control Device=Output Breaker Condition 0:Off 1:On |
unsigned 16 bits | R | |||||
| 101 | x | x | 01/01/2017 | Set Output Voltage | unsigned 16 bits | R/W | (Range : 210-240, Default:230) |
| 103 | x | x | 01/01/2017 | Set Regulation Type | unsigned 16 bits | R/W | 1:Standart, 2:Fast, 3:Stable 4:Slow (Range : 1-4, Default:1) |
| 104 | x | x | 01/01/2017 | Modbus – Slave Configuration | unsigned 16 bits | R/W | 1:9600_8None, 2:19200 8None, 3:38400 8None, 4:57600 8None, 5:115200 8None, 6:9600 8Even, 7:19200 8Even, 8:38400 8Even, 9:57600 8Even, 10:115200 8Even, 11:9600 8Odd, 12:19200 8Odd, 13:38400 8Odd, 14:57600 8Odd, 15:115200 8Odd (Range : 1-15, Default:1) |
| 105 | x | x | 01/01/2017 | Modbus – Slave Address | unsigned 16 bits | R/W | (Range : 1-252, Default:1) |
| 106 | x | x | 22/11/2021 | Sound Alarm Feature | unsigned 16 bits | R/W | 0: Off , 1:On (Range : 0-1, Default:1) |
| 107 | x | x | 01/01/2017 | Set Time – Date : Year (2digit) | unsigned 16 bits | R/W | (Range : 0-99, Default:None) |
| 108 | x | x | 01/01/2017 | Set Time – Date : Month | unsigned 16 bits | R/W | (Range : 1-12, Default:None) |
| 109 | x | x | 01/01/2017 | Set Time – Date : Day | unsigned 16 bits | R/W | (Range : 1-31, Default:None) |
| 110 | x | x | 01/01/2017 | Set Time – Date : Hour | unsigned 16 bits | R/W | (Range : 0-23, Default:None) |
| 111 | x | x | 01/01/2017 | Set Time – Date : Minutes | unsigned 16 bits | R/W | (Range : 0-59, Default:None) |
| 112 | x | x | 23/11/2021 | Sound Alarm Mute Advanced Feature ; When the device status gone to “OFF” from “ON”, The Sound Alarm Mute will be “unmuted” (#196- Sound Alarm Feature must be “ON”) |
unsigned 16 bits | R/W | 1: Unmuted , 2:Muted (Range : 1-2, Default:Unmuted) |
| 130 | x | x | 07/08/2024 | CH1 Modbus ID | unsigned 16 bits | R/W | (Range : 1-252, Default:1) |
| 131 | x | x | 07/08/2024 | CH1 Modbus Baudrate | unsigned 16 bits | R/W | 1:9600, 2:19200 , 3:38400, 4:57600 , 5:115200 |
| 132 | x | x | 07/08/2024 | CH1 Modbus Parity | unsigned 16 bits | R/W | 1: none, 2: even, 3:odd |
| 200 | x | x | 07/12/2021 | Frontpanel – Actual Error | Unsigned 16 bits | R | Details in Error List document |
| 201 | x | x | 07/12/2021 | L1 Phase -Actual Error | unsigned 16 bits | R | Details in Error List document |
| 202 | x | x | 07/12/2021 | L2 Phase -Actual Error | unsigned 16 bits | R | Details in Error List document |
| 203 | x | x | 07/12/2021 | L3 Phase -Actual Error | unsigned 16 bits | R | Details in Error List document |
| 204 | x | x | 07/12/2021 | Total Recorded Error | unsigned 16 bits | R | Details in Error List document |
| 205 | x | x | 07/12/2021 | Last 1 – Recorded Error Code | unsigned 16 bits | R | Details in Error List document |
| 206 | x | x | 07/12/2021 | Last 1 – Recorded Error Code Year (4digit) | unsigned 16 bits | R | Details in Error List document |
| 207 | x | x | 07/12/2021 | Last 1 – Recorded Error Code Month | unsigned 16 bits | R | Details in Error List document |
| 208 | x | x | 07/12/2021 | Last 1 – Recorded Error Code Day | unsigned 16 bits | R | Details in Error List document |
| 209 | x | x | 07/12/2021 | Last 1 – Recorded Error Code Hour (24h) | unsigned 16 bits | R | Details in Error List document |
| 210 | x | x | 07/12/2021 | Last 1 – Recorded Error Code Minute | unsigned 16 bits | R | Details in Error List document |
| 211 | x | x | 07/12/2021 | Last 2 – Recorded Error Code | unsigned 16 bits | R | Details in Error List document |
| 212 | x | x | 07/12/2021 | Last 2 – Recorded Error Code Year (4digit) | unsigned 16 bits | R | Details in Error List document |
| 213 | x | x | 07/12/2021 | Last 2 – Recorded Error Code Month | unsigned 16 bits | R | Details in Error List document |
| 214 | x | x | 07/12/2021 | Last 2 – Recorded Error Code Day | unsigned 16 bits | R | Details in Error List document |
| 215 | x | x | 07/12/2021 | Last 2 – Recorded Error Code Hour (24h) | unsigned 16 bits | R | Details in Error List document |
| 216 | x | x | 07/12/2021 | Last 2 – Recorded Error Code Minute | unsigned 16 bits | R | Details in Error List document |
| 217 | x | x | 07/12/2021 | Last 3 – Recorded Error Code | unsigned 16 bits | R | Details in Error List document |
| 218 | x | x | 07/12/2021 | Last 3 – Recorded Error Code Year (4digit) | unsigned 16 bits | R | Details in Error List document |
| 219 | x | x | 07/12/2021 | Last 3 – Recorded Error Code Month | unsigned 16 bits | R | Details in Error List document |
| 220 | x | x | 07/12/2021 | Last 3 – Recorded Error Code Day | unsigned 16 bits | R | Details in Error List document |
| 221 | x | x | 07/12/2021 | Last 3 – Recorded Error Code Hour (24h) | unsigned 16 bits | R | Details in Error List document |
| 222 | x | x | 07/12/2021 | Last 3 – Recorded Error Code Minute | unsigned 16 bits | R | Details in Error List document |
| 223 | x | x | 07/12/2021 | Last 4 – Recorded Error Code | unsigned 16 bits | R | Details in Error List document |
| 224 | x | x | 07/12/2021 | Last 4 – Recorded Error Code Year (4digit) | unsigned 16 bits | R | Details in Error List document |
| 225 | x | x | 07/12/2021 | Last 4 – Recorded Error Code Month | unsigned 16 bits | R | Details in Error List document |
| 226 | x | x | 07/12/2021 | Last 4 – Recorded Error Code Day | unsigned 16 bits | R | Details in Error List document |
| 227 | x | x | 07/12/2021 | Last 4 – Recorded Error Code Hour | unsigned 16 bits | R | Details in Error List document |
| 228 | x | x | 07/12/2021 | Last 4 – Recorded Error Code Minute | unsigned 16 bits | R | Details in Error List document |
| 229 | x | x | 07/12/2021 | Last 5 – Recorded Error Code | unsigned 16 bits | R | Details in Error List document |
| 230 | x | x | 07/12/2021 | Last 5 – Recorded Error Code Year (4digit) | unsigned 16 bits | R | Details in Error List document |
| 231 | x | x | 07/12/2021 | Last 5 – Recorded Error Code Month | unsigned 16 bits | R | Details in Error List document |
| 232 | x | x | 07/12/2021 | Last 5 – Recorded Error Code Day | unsigned 16 bits | R | Details in Error List document |
| 233 | x | x | 07/12/2021 | Last 5 – Recorded Error Code Hour (24h) | unsigned 16 bits | R | Details in Error List document |
| 234 | x | x | 07/12/2021 | Last 5 – Recorded Error Code Minute | unsigned 16 bits | R | Details in Error List document |
| 235 | x | x | 07/12/2021 | Last 6 – Recorded Error Code | unsigned 16 bits | R | Details in Error List document |
| 236 | x | x | 07/12/2021 | Last 6 – Recorded Error Code Year (4digit) | unsigned 16 bits | R | Details in Error List document |
| 237 | x | x | 07/12/2021 | Last 6 – Recorded Error Code Month | unsigned 16 bits | R | Details in Error List document |
| 238 | x | x | 07/12/2021 | Last 6 – Recorded Error Code Day | unsigned 16 bits | R | Details in Error List document |
| 239 | x | x | 07/12/2021 | Last 6 – Recorded Error Code Hour (24h) | unsigned 16 bits | R | Details in Error List document |
| 240 | x | x | 07/12/2021 | Last 6 – Recorded Error Code Minute | unsigned 16 bits | R | Details in Error List document |
| 241 | x | x | 07/12/2021 | Last 7 – Recorded Error Code | unsigned 16 bits | R | Details in Error List document |
| 242 | x | x | 07/12/2021 | Last 7 – Recorded Error Code Year (4digit) | unsigned 16 bits | R | Details in Error List document |
| 243 | x | x | 07/12/2021 | Last 7 – Recorded Error Code Month | unsigned 16 bits | R | Details in Error List document |
| 244 | x | x | 07/12/2021 | Last 7 – Recorded Error Code Day | unsigned 16 bits | R | Details in Error List document |
| 245 | x | x | 07/12/2021 | Last 7 – Recorded Error Code Hour (24h) | unsigned 16 bits | R | Details in Error List document |
| 246 | x | x | 07/12/2021 | Last 7 – Recorded Error Code Minute | unsigned 16 bits | R | Details in Error List document |
| 247 | x | x | 07/12/2021 | Last 8 – Recorded Error Code | unsigned 16 bits | R | Details in Error List document |
| 248 | x | x | 07/12/2021 | Last 8 – Recorded Error Code Year (4digit) | unsigned 16 bits | R | Details in Error List document |
| 249 | x | x | 07/12/2021 | Last 8 – Recorded Error Code Month | unsigned 16 bits | R | Details in Error List document |
| 250 | x | x | 07/12/2021 | Last 8 – Recorded Error Code Day | unsigned 16 bits | R | Details in Error List document |
| 251 | x | x | 07/12/2021 | Last 8 – Recorded Error Code Hour (24h) | unsigned 16 bits | R | Details in Error List document |
| 252 | x | x | 07/12/2021 | Last 8 – Recorded Error Code Minute | unsigned 16 bits | R | Details in Error List document |
| 253 | x | x | 07/12/2021 | Last 9 – Recorded Error Code | unsigned 16 bits | R | Details in Error List document |
| 254 | x | x | 07/12/2021 | Last 9 – Recorded Error Code Year (4digit) | unsigned 16 bits | R | Details in Error List document |
| 255 | x | x | 07/12/2021 | Last 9 – Recorded Error Code Month | unsigned 16 bits | R | Details in Error List document |
| 256 | x | x | 07/12/2021 | Last 9 – Recorded Error Code Day | unsigned 16 bits | R | Details in Error List document |
| 257 | x | x | 07/12/2021 | Last 9 – Recorded Error Code Hour (24h) | unsigned 16 bits | R | Details in Error List document |
| 258 | x | x | 07/12/2021 | Last 9 – Recorded Error Code Minute | unsigned 16 bits | R | Details in Error List document |
| 259 | x | x | 07/12/2021 | Last 10 – Recorded Error Code | unsigned 16 bits | R | Details in Error List document |
| 260 | x | x | 07/12/2021 | Last 10 – Recorded Error Code Year (4digit) | unsigned 16 bits | R | Details in Error List document |
| 261 | x | x | 07/12/2021 | Last 10 – Recorded Error Code Month | unsigned 16 bits | R | Details in Error List document |
| 262 | x | x | 07/12/2021 | Last 10 – Recorded Error Code Day | unsigned 16 bits | R | Details in Error List document |
| 263 | x | x | 07/12/2021 | Last 10 – Recorded Error Code Hour (24h) | unsigned 16 bits | R | Details in Error List document |
| 264 | x | x | 07/12/2021 | Last 10 – Recorded Error Code Minute | unsigned 16 bits | R | Details in Error List document |
| 301 | x | 01/01/2022 | Device ID Input Breaker -1 | unsigned 16 bits | R | 0:Close, 1:Open 2: No Information (If Com status=Unknown; This data is meaningless) |
|
| 302 | x | 01/01/2022 | Device ID Input Breaker -2 | unsigned 16 bits | R | ||
| 303 | x | 01/01/2022 | Device ID Input Breaker -3 | unsigned 16 bits | R | ||
| 304 | x | 01/01/2022 | Device ID Input Breaker -4 | unsigned 16 bits | R | ||
| 305 | x | 01/01/2022 | Device ID Input Breaker -5 | unsigned 16 bits | R | ||
| 306 | x | 01/01/2022 | Device ID Input Breaker -6 | unsigned 16 bits | R | ||
| 307 | x | 01/01/2022 | Device ID Input Breaker -7 | unsigned 16 bits | R | ||
| 308 | x | 01/01/2022 | Device ID Input Breaker -8 | unsigned 16 bits | R | ||
| 309 | x | 01/01/2022 | Device ID Input Breaker -9 | unsigned 16 bits | R | ||
| 310 | x | 01/01/2022 | Device ID Input Breaker -10 | unsigned 16 bits | R | ||
| 311 | x | 01/01/2022 | Device ID Input Breaker -11 | unsigned 16 bits | R | ||
| 312 | x | 01/01/2022 | Device ID Input Breaker -12 | unsigned 16 bits | R | ||
| 313 | x | 01/01/2022 | Device ID Input Breaker -13 | unsigned 16 bits | R | ||
| 314 | x | 01/01/2022 | Device ID Input Breaker -14 | unsigned 16 bits | R | ||
| 315 | x | 01/01/2022 | Device ID Input Breaker -15 | unsigned 16 bits | R | ||
| 316 | x | 01/01/2022 | Device ID Input Breaker -16 | unsigned 16 bits | R |
| 351 | x | 01/01/2022 | Device ID Output Breaker -1 | unsigned 16 bits | R | 0:Close, 1:Open 2: No Information (If Com status=Unknown; This data is meaningless) |
|
| 352 | x | 01/01/2022 | Device ID Output Breaker -2 | unsigned 16 bits | R | ||
| 353 | x | 01/01/2022 | Device ID Output Breaker -3 | unsigned 16 bits | R | ||
| 354 | x | 01/01/2022 | Device ID Output Breaker -4 | unsigned 16 bits | R | ||
| 355 | x | 01/01/2022 | Device ID Output Breaker -5 | unsigned 16 bits | R | ||
| 356 | x | 01/01/2022 | Device ID Output Breaker -6 | unsigned 16 bits | R | ||
| 357 | x | 01/01/2022 | Device ID Output Breaker -7 | unsigned 16 bits | R | ||
| 358 | x | 01/01/2022 | Device ID Output Breaker -8 | unsigned 16 bits | R | ||
| 359 | x | 01/01/2022 | Device ID Output Breaker -9 | unsigned 16 bits | R | ||
| 360 | x | 01/01/2022 | Device ID Output Breaker -10 | unsigned 16 bits | R | ||
| 361 | x | 01/01/2022 | Device ID Output Breaker -11 | unsigned 16 bits | R | ||
| 362 | x | 01/01/2022 | Device ID Output Breaker -12 | unsigned 16 bits | R | ||
| 363 | x | 01/01/2022 | Device ID Output Breaker -13 | unsigned 16 bits | R | ||
| 364 | x | 01/01/2022 | Device ID Output Breaker -14 | unsigned 16 bits | R | ||
| 365 | x | 01/01/2022 | Device ID Output Breaker -15 | unsigned 16 bits | R | ||
| 366 | x | 01/01/2022 | Device ID Output Breaker -16 | unsigned 16 bits | R | ||
| 401 | x | 01/01/2022 | Communication Status Device ID 1 | unsigned 16 bits | R | Other:Unknown 1:Master, 2:Slave, | |
| 402 | x | 01/01/2022 | Communication Status Device ID 2 | unsigned 16 bits | R | ||
| 403 | x | 01/01/2022 | Communication Status Device ID 3 | unsigned 16 bits | R | ||
| 404 | x | 01/01/2022 | Communication Status Device ID 4 | unsigned 16 bits | R | ||
| 405 | x | 01/01/2022 | Communication Status Device ID 5 | unsigned 16 bits | R | ||
| 406 | x | 01/01/2022 | Communication Status Device ID 6 | unsigned 16 bits | R | ||
| 407 | x | 01/01/2022 | Communication Status Device ID 7 | unsigned 16 bits | R | ||
| 408 | x | 01/01/2022 | Communication Status Device ID 8 | unsigned 16 bits | R | ||
| 409 | x | 01/01/2022 | Communication Status Device ID 9 | unsigned 16 bits | R | ||
| 410 | x | 01/01/2022 | Communication Status Device ID 10 | unsigned 16 bits | R | ||
| 411 | x | 01/01/2022 | Communication Status Device ID 11 | unsigned 16 bits | R | ||
| 412 | x | 01/01/2022 | Communication Status Device ID 12 | unsigned 16 bits | R | ||
| 413 | x | 01/01/2022 | Communication Status Device ID 13 | unsigned 16 bits | R | ||
| 414 | x | 01/01/2022 | Communication Status Device ID 14 | unsigned 16 bits | R | ||
| 415 | x | 01/01/2022 | Communication Status Device ID 15 | unsigned 16 bits | R | ||
| 416 | x | 01/01/2022 | Communication Status Device ID 16 | unsigned 16 bits | R | ||
| 451 | x | 01/01/2022 | Work Status Device ID 1 | unsigned 16 bits | R | 0:Off, 1:On (If Com status=Unknown; This data is meaningless) |
|
| 452 | x | 01/01/2022 | Work Status Device ID 2 | unsigned 16 bits | R | ||
| 453 | x | 01/01/2022 | Work Status Device ID 3 | unsigned 16 bits | R | ||
| 454 | x | 01/01/2022 | Work Status Device ID 4 | unsigned 16 bits | R | ||
| 455 | x | 01/01/2022 | Work Status Device ID 5 | unsigned 16 bits | R | ||
| 456 | x | 01/01/2022 | Work Status Device ID 6 | unsigned 16 bits | R | ||
| 457 | x | 01/01/2022 | Work Status Device ID 7 | unsigned 16 bits | R | ||
| 458 | x | 01/01/2022 | Work Status Device ID 8 | unsigned 16 bits | R | ||
| 459 | x | 01/01/2022 | Work Status Device ID 9 | unsigned 16 bits | R | ||
| 460 | x | 01/01/2022 | Work Status Device ID 10 | unsigned 16 bits | R | ||
| 461 | x | 01/01/2022 | Work Status Device ID 11 | unsigned 16 bits | R | ||
| 462 | x | 01/01/2022 | Work Status Device ID 12 | unsigned 16 bits | R |
| 463 | x | 01/01/2022 | Work Status Device ID 13 | unsigned 16 bits | R | ||
| 464 | x | 01/01/2022 | Work Status Device ID 14 | unsigned 16 bits | R | ||
| 465 | x | 01/01/2022 | Work Status Device ID 15 | unsigned 16 bits | R | ||
| 466 | x | 01/01/2022 | Work Status Device ID 16 | unsigned 16 bits | R |
man-stab-imp1 rev1.3 250403 ita-eng FW 7.2.8.docx
FIRMWARE VERSION 7.2.8