Z1T-ND Single Function Timer Relay
Instruction Manual
- Sleek design with NEW 18 mm width in accordance with DIN norm
- Conforms to IEC 61812-1+ UL 508
- Wide power supply range (12-240 V AC/DC)
- SPDT relay output (10A)
- Wide and easily adjustable time range
- LED notifications
- High sensitivity and switching capacity
- High mechanical endurance
STEP 1
| Model Name Z1A-ND30s |
Order No 261025 |
Mode ND |
Relay Count 1 CIO |
Time Range 1 sec .. 30 sec |
|
| Z1A-ND100s | 261023 | ND | 1 CIO | 1 sec .. 100 sec | |
| Z1T-ND100s | 261010 | ND | 1 CIO | 1 sec .. 100 sec | |
| Z1T-PFD120m-24 | 261011 | PFD | 1 CIO | 1 sec .. 120 min | |
| Z1T-PFD120s-24 | 261030 | PFD | 1 CIO | 1 sec .. 120 sec | |
| Z1T-NDX | 261012 | ND | 1 CIO | 0 sec .. 5109 sec | |
| Z1T-FDF | 261013 | FDF | 1 CIO | 0.1 sec .. 10 days | |
| Z1T-NDF | 261014 | NDF | 1 CIO | 0.1 sec .. 10 days | |
| Z1T-ND100s.2 | 261026 | ND | 2 CIO | 1 sec .. 100 sec |
| Operating Voltage | 12..240V AC/DC ±10% 24..240V AC/DC ±10% (for Z1T-PFD120m-24, Z1T-PFD120m/s-24) 24V AC/DC (A2-A3 ye 180 .. 265V AC (Al -A3) (for Z1 A-xxx) |
|
| Operating Frequency | 45..65Hz | |
| Power Consumption | DC | < 1.5 W < 8 W (for Z1T-PFD120m-24) |
| AC | < 5 VA < 8 VA (for Z1T-PFD120m-24) |
|
| Relay Outputs | Maximum Switching (Voltage/Current/Power) |
115 VAC / 10A / 1250 VA 250VAC / 5 A / 1250 VA 250VAC / 16A / 4000 VA (for Z1T-PFD120m/s-24 ) |
| Cable Cross Section | 2.5mm2 / AWG 14-30 solid or stranded | |
| Screw Tightening Torque | 0.5 Nm / 4.5 lb-inch | |
| Cable Stripping Size (Min / Max) | 8mm / 9mm | |
| Operating Temperature Range | -20 / +60 °C | |
| Max Surrounding Air Temperature | 60°C (55°C for Z1T-PFD120m/s-24) | |
| Protection Degree (IEC 60529) | IP 20 | |
| Pollution Degree | 2 | |
NOTE: The charging time of the Z1T-PFD120m-24 product varies between 3 seconds and 1 minute, and the charging time of the Z1T-PFD120s-24 product varies between 3 and 10 seconds.
NOTE: Use 60/75°C copper (CU) wire only.
![]()
Doc.No.9.0.0.9.040156 www.klemsan.com.tr Rev. No.16092025
USER ASSISTANT
SETTING THE TIMER RELAY
Z1A-ND30s Z1A-ND100s
Z1T-ND-100s Z1T-ND-100s.2
STEP 1
Check the device model name and understand which operating modes your device supports.
STEP 2
Set time range from the pot No.3 in Z1A-ND30s Z1A-ND100s
Set time range from the pots No.3 Z1T-ND-100s Z1T-ND-100s.2
Example → For t = 20 seconds → (Z1A-ND30s Z1A-ND100s) Set pot no.3 to 20s
Example→ Forte = 100 seconds → (Z1T-ND-100s Z1T-ND-100s.2) Set pot no.3: t1 to 90s + t2 to 10s
Please disconnect the power before adjusting the timers, device will start with the new settings after connecting the power
STEP 1
| OPERATION MODI | FUNCTION ILLUSTRATION | FUNCTION STATEMENT |
| Mode: ND On Delay |
The output relay is initially de-energized and energized after an adjustable time delay, toff. | |
| Mode:FDF OFF Flash |
The output relay is initially de-energized and energized after an adjustable time delay, toff, and stays energized for an adjustable period, ton, and then de-energized. This loop is repeated until the device is powered off. | |
| Mode:NDF ON Flash |
The output relay is initially energized and de-energized after an adjustable time delay, ton, and stays de-energized for an adjustable period, toff, and then energized. This loop is repeated until the device is powered off. | |
| Mode:PFD Power-Off Delay |
The output relay is initially energized and the device starts to charge. When the device is power off, the output relay remains energized until the adjusted time. The loop starts again when the device is power on. |
![]()
USER ASSISTANT
SETTING THE TIMER RELAY
Z1T-PDF120m-24
Z1T-PDF120s-24
STEP 1
Check the device model name and understand which operating modes your device supports.
STEP 2
Example → For ton = 100 seconds→ Set pot no.3 to 100s and pot no.4 to 1
Example → For toff = 50 seconds → (Z1T-FDF Z1T-NDF) Set pot no.4 to 100s and pot no.4 to .5
Example → Fort = 45 minutes→ (Z1T-PDF120m-24) Set pot no.3 to 45m and pot no.4 to 1
Example→ Fort = 45 seconds → (Z1T-PDF120s-24) Set pot no.3 to 45s and pot no.4 to 1
Z1T-FDF Z1T-NDF
Please disconnect the power before adjusting the timers, device will start with the new settings after connecting the power
![]()
USER ASSISTANT
SETTING THE TIMER RELAY
Z1T-NDX
STEP 1
Check the device model name and understand which operating modes your device supports.
STEP 2
Select the desired time adjustment by the mode selection switches N.3
For more information review Table No.1
Set time range from the pots No.4 and No.5
Example →For toff = 60 minutes→ Mode (1,2,3)=1, Mode(4,5,6,8)=0, Xtm-4,Xt a = 4
Time adjustment formula: toff: (t1+..+18)xtm+ta
Please disconnect the power before adjusting the timers, device will start with the new settings after connecting the power