KNX RF Multi Operating Top Unit
Technical data
Ambient conditions
- Ambient temperature -5 … +45 °C
- Storage/transport temperature -25 … +70 °C
- Relative humidity max. 93 % (no condensation)
KNX
- KNX medium RF1.M
- Safety KNX Data Secure (X-mode)
- Commissioning mode S mode
- Radio frequency 868.3 MHz, 868.95 MHz, 869.85 MHz, 869.525 MHz
- Transmission capacity max. 20 mW
- Transmitting range in free field Typ. 100 m
- Receiver category 2
- Information according to ErP 2009/125/EC
- Electronic room temperature controller yes
Power consumption
- In idle state <0.5 W
- In standby mode with information and status display yes
- This controller fulfils the following control functions TE(1/2/3/0/0/0/0/0)
Safety instructions
- To avoid potential damage, read and follow the following instructions:
- Electric devices may only be mounted and connected by electrically skilled persons.
- Danger of electric shock. Always disconnect before carrying out work on the device or load. In so doing, take all the circuit breakers into account, which support dangerous voltages to the device and or load.
- The radio communication takes place via a non exclusively available transmission path, and is therefore not suitable for safety related applications, such as emergency stop and emergency call.
- Instructions are part of the product. So keep them in a safe place.
Device components
Front view 1-gang (see figure 1) and 2-gang (see figure 2)
- Rockers
- Status LED
- Cover frame
- System 3000 insert

Function
System information
- This device is a product of the KNX system and complies with the KNX directives. Detailed technical knowledge obtained in KNX training courses is a prerequisite for proper understanding.
- The function of the device depends on the software. Detailed information on software versions and the respective scope of functions as well as the software itself can be obtained from the manufacturer’s product database.
- The device can be updated. The firmware is easy to update with the Gira ETS Service app (additional software).
- The device is KNX Data Secure capable. KNX Data Secure offers protection against manipulation in building automation and can be configured in the ETS project. Detailed technical knowledge is a prerequisite. A device certificate, which is attached to the device, is required for safe commissioning. During mounting, the device certificate must be removed from the device and stored securely.
- The range of a radio system depends on various external circumstances. The range can be optimized by the choice of installation location. The product documentation and system documentation for this device contains application basics for the KNX RF system.
- The device is planned, installed and commissioned with version 6.3.0 or higher of the ETS.
Intended use
- Operation of loads, e.g. light on/off, dimming of brightness and color temperature, color control with color run and brightness adjustment, Venetian blinds up/down, value transmitter 1-byte, 2-bytes, 3-bytes and 6-bytes, bright-ness values, temperatures, calling up and saving of light scenes
- Operation in cabled KNX systems via media coupler (see section Accessories)
- Operation of switching, dimming, Venetian blind or room temperature insert or three wire extension unit of the System 3000
Product characteristics
- Activation of blind/shutters, with Venetian blind insert
- Switching and dimming of lighting, with switching or dimming insert
- Dimming and color temperature control of lighting, with DALI insert TW
- Room temperature control, with room temperature control insert
- Push button sensor functions switching, dimming, color control, Venetian blind, value transmitter, scene extension unit, 2-channel operation and controller extension adjustable
- Two or four push buttons for rocker or push button function
- Controller extension with adjustable operating mode selection, forced operating mode switch over, presence function and setpoint shift
- Status LED – optionally red, green, blue – adjustable per rocker
- LED functions orientation lighting and night reduction can be set separately
- Brightness of LED adjustable and switchable while in operation
- Disable or function switch over of all or of individual button functions possible with disabling function
- Temperature measurements optionally with device internal sensor and external sensor connected via communication object (only with suitable inserts) Temperature measurements are only possible in combination with the follow-ing inserts:
- “Relay switching insert”
- “Electronic switching insert”
- “Flush mounted DALI Power control unit insert”
- “Blind control insert with auxiliary input”
- “Blind control insert without auxiliary input”
- “Room temperature controller insert with sensor connection”
- “Auxiliary insert 3-wire”
For accurate temperature measurement, make sure that the connected loads do not exceed 40 W for the electronic switch insert.
To ensure good transmission quality, keep a sufficient distance from any possible sources of interference, e.g. metallic surfaces, microwave ovens, hi-fi and TV systems, ballasts or transformers.
Operation
The operation of functions or electrical consumers can be set individual for each device:
| Operating concept | Single area operation | Dual area operation |
| Rocker function | – | Each rocker can perform an individual function. |
| Button function | Two push buttons above one another perform the same function. | Each button can perform an individual function. |
Operating concept
The operating concept can be configured in the ETS either as a rocker function or alternatively as a button function. With the rocker function, two buttons lying one above the other are combined into one rocker. In the button function, each button is evaluated as single-area operation.

Examples for operating various standard applications
- Switch: Short press on button.
- Dim: Long press on button. The dimming process ends when the button is released.
- Move Venetian blind: Long press on button.
- Stop or adjust Venetian blind: Short press on button.
- Set value, e.g. brightness or temperature setpoint: Short press on button.
- Open scene: Short press on button.
- Save scene: Long press on button.
- Execute channel 1: Short press on button.
- Execute channel 2: Long press on button.
- Operate controller extension: Short press on button.
Insert cover alignment
The device combination of insert and cover carries out an automatic insert cover alignment as soon as a cover is placed on an insert and the mains voltage is switched on.
- Case 1: Insert and cover are brand new
After the insert cover alignment, the device combination is functional in a standard configuration. - Case 2: Insert is brand new and cover was already in operation
After the insert cover alignment, the device combination is functional in a standard configuration. - Case 3: Insert was already in operation and cover is brand new
After the insert cover alignment, the device combination is functional in a standard configuration. - Case 4: Insert and cover were already in operation in combination
After the insert cover alignment, the device combination is functional. The device combination performs its function according to its last configuration. - Case 5: Insert and cover were already in operation separately from one another After the insert cover alignment, the device combination is not functional. The insert cover alignment identifies this case as a swapping of the covers, for example after renovating a room. The insert cover alignment reports an error via the status LED.
This device combination becomes functional again after programming with the ETS, a master reset or resetting to factory settings. - Case 6: Insert is not supported by the cover
The insert cover alignment reports an error via the status LED if the cover has been placed on an insert not supported by the cover. The device combination is not functional.
Error message
- The error reported by the insert cover alignment is indicated by the status LED for 60 seconds. Within these 60 seconds, the status LED flashes 3 times in pulses.
- After an error has been detected during insert cover alignment, the new assignment of a device combination of insert and cover is only possible via the ETS. The device combination remains without function until a new ETS is commissioned.
- The 60-second signaling of the error is restarted each time the button is actuated.
- The 2-gang device variant indicates the error message via the left status LED.
- A firmware update is also possible in the event of an error.
As delivered state
The device combination of insert and cover functions in the delivery state after successful insert cover alignment. The cover is for local use in a standard configuration.
- The device combination does not transmit RF telegrams.
- The ETS can reset the device to the delivery state with the “Unload device” command.
Status LED in the delivery state
The status LEDs perform the “Actuation indicator” function in the delivery state. Each push button or rocker actuation causes the associated green status LED to illuminate for 3 seconds.
Information for electrically skilled persons
Mounting and electrical connection
DANGER!
- Electric shock when live parts are touched.
- Electric shocks can be fatal.
- Always disconnect device before carrying out work on it. To do so, switch off all corresponding circuit breakers, secure them against being switched on again and check that there is no voltage. Cover up any adjacent live parts.
Mounting and connecting the device
In secure operation (prerequisites):
- Secure commissioning has been activated in the ETS.
- Device certificate entered/scanned or added to the ETS project. A high resolution camera should be used to scan the QR code.
- Document all passwords and keep them safe.
- The insert must be disconnected from the power supply before plugging in or unplugging the RF Multi operating top unit.
When using a three-wire extension unit in combination with a KNX RF operating cover, wiring the extension unit connections between the main unit and extension unit is not permitted, as this will cause interference.
Switching, dimming, Venetian blind or room temperature controller insert or three wire extension unit are mounted and connected properly (see instructions of the relevant inserts).
The mains voltage has been switched off.
- Fit the cover with frame on the insert (see figure 1).
- Switch on mains voltage.
- In secure operation: The device certificate must be removed from the device and stored securely.
- The device can be commissioned and is ready for operation.
- If the status LED flashes red three times at repeated intervals, the cover was previously connected to another insert. To enable operation again, either place the cover on the associated insert or put the device combination into operation with the ETS.
- When switching to another application, the device should always be reset to the default setting and then reprogrammed.
Commissioning
Programming the physical address and application program, 1-gang (see figure 5) and 2-gang (see figure 6)
- Project design and commissioning with ETS from version 6.3.0 and above.
- The RF Multi operating top unit works with the RF/TP media coupler (order no. 5110 00) from index I01. An update file for older RF/TP media couplers can be found on our website.

Precondition: The device is connected and ready for operation.
Activate programming mode: Press the top right button and bottom right button simultaneously and hold for longer than 4 seconds with 1-gang (see figure 5) and 2-gang (see figure 6).
The Status LED flashes red. Programming mode is activated.
When the programming mode is activated, telegrams can be sent to the bus.
Programming the physical address.
The status LED returns to its previous state. Physical address is programmed.
Prerequisite for the “Dimming” function: Load is connected to the insert.
- Programming the application program.
- The status LED is switched off while the application program is programmed. As soon as the programming is successfully completed, the status LED carries out its parameterized function.
- Relevant for “dimming” and for devices of device generation I00 and I01 (no longer relevant from device generation I02): The load must be connected before ETS commissioning. Without a connected load, the ETS aborts the programming process of the application program.
- When the application program is unloaded, the status LEDs behave as in the delivery state.
Safe state mode and master reset
Safe state mode
- The safe state mode stops the execution of the loaded application program.
- If the device does not work properly for instance as a result of errors in the project design or during commissioning the execution of the loaded application program can be halted by activating the safe state mode. The device remains passive in safe state mode, since the application program is not being executed (state of execution: terminated).
Only the system software of the device is still functional. ETS diagnosis functions and programming of the device are possible.
Activating safe state mode
- Switch off the voltage.
- Wait approx. 15 s.
- Press the top right and bottom right button.
- With the buttons pressed, switch the voltage back on and keep the buttons pressed for more than 10 seconds.
- Safe state mode is activated. The status LED flashes red slowly (approx. 1 Hz).
- Only release the top right and bottom right buttons when the LED flashes.
Deactivating safe state mode
Switch off the voltage (wait approx. 15 s) or carry out ETS programming.
Master reset
The master reset restores the basic device settings (physical address 15.15.255, firmware remains in place). The device must then be recommissioned with the ETS.
- In secure operation, a master reset will deactivate the device security. The device can then be recommissioned with the device certificate.
- Devices can be reset to factory settings with the ETS Service App. This function uses the firmware included in the device that was active at the time of delivery (delivery state). Restoring the factory settings causes the devices to lose their physical address and configuration.
If the device for instance as a result of errors in the project design or during commissioning does not work properly, the loaded application program can be deleted from the device by performing a master reset. The master reset resets the device to delivery state. Afterwards, the device can be put into operation again by programming the physical address and application program.
Performing a master reset
Prerequisite: safe-state mode is activated.
- Press and hold down the top right and bottom right button for more than 5 seconds until the status LED flashes.
- Release the top right button and bottom right button.
- The device performs a master reset. The status LED flashes quickly (approx. 4 Hz).
- The device restarts and is in delivery state.
Product information in accordance with the Ecodesign Directive (ErP 2009/125/EC)
| Contact details:
Gira Giersiepen GmbH & Co. KG, Dahlienstraße, 42477 Radevormwald, Germany |
|||
| Model identifier:
RF Multi operating top unit, 1-gang , 5104 .., 5105 .., 5106 .. RF Multi operating top unit, 2-gang , 5107 .., 5108 .. |
|||
| Specification | Icon | Value | Unit |
| Power consumption | |||
| In the off state | P0 | – | W |
| In standby mode | Psm | – | W |
| In idle state | Pidle | <0.5 | W |
| In networked standby mode |
Pnsm |
– | W |
| In standby mode with information or status display | yes | ||
| Type | |||
| Single-stage heat output,
no room temperature control |
no | ||
| Two or more manual levels, no room temperature control | no | ||
| Room thermostat with mechanical thermostat | no | ||
| Electronic room temperature controller | yes | ||
| Electronic room temperature controller with time-of-day control | no | ||
| Electronic room temperature controller with weekday regulation | no | ||
| Other control options | |||
| Presence detection | yes | ||
| Detection of open windows | yes | ||
| Remote control option | yes | ||
| Adaptive control of the start of heating | no | ||
| Operating time limit | no | ||
| Black ball sensor | no | ||
| Self-learning function | no | ||
| Control accuracy | no | ||
Codes of the control functions
The format of the code is TC (f1/f2/f3/f4/f5/f6/f7/f8), where TC is the code for temperature control and f1 to f8 are the codes for the respective control functions, if avail-able; otherwise “0” must be specified.
| (TC)* | Control functions | |||||||||
| f1 | f2 | f3 | f4 | f5 | f6 | f7 | f8 | |||
| Type of temperature control | Single-stage heat output, no room temperature control | NC | ||||||||
| Two or more manual levels, no room temperature control | TX | |||||||||
| Room thermostat with mechanical thermostat | TM | |||||||||
| Electronic room temperature controller | HP | |||||||||
| Electronic room temperature controller with daytime control | TD | |||||||||
| Electronic room thermostat with weekday control | TW | |||||||||
| Control functions | Presence detection | 1 | ||||||||
| Detection of open windows | 2 | |||||||||
| Remote control option | 3 | |||||||||
| Adaptive control of the start of heating | 4 | |||||||||
| Operating time limit | 5 | |||||||||
| Black ball sensor | 6 | |||||||||
| Self-learning function | 7 | |||||||||
| Control accuracy with CA < 2 Kelvin and CSD < 2 Kelvin | 8 | |||||||||
* Temperature control code
Warranty
The warranty is provided by the specialist trade in accordance with statutory requirements. Please submit or send faulty devices postage paid together with a fault description to your responsible salesperson (specialist trade / installation company /electrical specialist trade). They will forward the devices to the Gira Service Center.
Gira
- Tel +49(0)21 95 – 602-0
- Fax +49(0)21 95 – 602-191
- www.gira.de
- info@gira.de
Documents / Resources
![]() | RF Multi Operating Top Unit |
References
- Sucheb.gira.de
- Sucheb.gira.de
- Sucheb.gira.de
- Schalter, Steckdosen & smarte Technik | Girawww.gira.de
- User Manualmanual.tools