TROX CHM-35 Wall Diffuser Chm

Installation
- Ensure all personnel involved have carefully read and understood the manual before starting any work.
- Comply with all safety instructions to avoid accidents, injuries, and property damage.
- Mount the diffuser face with front plate and front rails securely to the wall using the provided mounting brackets.
- Adjust the air control blade as needed for optimal airflow distribution.
- Connect the standard spigot to the ventilation system.
- Install volume flow limiter type VFL if required.
Safety
Follow the safety notes and signal words provided in the manual to ensure safe installation and operation of the wall diffuser. Beaware of potential hazards and take necessary precautions.
General Information
- This manual is intended for use by fitting and installation companies, technicians, and qualified personnel.
- Ensure the system owner receives this manual and includes it with the system documentation.
- Refer to project-specific documents and product data sheet for additional information.
FAQ
- Q: What should I do if I encounter a potentially hazardous situation during installation?
- A: Follow the safety instructions provided in the manual, assess the situation, and take appropriate measures to mitigate the risk.
- Q: Can I adjust the volume flow limiter on the wall diffuser?
- A: Yes, the volume flow limiter type VFL can be adjusted as needed for proper airflow control. Refer to the manual for detailed instructions.
Product Overview

- Diffuser face consisting of front plate and front rails
- Adjustable air control blade
- Plenum box
- Mounting brackets for wall mounting (wall thickness 90 – 130 mm)
- Spigot, prepared for the installation of a volume flow limiter
- Volume flow limiter type VFL (to be ordered separately)
- Standard spigot
- Damper blade
- Lip seal
- Splitters (removable from room side)
General
Information on this manual
This manual is intended for use by fitting and installation companies, in-house technicians, technical staff, instructed persons, and qualified electricians or air conditioning technicians. The personnel must have carefully read and understood this manual before starting any work. The basic prerequisite for safe working is to comply with all safety notes and instructions in this manual. The local regulations for health and safety at work and the general safety regulations for the area of application of the ventilation unit also apply. This manual must be given to the system owner when handing over the system. The system owner must include the manual with the system documentation. This manual must be kept in a place that is accessible at all times. Illustrations in this manual are mainly for information and may differ from the actual design.
Other applicable documentation
- Project-specific documents (if any)
- Product data sheet
Explanation of symbols
Safety notes
Symbols are used in this manual to alert readers to areas of potential hazard. Signal words express thedegree of the hazard. Comply with all safety instructions and proceed carefully to avoid accidents, injuries and damage to property.

Tips and recommendations
Useful tips and recommendations as well as information for efficient and fault-free operation
Safety notes in the operating instructions
Safety notes can refer to specific, individual instructions. Such safety instructions are embedded in the instructions so that they do not interrupt the flow of reading when carrying out the task. The above listed signal words will be used.
Example:
- Loosen the screw.
- CAUTION!
Risk of jamming on the lid!
Close the lid carefully. - Tighten the screw
Additional markers
In order to highlight instructions, results, lists, references and other elements, the following markers are used in this manual:

TROX Technical Service
To ensure that your request is processed as quickly as possible, please keep the following information ready:
- Product name
- TROX order number
- Delivery date
- Brief description of the fault
Online www.troxtechnik.com
Phone +49 2845 202-400
Claims for material defects
The provisions of the respective General Terms and Conditions of Delivery apply to claims for material defects. For purchase orders placed with TROX GmbH, see Section VI, Warranty Claims, of the Delivery and Payment Terms of TROX GmbH,
www.trox.de/en/
Copyright
This documentation – including all illustrations – is protected by copyright and pertains only to the corresponding product. Any use outside the limits of copyright law is not permitted without our consent and will result in compensation for damages.
This applies in particular to:
- Publication
- Reproduction
- Translation
- Saving and processing in electronic systems
Safety
Personnel
Qualification
HVAC technician
HVAC technicians are individuals who have sufficient professional or technical training in the field they are working in to enable them to carry out their assigned duties at the level of responsibility allocated to them and in compliance with the relevant guidelines, safety regulations and instructions. HVAC technicians are individuals who have in-depth knowledge and skills related to HVAC systems; they are also responsible for the professional completion of the work under consideration. HVAC technicians are individuals who have sufficient professional or technical training, knowledge and actual experience to enable them to work on HVAC systems, understand any potential hazards related to the work under consideration, and recognise and avoid any risks involved
Transport and storage
Trained personnel
Trained personnel are individuals who have sufficient professional or technical training, knowledge and actual experience to enable them to carry out their assigned duties, understand any potential hazards related to the work under consideration, and recognise and avoid any risks involved.
Personal protective equipment
Personal protective equipment must be worn for any work in order to reduce health or safety hazards to a minimum. The appropriate protective equipment for a job must be worn for as long as the job takes.
Industrial safety helmet

Industrial safety helmets protect the head from falling objects, suspended loads, and the effects of striking the head against stationary objects.
Protective gloves

Protective gloves protect hands from friction, abrasions, punctures, deep cuts, and direct contact with hot surfaces.
Safety shoes

Safety shoes protect the feet from crushing, and falling parts and prevent slipping on a slippery floor.
Repair and replacement parts
Only qualified personnel may repair the products, and they have to use genuine replacement parts. Transport and storage
Delivery check
After delivery, carefully remove the packaging and check the device for any transport damage and completeness. In case of transport damage or incomplete delivery, inform the forwarding agent and the supplier immediately. After inspection of the goods, put the product back into its packaging to protect it from dust and contamination.
Fixing and installing material
Unless otherwise specified, fixing and installation materials are not included in the delivery and must be provided by the client, in accordance with the respective installation situation.
Factory setting
The air control blades are factory-set to a certain position. Adjusting the air control blades leads to increased efforts during commissioning. Therefore, avoid moving the air control blades during on-site transport, unpacking and installation.
Transport on site
CAUTION!
Risk of injury from sharp edges, sharp corners, and thin sheet metal parts! Sharp edges, sharp corners and thin-walled sheet metal parts can cause abrasions and cuts to the skin.
- Be careful when carrying out any work.
- Wear protective gloves, safety shoes, and a hard hat.
Observe the following points during transport:
- Be careful when unloading or moving the product on site, and pay attention to the symbols and information on the packaging.
- If possible, take the product in its transport packaging up to the installation location.
- Use only lifting and transport gear designed for the required load.
- During transport, always secure the load against tipping and falling.
- Bulky equipment should be transported by at least two people to prevent injury and damage.
Storage
Observe the following points for storage:
- Store the product only in its original packaging
- Protect the product from the effects of weather
- Protect the product from humidity, dust and contamination
- Storage temperature: -10 °C to 90 °C
- relative humidity: 80 % maximum, no condensation
Packaging
After unpacking, properly dispose of packaging material.
Installation
General installation information
Observe during installation:
- For room heights up to 4 m (lower edge of ceiling)
- Wall installation in lightweight partition wall
- For cleaning purposes, the air diffusers must be easily accessible after installation.
- Fixing material provided by the manufacturer and additional material for sound insulation.
Protect the device from dust and contamination
Before installation, ensure that the air-ducting components cannot be contaminated by construction activities (VDI 6022). If this is not possible, at least cover the device or take other precautions to protect it from contamination. In this case, make sure the device is not in operation. Ensure that all components are clean before you install them. Clean thoroughly if necessary. When interrupting the installation procedure, protect all device openings from the ingress of dust or humidity.
Installation front grille
Installing the slot diffuser
Personnel:
- Trained personnel
Protective equipment:
- Industrial safety helmet
- Protective gloves
- Safety shoes

- The unit with protective foil is inserted into the drywall.
The wall is completed with panels etc. and sanded. The protective foil remains on the unit until the final coating of the wall to prevent soiling
- Installation front plate
- Mount the loose fixing material as shown.
- Insert into front rail.
- Caution, do not squeeze the clamp too tightly!
- Ensure correct fit!
- Position in the longitudinal direction.
- Insert the front rail together with the screws into the fixing holes on the plenum box.
Note:
Using an Allen key (SW4) simplifies the fixing procedure.
- Mount the front plate in the plenum box
Installation in lightweight partition walls and ceiling bulkhead
Installation in lightweight partition walls

Installation into ceiling bulkheads
Technical data
Dimensions and weights


- Supply air
- Extract air

CHM
| LN | L1 | L3 | S1 | S2 (supply air) | S3 (extract air) |
| 550 | 500 | 530 | 265 | 110 | 160 |
| 850 | 800 | 830 | 415 | 185 | 235 |
| 1000 | 950 | 980 | 490 | 235 | 260 |
| 1175 | 1125 | 1155 | 578 | 272 | 310 |
CHM Spigot
| DN | without VFL | prepared for VFL | ||
| ØD | C | ØD | C | |
| 100 | 98 | 50 | 102 | 240 |
| 125 | 123 | 48 | 127 | 260 |
CHM Weights
| LN | m [kg] | |||
| 550 | 850 | 1000 | 1175 | |
| Plenum box | 4.7 | 6.3 | 7.0 | 7.9 |
| Front plate PL35 | 1.4 | 2.1 | 2.4 | 2.8 |
| Front plate 3PL35 | 1.8 | 2.6 | 3.0 | 3.5 |
| Front plate 3PL18 | 1.6 | 2.3 | 2.6 | 3.1 |
| Front plate 2PL50 | 1.7 | 2.5 | 3.0 | 3.5 |
| Splitter | 3.8 | 4.7 | 5.1 | 5.6 |
| Total weight = plenum box + front plate + splitter (if any) | ||||
Volume flow rate

CHM Volume flow controller
| Nominal size VFL | ØD [mm] | L [mm] | m [kg] |
| 100 | 98 | 100 | 0.15 |
| 125 | 122 | 118 | 0.25 |
Setting the volume flow rate setpoint
Tool:
- Torx T9 screwdriver (provided by the client)

- Use the Torx screwdriver to set the required volume flow rate setpoint on the volume flow scale (Ä sticker).

- After setting the volume flow, the slotted hole must be sealed with the enclosed clear sticker for acoustic optimization
Installing the terminal unit Personnel:
- HVAC technician
Protective equipment:
- Industrial safety helmet
- Protective gloves
- Safety shoes
Before installation, ensure that the air-ducting components cannot be contaminated by construction activities (VDI 6022). If this is not possible, at least cover the device or take other precautions to protect it from contamination. In this case, make sure the device is not in operation. Ensure that all components are clean before you install them. Clean thoroughly if necessary. When interrupting the installation procedure, protect all device openings from the ingress of dust or humidity.
For installation, please note:
- The installed product must be accessible for maintenance and adjustments.
Avoid damage of the terminal unit:
- Always the device with care.
- Lift the device only by lifting the entire casing.
- Never lift the device by the control damper, rotary knob or actuator.

- Set the volume flow setpoint before installation,
- Push the VFL (/1) into the plenum box (/3). Observe the air direction arrow! (/2).
- Insert splitters and diffuser face into the plenum box
- Use the provided stickers to label the volume flow limiters. You can write on the stickers and affix them to the outside air duct(/4)
Setting the airflow direction
Setting the airflow direction
These are only schematic diagrams to illustrate the setting of the air control blades. The air control blades have notches on the mullions which are used for adjustment. If necessary, we recommend that you use both hands to adjust the air control blades on the notches.
Airflow
Initial commissioning
General information
Before you start commissioning, check the following points:
- Check that the air diffusers are fitted correctly.
- Remove protective foils, if any.
- Ensure that all air diffusers are clean and free from residues and foreign matter.
For commissioning, see also VDI 6022, Sheet 1 – Hygienic requirements for ventilation and air conditioning systems.
Settings VFL
- Loosen the screws in the front panel and remove the front panel
- Loosen the screws of the perforated plate and remove the perforated plate
- Settings VFL
Assembly in the same order

- Loosen the screws in the front panel and remove the front panel
- Using both handes, pull the splitter out of the holder
- Settings VFL
Assembly in the same order
Maintenance
System owner’s responsibility
WARNING!
Only authorised specialist personnel may perform the described maintenance measures. The system owner is responsible for maintenance. With their maintenance management, the system owner is responsible for creating a maintenance plan, for defining the maintenance goals, and for the functional reliability of the equipment. The legal regulations must be observed during maintenance, e.g. the system owner is responsible for hygienic operation in accordance with VDI 6022.
Maintenance and cleaning
During cleaning, the following points must be observed:
- The cleaning intervals given in the VDI 6022 standard apply.
- Clean surfaces with a damp cloth.
- Use only common household cleaners, do not use any aggressive cleaning agents.
- Do not use cleaning agents that contain chlorine.
- Do not use equipment for removing stubborn contamination, e.g., scrubbing sponges or scouring cream, as it may damage the surfaces.
Inspection measures
- Remove contamination that affects the function of the wall diffuser.
- Check all screw connections for tightness and retighten them, if necessary.
- Document the maintenance work.
Repair work
Repair work is only allowed to be carried out by specialist personnel or by the manufacturer. Only genuine replacement parts may be used.
Disposal
ENVIRONMENT!
Risk of harm to the environment due to incorrect disposal!
Incorrect disposal may harm the environment.
- Be sure to comply with the relevant national guidelines and regulations.
- In case of doubt, contact your local authorities or a specialist disposal company.
Note: The wall diffuser must be dismantled for disposal. If no disposal or return agreements with TROX GmbH are in place, we recommend disposing of the materials as follows:
| Pos. | Component | Material/ waste code | Type of dis- posal |
| 1 | Front rail, end angle | Aluminium EWC 170402 | Scrap metal recycling |
| 2 | Plenum box, spigot, front plate, perfo- rated plate, brackets for splitters | galvanised steel EWC 170404 | Scrap metal recycling |
| 3 | Air control blades | Plastic EWC 170203 | according to the EWC |
| 4 | VFL | Plastic EWC 170203 | according to the EWC |
| EWC European Waste Catalogue | |||